Dell 3750W User Manual page 65

Online rack ups 3750w and 4200w
Hide thumbs Also See for 3750W:
Table of Contents

Advertisement

Table 14. Battery
Configuration
Battery Type
Voltage
Fuses
Type
Charging
Monitoring
Battery Runtimes*
*Battery runtimes are approximate and vary depending on the load configuration and battery charge.
Input
Filter
Figure 29. Online UPS Block Diagram
3700W: (16) 12V, 7.2 Ah internal batteries; (16) 12V, 7.2 Ah EBM
4200W: (16) 12V, 7.2 Ah internal batteries; (16) 12V, 7.2 Ah EBM
CSB GP1272 7.2 Ah or YUASA NP7-12 7Ah
3750W: 192 Vdc internal, 192 Vdc/30A EBM
4200W: 192 Vdc internal, 192 Vdc/30A EBM
Sealed, maintenance‐free, valve‐regulated, lead‐acid
Approximately 4 hours to 90% usable capacity at nominal line and no
Advanced monitoring for earlier failure detection and warning
3750W internal batteries: 5 minutes at full load/21 minutes at half load
4200W internal batteries: 5 minutes at full load/16 minutes at half load
3750W with one EBM attached: 14 minutes at full load/43 minutes at half load
4200W with one EBM attached: 11 minutes at full load/35 minutes at half load
Bypass
AC/DC
Boost
DC/DC
Charger
Battery
UPS: (1) 30A fuse
EBM: (1) 30A fuse
supplementary power supply load
DC/AC
Inverter
Output
Filter
Specifications
|
65