6.2
Activation of the protective organs
Measure whether there is a low-impedance connection between contacts 1 and 2 at connection X4 to ensure that the NC
contact of the digital output of the power storage system is closed.
Make sure that mains voltage is present at connection X1.
Activate the circuit breaker F3 of the control circuit
• The power contactor K1 activates
Activate the circuit breaker F2 of the backup supply
• The loads selected for backup power mode are now supplied in mains parallel operation
Activate the circuit breaker F1 of the power storage connection
The power storage system is now ready for configuration according to the system accompanying documentation (see section 1.1).