Terminal
Name
O
Analog input, voltage
H
+10V analog reference
AL0
Relay common contact
AL1
Relay contact, normally
closed during RUN
AL2
Relay contact, normally
open during RUN
Description
Ratings and Notes
0 to 9.6 VDC range, 10VDC
nominal, 12VDC max., input
impedance 10 kΩ
10VDC nominal, 10 mA max.
Contact rating
Max resistive load = 250VAC,
2.5A; 30VDC 3A;
Max inductive load = 250VAC,
0.2A; 30VDC 0.7A
Minimum load = 5VDC 100mA,
100VAC 10mA