Ups Monitor Setup - MikroTik RouterOS v2.9 Reference Manual

Reference manual
Table of Contents

Advertisement

Packages required: ups
License required: level1
Home menu level: /system ups
Standards and Technologies:
Hardware usage: Not significant
Related Documents
Software Package Management
Description
Cabling
The APC UPS (BackUPS Pro or SmartUPS) requires a special serial cable. If no cable came with
the UPS, a cable may be ordered from APC or one can be made "in-house". Use the following
diagram:
Router Side (DB9f)
2
3
5
7
Note that you may also connect with USB if available.

UPS Monitor Setup

Home menu level: /system ups
Property Description
alarm-setting ( delayed | immediate | low-battery | none ; default: immediate ) - UPS sound alarm
setting:
• delayed - alarm is delayed to the on-battery event
• immediate - alarm immediately after the on-battery event
• low-battery - alarm only when the battery is low
• none - do not alarm
load ( read-only: percentage ) - the UPS's output load as a percentage of full rated load in Watts.
The typical accuracy of this measurement is ±3% of the maximum of 105%
manufacture-date ( read-only: text ) - the UPS's date of manufacture in the format "mm/dd/yy"
(month, day, year)
min-runtime ( time ; default: 5m ) - minimal run time remaining. After a 'utility' failure, the router
will monitor the runtime-left value. When the value reaches the min-runtime value, the router will
go to hibernate mode
Copyright 1999-2007, MikroTik. All rights reserved. Mikrotik, RouterOS and RouterBOARD are trademarks of Mikrotikls SIA.
Other trademarks and registred trademarks mentioned herein are properties of their respective owners.
APC's smart protocol
Signal
Receive
Send
Ground
CTS
Direction
IN
OUT
IN
UPS Side (DB9m)
2
1
4
6
Page 685 of 695