Page 1
Centrifugal Roof Downblast Exhaust Fans Models G and GB • General Clean Air • Light Contaminants • Seismic • High Wind • Variable Volume ® Performance data now included. March 2013...
Our Commitment ..... . 52 Codes and Certifications Greenheck Fan Corporation certifies that the Models G and GB fans shown herein are licensed to bear the AMCA Seal.
Models G and GB Spun Aluminum • Downblast Centrifugal Roof Exhaust Fans Model Comparison Drive Impeller Type Performance Location Mounting Airflow Application Type Model 6,308 1.75 44,700 3.25 * Smoke Control available on models: 101, 101HP, 121, 131, 141, 141HP, 161, 161HP, 200, 240, 300, 360, 420 and 480. ** High wind limited to sizes 300 and smaller Greenheck models G and GB centrifugal roof exhaust fans provide the industry’s best performance and...
Construction Features Models G and GB Standard Construction Features An aluminum, backward-inclined, non-overloading centrifugal wheel is utilized to generate high-efficiency and minimal sound. Wheel cones are carefully matched to the Wheel venturi for maximum efficiency. Each wheel is robotically welded and statically and dynamically balanced for long life and quiet operation.
Applications G and GB models Emergency Smoke Control - GB When you buy a Greenheck • UL/cUL Listed for 500°F for 4 hours and (260°C) model GB with the smoke 1,000°F for 15 minutes. (538°C) control option, you receive a •...
Applications G and GB models High Wind and Hurricane - G and GB Greenheck is leading the High Wind Standard for roof top fans and ventilators. Forceful winds and wind-borne debris are the cause of most hurricane damage. Hurricane winds start at 75 mph. and can exert a force of 75 pounds per square foot of pressure—or over 900 pounds on a fan and curb.
Vari-Green Motor Option ® Model G Features ® 1. Dial on Motor Control - a potentiometer (dial on Greenheck’s electronically commutated (EC) motor control) is mounted on the motor for easy Vari-Green (VG) motor combines motor speed adjustment for system balance. Simply turn technology, controllability and energy-efficiency the dial.
Vari-Green Control Options ® The Vari-Green constant pressure control is preprogramed Demand Control Ventilation for and easy to install for applications that include venting Multistory Buildings dryers, bathrooms, residential type kitchen space or industrial process exhaust. Applications requiring constant pressure or variable volume can utilize G fans with Vari-Green motors Contact fans@greenheck.com for more information.
Options and Accessories Roof Curbs High Wind and Severe Duty Roof Curbs Prefabricated roof curbs reduce installation time and GPF/GPFP/GPFR – Approved for high wind costs by ensuring compatibility between the fan, the applications up to a 75 psf wind-load rating. curb and roof opening.
Page 11
Options and Accessories Birdscreen Speed Controllers for Standard Motors Galvanized mesh is standard, optional aluminum or stainless Available for use with shaded steel rigid wire are also available. pole and permanent split capacitor (PSC) open motors on model G fans. They provide an economical means of system balancing with direct drive fans.
Typical Installations Models G and GB General Clean Air (figure 1) Factory Wired from Motor to Disconnect Models G and GB exhaust fans are designed to meet the needs of general clean air applications. Tests were conducted to assure safe, rugged and reliable fans.
Typical Installations Models G and GB Fan Inlet Connections In order to assure proper fan performance, caution must be exercised in fan placement and connection Good to the ventilation system. Obstructions, transitions, Good poorly designed elbows, improperly selected dampers, etc., can cause reduced performance, excessive noise, and increased mechanical stress.
Specifications Vari-Green ® Vari-Green Control – Indoor Air Quality – Temperature / Humidity Control to be a packaged indoor air quality control designed to regulate fan speed based on level of temperature and/or relative humidity in a space. Control shall include a Proportional Integral Derivative (PID) feedback loop and shall have labeled terminal strips for easy wiring.
Direct Drive Specifications Model G For models G-060 through G-095, the fan shall have sleeve bearing motors, carefully matched to the fan load, and furnished at specified voltage, phase and enclosure. For models G-097 through G-203, motors shall be heavy-duty ball bearing type, carefully matched to the fan load, and furnished at the specified voltage, phase and enclosure.
• All calculations and testing shall be done by a state licensed P.E., and a certified test lab. Fans shall be Greenheck model G, as specified on page 48, with high wind-resistant construction option and manufactured by Greenheck Fan Corporation in Schofield, Wisconsin, USA.
Wheels shall be Fans shall be model GB as manufactured by statically and dynamically balanced in accordance to Greenheck Fan Corporation of Schofield, AMCA Standard 204-05. Wisconsin, USA. Motors shall be heavy-duty ball bearing type, carefully matched to the fan load and furnished at the specified...
C, 60 foot building height, and a type II building. on page 50, with seismic rated construction option • Fan shall be tested in accordance with ASTM and manufactured by Greenheck Fan Corporation in E-330-02 Structural Performance of Exterior Schofield, Wisconsin, USA.