This product is designed for commercial / industrial use only. This product is not intended for use with life support or other U.S. FDA designated “critical” devices. Maximum loads must not exceed those shown on the Liebert XDF serial tag. Operate this product in an indoor environment at an ambient temperature between 35°F and 104°F (1.6°C to 40°C).
Glossary of Symbols LOSSARY OF YMBOLS Hazardous Voltage Present Note following instructions Consult user manual for additional information Indicates weight Indicates ground connection Indicates alternating current...
The unit is available in a variety of configurations to suit your electronic equipment’s environmental requirements. The self-contained, air cooled Liebert XDF is intended for installation in open areas. Installation in closed-in areas, such as in a closet, alcove or similar space, requires field-supplied ducting, an exter- nal booster fan and sufficient makeup air.
Operational Overview - Water/Glycol Cooled Model The water/glycol cooled XDF model employs a single-stage cooling system rated at 14kW to supply cooling air to the rack-mounted equipment. A bank of fans circulates this cooling air through the elec- tronic equipment in the XDF (see Figure 1). An evaporator coil extracts heat from the circulating air.
Figure 3 Component location, rear of XDF SELF-CONTAINED AIR COOLED MODEL Condenser air intakes, perforated grilles Backup ventilation damper (air exit) Service access for gauges to be inserted for testing Three-phase electrical cord, 10 feet (3m) Single-phase electrical cord, 10 feet (3m) WATER/GLYCOL COOLED MODEL Backup ventilation damper (air exit)
Figure 4 Dimensional data, self-contained, air cooled model 34-1/8" (867mm) Rack Section 24-1/8" 2-1/2" (613mm) (64mm) 79-3/4" (2026mm) FRONT 2-5/8" Cooling Section (68mm) 9-5/16" (252mm) Single-Phase Power Cord Entrance ; factory-supplied, 10' (3m) NEMA 5-15P Cover Plate Control Side LEFT SIDE 3-Phase Power Cord Entrance ;...
Figure 6 Dimensional data, all models—top, bottom and cable entry cutouts 4-1/2" TOP VIEW (114mm) 4-3/8" (112mm) 15" (381mm) 4" (102mm) Cable Entry Cutout 4-1/2" (114mm) Front Self-contained, air cooled model shown; water cooled unit dimensions are identical; water cooled unit does not have condenser fan.
XDF C OMPONENTS Standard Components—Self-Contained, Air Cooled and Water/Glycol Cooled Models 3.1.1 Frame The self-contained, air cooled XDF is 82-1/4 inches (2089mm) tall; the water/glycol cooled unit, 79-3/4 (2026) tall. The self-contained, air cooled XDF has 36U (63 inches) of usable rack height. The water/glycol cooled XDF has 42U (73-1/2 inches) of usable rack height.
3.1.5 Environmental Control The XDF supplies cooling air—68°F to 77°F (20-25°C)—to electronic equipment in the rack-mount equipment compartment. In normal operation, six fans at the right front corner of the XDF circulate cooling air through the equipment compartment. The laterally circulating air absorbs heat generated by the electronic equip- ment and transfers the heat to an evaporator coil at the right rear of the XDF.
3.1.6 Control—Liebert’s iCOM Controller The XDF is equipped with Liebert’s iCOM controller for all programming functions on the XDF. The menu-driven, 128 x 64 dot matrix graphic display shows the status of the conditioned space, set- points, alarm status and settings, event histories and the time. Refer to 10.2 - iCOM Components and Functions and 10.3 - Navigating Through the iCOM Display for details or call 800-543-2778.
Coolant Source—Water/Glycol Models The XDF water/glycol cooled models may be connected to either of two types of coolant sources: • a closed-loop water system (cooling tower) • a drycooler loop 3.2.1 Closed-Loop Water System A closed water supply system is required for efficiency and to protect the equipment from particles and other contaminants that might obstruct the system’s piping.
3.2.2 Drycooler Loop The water/glycol cooled XDF model requires an external supply of coolant, either water or glycol, to remove heat extracted from the XDF. Contact the factory for drycooler requirements when connecting multiple XDF units. For information on setting up a drycooler system, contact your local Liebert representative. Figure 11 Water/glycol cooled general arrangement with drycooler as coolant source Water/Glycol Cooled...
NSTALLATION Inspection Upon arrival of the unit, and before unpacking it, verify that the delivered equipment matches the bill of lading. Examine the packaging for any signs of mishandling or damage. Inspect all items for dam- age, visible or concealed. Report any damage immediately to the carrier and file a damage claim. Send a copy to Liebert Corporation or to your sales representative.
4.3.1 Handling the Unit While It is Packaged • If possible, transport the XDF using a forklift or pallet jack. Otherwise use a crane with belts or cables and spreader bars to protect the XDF’s sides from damage. • If using a forklift or pallet jack, make sure the forks (if adjustable) are spread to the widest dis- tance that fit under the skid.
4.3.3 Removing the XDF from Skid This unit is on casters—to prevent it from rolling, ensure that the skid is on a flat surface before removing the XDF from the skid. 1. Remove eight lag bolts from the unit tie-down brackets on the controls side of the unit. 2.
Figure 16 Roll XDF off the shipping skid Fit tabs on ramps into holes on front of skid Appropriate number of workers roll XDF ... Self-contained, air cooled unit shown; steps apply to all XDF units ... off the skid onto level surface and roll unit to installation location Installation...
XDF Site Preparation When deciding where to place your Liebert XDF, keep in mind these factors: • electricity is required to operate the compressor (208V-3ph-60Hz) and the controls and evaporator fans (120V-1ph-60Hz) • adequate ventilation and makeup air are necessary for proper equipment operation and protec- tion •...
Voltage Requirements All XDF systems require two input power circuits. Each power cord is 10 feet (3m) long. For the full load amp requirements of each option, refer to 12.1 - Optional Power Systems or the component’s user manual. 4.5.1 Voltage Input Requirements The first input connection provides power—120V-1ph-60Hz, line-to-neutral—to the controls, evapora- tor fans and condenser fan.
4.5.2 Uninterruptible Power Supply—Optional If your XDF is equipped with a UPS, it will require connection to a dedicated electrical circuit. Review the UPS’s user manual before connecting utility power to the unit. 4.5.3 MP Advanced Power Strips—Optional MP Advanced Power Strips are available in several power ranges. Consult Table 14 in 12.0 - Specifi- cations or the MP Advanced Power Strip user manual, SL-28015, for your model’s power require- ments.
Equipment Layout WARNING Risk of electric shock. Can cause injury or death. Disconnect all local and remote electric power before working within and/or installing equipment. Before installing or rearranging equipment, ensure the equipment and the UPS are switched off. Ensure that all electrical sources are disconnected. The lateral, circular flow of cooling air permits arranging equipment as required for stability if the XDF is filled or nearly filled with equipment.
Frame and Enclosure Configurations 4.8.1 Internal Mounting Rails The XDF can accommodate rack-mounted or free-standing computer and network equipment. The unit features 19-inch (483mm) rear-mount rack rails. These internal mounting rails are designed in accordance with the EIA 310D rack standard. The rails are adjustable for equipment of different sizes.
4.10 Door—Remove The XDF’s doors are removable for convenience when installing equipment. 4.10.1 Remove the Door 1. Remove the bolts securing the lower half of each two-piece hinge to the door. 2. Remove the lower half of each hinge. 3. Lift the door straight up until the pins clear the hinges.
4.11.2 Remove the Right Panel WARNING Risk of electric shock. Can cause injury or death. Disconnect all local and remote electric power before working within and/or installing equipment. To remove the right panel from the XDF: 1. Locate the four panel retainers on the outside of the right XDF panel. One retainer is in each corner of the panel.
IPING ONSIDERATIONS The XDF’s supply and return fittings are on the upper portion of the rear of the unit (see Figure 6). The 1-1/8" diameter pipes have one-inch female NPT fittings. The pipes are capped at the factory. Pip- ing connections to the XDF should be done by qualified personnel. All work must be done in compli- ance with all national and local regulations.
5.2.1 Expansion Tanks, Fluid Relief Valves and Other Devices An expansion tank must be provided for expansion and contraction of the fluid due to temperature change in this closed system. Vents are required at system high points to vent trapped air when fill- ing the system.
Drycooler Loop System 5.3.1 Glycol Solutions The percentage of glycol to water must be determined by using the lowest design outdoor temperature in which the system is operating. Table 3 indicates the solution freeze point at several concentration levels of ethylene glycol. Propylene glycol concentrations should be 1% higher than the ethylene glycol table val- ues to find the freeze point.
ILLING THE WITH Preparing the System for Filling It is important to remove any dirt, oil or metal filings that may contaminate the cooling system piping in order to prevent contamination of the coolant and fouling of the drycooler piping (IF USED). The system should be flushed thoroughly using a mild cleaning solution or high-quality water and then completely drained before charging with coolant.
LECTRICAL ONNECTIONS Power is supplied to the XDF through two factory-connected power cords (120V and 208V). For more information, refer to 4.5.1 - Voltage Input Requirements Additional electrical connections required for operation depend on the equipment installed in the XDF and remote communications desired. The XDF has slots for two communication cards, such as Liebert’s Intellislot card, and two alarm/warning hardwire connections.
Utility Power Supply The XDF’s 120V and 208V input power cords are stored for shipment in a compartment at the bottom left of the rear of the XDF. The 10 feet (3m) cords may be routed to power outlets on the floor or wall. If the power connections are overhead, the cables may be routed inside the unit and out the top.
ABLE ANAGEMENT The XDF is able to host many of the components of the Foundation cable management products. These optional items deliver a flexible solution to rack-enclosure cable problems by utilizing a patent pending platform to provide adaptive equipment and cabling support. Cable and equipment mounting options are available to meet changing requirements.
Cable Access 8.3.1 Top Cover and Back Optional sealed entrance cable bundles (cone-shaped seals and clamps) permit use of the round openings on the top of the XDF for cable entry. To bring cable through these holes: 1. Replace the plug with a sealed entrance cable bundle. 2.
TARTUP Before plugging in your electronic equipment, make sure that all power switches are in the OFF posi- tion. • Be certain there are no obstructions, wire bundles, manuals, trash, etc., in front of or on either side of the XDF. Make sure all doors are shut and sealed properly. •...
Starting the XDF The XDF is started, stopped and controlled with Liebert’s iCOM controller. Figure 28 shows the iCOM keypad. Figure 28 iCOM controller keys On/Off Key To start the XDF: 1. Press the On/Off key on the iCOM controller. 2.
10.0 O PERATION The XDF is intended for operation with its doors closed and latched. This increases efficiency and keeps out dust and humidity. With the doors closed, the XDF will achieve full capacity in ambient conditions up to 95°F (35°C) and 40 percent relative humidity.
Table 7 Keyboard icons and functions Icon Key Name On/Off Key Alarm Key Help Key ESCape Key Enter Key Increase Key (Up Arrow) Decrease Key (Down Arrow) Left and Right Arrow Keys Upper LED Lower LED Function Controls the operational state of the cooling unit. Silences an alarm.
10.3 Navigating Through the iCOM Display iCOM displays icons and text for monitoring and controlling your Liebert cooling unit. The iCOM’s default screen may be either graphical or simple (no bar graphs). Figure 30 iCOM graphical display default screen components UNIT 1 Internal Cabinet...
10.3.1 Accessing Menus and Settings Viewing Data No password is required to view data or settings. To view data: 1. From the default screen, press the Enter key to view the opening page of the six-page user menu (see Figure 32). 2.
Operation 10.4 Changing Operational Settings Changes to the XDF’s operation settings in the Set Alarms and Setpoints menus require a pass- word. 1. From the default screen, press the Enter key to view the opening page of the six-page user menu. 2.
Table 8 User menu icons Icon Name °C / °F % RH Setpoints EVENT Event Log Graphic Data Record View Network Set Alarms ALARMS Sensor Data Display Setup 1234h Total Run Hours Sleep Mode Service Contacts Description View and change internal cabinet temperature setpoint (humidity setpoint inactive on XDF) Contains last 400 events Displays temperature and humidity graphs...
10.5 Changing iCOM’s Display Settings No password is required to change the way iCOM displays data. The Display Setup submenus control how such data as temperature, date and time is shown. To change the display settings: 1. From the default screen, press the Enter key (see Figure 28) to access the user menu. 2.
10.7 Operation With the Door Open If the external ambient dew point exceeds the XDF’s internal tempera- ture, the iCOM control will flash a warning that condensation may form inside the enclosure if a door is opened. The warning is an icon of a door with an “X”...
10.8 Backup Ventilation System The XDF is equipped with a backup ventilation system that circulates ambient air through the XDF should any component of the cooling system fail or if power is lost. The backup ventilation system begins operating only after the internal temperature exceeds the ambient external temperature. If powered by a UPS, evaporator fans circulate ambient air until the XDF returns to normal opera- tion.
11.1 Periodic Maintenance The Liebert XDF requires very little maintenance. The XDF’s condenser coil must be inspected peri- odically to determine the necessary cleaning interval based on conditions at the installation site. Depending on site conditions, the coil may require cleaning as often as twice a month or as seldom as twice per year.
12.0 S PECIFICATIONS Figure 36 XDF model numbers Model Model Type Liebert Extreme Heat Density Foundation Enclosure S = Self-Contained, Air Cooled W = Water Cooled Table 10 Physical specifications Dimensions Height, In. (mm) Equipment Rack Area Width, In. (mm) Depth, In.
Table 11 Electrical specifications Electrical Data Control & Fan Supply Max Fuse or Circuit Breaker Amps Min. Supply Circuit Ampacity Receptacle required Compressor Supply Max Fuse or Circuit Breaker Amps Min. Supply Circuit Ampacity Receptacle required Condensate Pump Amps (Optional) Table 12 Total heat rejection Rating Point,...
12.2 Optional Managed Power - Advanced Power Strips, Vertical- or Horizontal-Mount MP Advanced Power Strips are available in 19" rack-mount and vertical-mount form to accommodate different installation requirements. See Mounting Method & Size in Table 14 for specific configu- rations. Table 14 MP Advanced Power Strip specifications Mounting...
Need help?
Do you have a question about the Liebert XDF and is the answer not in the manual?
Questions and answers