Fire-Lite CRF-300 Installation Instructions

Fire-Lite CRF-300 Installation Instructions

Relay control module

Advertisement

Specifications

Normal Operating Voltage:
EOL Resistance:
Temperature Range:
Humidity:
Dimensions:
Accessories:

Before Installing

This information is included as a quick reference installation guide. Refer to the control panel installation manual for detailed system
information. If the modules will be installed in an existing operational system, inform the operator and local authority that the system
will be temporarily out of service. Disconnect power to the control panel before installing the modules.
NOTICE: This manual should be left with the owner/user of this equipment.
General Description
The CRF-300 Relay Control Module is intended for use in addressable, two-wire systems, where the individual address of each module is
selected using the built-in rotary switches. It allows a compatible control panel to switch discrete contacts by code command. The relay
contains two isolated sets of Form-C contacts, which operate as a DPDT switch and are rated in accordance with the table in the manual.
Circuit connections to the relay contacts are not supervised by the module. The module also has a panel controlled LED indicator. This
module can be used to replace an C304 module that has been configured for Form-C operation.
Compatibility Requirements
To ensure proper operation, these modules shall be connected to listed compatible system control panels only.

Mounting

The CRF-300 mounts directly to 4" square electrical boxes (see Figure 2A). The box must have a minimum depth of 2
face mounted electrical boxes (SMB500) are available.
NOTE: All wiring must conform to applicable local codes, ordinances, and regulations. When using control modules in nonpower limited
applications, the CB500 Module Barrier must be used to meet UL requirements for the separation of power-limited and
nonpower-limited terminals and wiring. The barrier must be inserted into a 4"x4"x2
be placed into the barrier and attached to the junction box (Figure 2A). The power-limited wiring must be placed into the isolated
quadrant of the module barrier (Figure 2B).
1. Install module wiring in accordance with the job drawings and appropriate wiring diagrams.
2. Set the address on the module per job drawings.
NOTE: Some panels support extended addressing. In order
to set the module above address 99 on compatible
systems, carefully remove the stop on the upper rotary
switch with thumb in the direction shown in Figure 1.
3. Secure module to electrical box (supplied by installer),
as shown in Figure 2A.
Figure 1. Controls and indicators:
LOOP
F300-04-00
CRF-300 Relay Control Module
Installation Instructions
15 to 32 VDC
Not used
32˚F to 120˚F (0˚C to 49˚C)
10% to 93% Noncondensing
4
1
/
" H x 4" W x 1
2
SMB500 Electrical Box; CB500 Barrier
9
0
7 8
9
6
5
10
8
4
11
1
3
12
13
2
7
2
1
14
0
15
TENS
6 7 8 9
5
6
3
4
3
5
4
2
1
0
ONES
ADDRESS
A78-2318-08
Fire•Lite Alarms, Inc., One Fire-Lite Place, Northford, CT 06472, 203-484-7161
1
/
" D (Mounts to a 4" square by 2
4
1
1
/
" deep box.)
8
1
/
" junction box, and the control module must
8
Figure 2A. Module mounting with barrier:
Figure 2B:
A78-2610-08
1
/
". Sur-
8
ISOLATED
QUADRANT
A78-2611-11
I56-1190-01

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the CRF-300 and is the answer not in the manual?

Questions and answers

Summary of Contents for Fire-Lite CRF-300

  • Page 1 3. Secure module to electrical box (supplied by installer), as shown in Figure 2A. Figure 1. Controls and indicators: Figure 2B: TENS 6 7 8 9 ISOLATED QUADRANT ONES ADDRESS LOOP A78-2611-11 A78-2610-08 A78-2318-08 F300-04-00 I56-1190-01 Fire•Lite Alarms, Inc., One Fire-Lite Place, Northford, CT 06472, 203-484-7161...
  • Page 2 Relay Contact Ratings: CURRENT RATING MAXIMUM VOLTAGE LOAD DESCRIPTION APPLICATION 30 VDC Resistive Non Coded 30 VDC Resistive Coded .9 A 110 VDC Resistive Non Coded .9 A 125 VAC Resistive Non Coded .5 A 30 VDC Inductive (L/R=5ms) Coded 30 VDC Inductive (L/R=2ms) Coded...

Table of Contents