AIR CONDITIONER
5-unit multi-split type
DESIGN & TECHNICAL MANUAL
INDOOR
OUTDOOR
ACUH07LUAS1
ADUH07LUAS1
ACUH09LUAS1
ADUH09LUAS1
ACUH12LUAS1
ADUH12LUAS1
ACUH18LUAS1
ASU7RLF1
ASU9RLF1
ASU12RLF1
ASU15RLF1
AOU45RLXFZ
ADUH18LUAS1
ASUH07LPAS
ASUH18LPAS
ASUH09LPAS
ASUH24LPAS
ASUH12LPAS
ASUH15LPAS
ADUH24LUAS1
AGU9RLF
AGU12RLF
AGU15RLF
DR_MU002EF_17
2022.12.23

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the ACUH07LUAS1 and is the answer not in the manual?

Questions and answers

Jennifer Greer Quick
February 17, 2025

Outdoor unit platform size for air handler

Susan E. Campbell
February 19, 2025

Please show me the heads, inside and outside of head photos so I can see the components. Also what do the individual controls look like? I have ASUH15LPAS, 09LPAS, and 07LPAS on a quote from an installer but I haven't been able to read anything about them or even see them. I especially want to see the control with buttons, screen and close up view of the symbols plus something that explains the symbols.

1 comments:
Mr. Anderson
February 20, 2025

The Fujitsu ACUH07LUAS1 consists of both indoor and outdoor units. The indoor unit is a compact cassette-type air conditioner designed for multi-room systems. It includes parts such as a bracket panel, louver spring, step motor, shaft cover, drain pan, air filter, and remote controller. The outdoor unit is designed to accommodate multiple indoor units.

For the ASUH15LPAS, ASUH09LPAS, and ASUH07LPAS models, individual controls and symbols are not explicitly listed in the provided information. However, these models feature a wireless remote controller with an optional wired version. The remote controller is responsible for adjusting temperature, fan speed, and operation modes, but specific button layouts and symbols are not detailed in the given content.

This answer is automatically generated

Summary of Contents for Fujitsu ACUH07LUAS1

  • Page 1 AIR CONDITIONER 5-unit multi-split type DESIGN & TECHNICAL MANUAL ACUH07LUAS1 ADUH07LUAS1 ADUH18LUAS1 ADUH24LUAS1 ACUH09LUAS1 ADUH09LUAS1 ACUH12LUAS1 ADUH12LUAS1 ACUH18LUAS1 INDOOR ASU7RLF1 ASUH07LPAS ASUH18LPAS AGU9RLF ASU9RLF1 ASUH09LPAS ASUH24LPAS AGU12RLF ASU12RLF1 ASUH12LPAS AGU15RLF ASU15RLF1 ASUH15LPAS OUTDOOR AOU45RLXFZ DR_MU002EF_17 2022.12.23...
  • Page 2 • Product specifications and design are subject to change without notice for future improvement. • For further details, please check with our authorized dealer. Trademarks ™ FGLair is trademark of Fujitsu General Limited in the United States, other countries or both. ™ Google Play is trademark of Google LLC. ®...
  • Page 3: Table Of Contents

    CONTENTS Part 1. INDOOR UNIT................1 1. Model lineup ....................2 1-1. Indoor unit connection patterns..................3 2. Specifications....................6 2-1. Compact cassette type ....................6 2-2. Slim duct type ........................7 2-3. Wall mounted type (ASU7-15RLF1).................9 2-4. Wall mounted type (ASUH07-15LPAS)................10 2-5. Wall mounted type (ASUH18-24LPAS)................11 2-6.
  • Page 4 CONTENTS (continued) 11. External input and output (Compact cassette type and slim duct type indoor unit) ....................86 11-1.External input ........................87 11-2.External output......................88 11-3.Combination of external input and output..............89 11-4.Details of function ......................92 12. External input and output (RLF1 series wall mounted type and floor type indoor unit) ....................120 12-1.External input ......................120 12-2.External output......................123...
  • Page 5 CONTENTS (continued) 18-1.Controllers ........................226 18-2.Cassette grille ......................227 18-3.Others .........................228 19. Indoor unit installation precautions ............233 19-1.Places where prohibited for use..................233 19-2.Points to remember when installing ................233...
  • Page 6 CONTENTS (continued) Part 2. OUTDOOR UNIT..............237 1. Specifications....................238 2. Dimensions....................240 2-1. Model: AOU45RLXFZ ....................240 3. Installation space ..................241 3-1. Model: AOU45RLXFZ ....................241 4. Refrigerant circuit ..................244 4-1. Model: AOU45RLXFZ ....................244 5. Wiring diagram ..................245 5-1. Model: AOU45RLXFZ ....................245 6. Capacity table....................246 6-1.
  • Page 7: Part 1. Indoor Unit

    Part 1. INDOOR UNIT COMPACT CASSETTE TYPE: ACUH07/09/12/18LUAS1 SLIM DUCT TYPE: ADUH07/09/12/18/24LUAS1 WALL MOUNTED TYPE: ASU7/9/12/15RLF1 ASUH07/09/12/15LPAS ASUH18/24LPAS FLOOR TYPE: AGU9/12/15RLF...
  • Page 8: Model Lineup

    1. Model lineup Indoor unit ACUH07LUAS1 ADUH07LUAS1 ADUH18LUAS1 ACUH09LUAS1 ADUH09LUAS1 ACUH12LUAS1 ADUH12LUAS1 ACUH18LUAS1 ADUH24LUAS1 ASU7RLF1 ASUH07LPAS ASU9RLF1 ASUH09LPAS ASU12RLF1 ASUH12LPAS ASU15RLF1 ASUH15LPAS ASUH18LPAS AGU9RLF ASUH24LPAS AGU12RLF AGU15RLF Outdoor unit AOU45RLXFZ - 2 - 1. Model lineup...
  • Page 9: Indoor Unit Connection Patterns

    1-1. Indoor unit connection patterns  5 units NOTE: The optional kit UTP-MU45A2 is necessary for the following 2-unit combination sys- tems, including ASUH24LPAS. (Marked with * in the table below) • ASUH24LPAS and ASU12RLF1 • ASUH24LPAS and ASU15RLF1 Outdoor unit: AOU45RLXFZ Unit 1 Unit 2 Unit 3...
  • Page 10 Outdoor unit: AOU45RLXFZ Unit 1 Unit 2 Unit 3 Unit 4 Unit 5 Total — — — — — — — — — — — — — — — — — — — — — — — — — — —...
  • Page 11 Outdoor unit: AOU45RLXFZ Unit 1 Unit 2 Unit 3 Unit 4 Unit 5 Total 7: 7,000Btu/h, 9: 9,000Btu/h, 12: 12,000Btu/h, 15: 14,000Btu/h, 18: 18,000Btu/h, 24: 24,000Btu/h - 5 - 1-1. Indoor unit connection patterns 1. Model lineup...
  • Page 12: Specifications

    2. Specifications 2-1. Compact cassette type Model name ACUH07LUAS1 ACUH09LUAS1 ACUH12LUAS1 ACUH18LUAS1 Power supply 208/230 V ~ 60 Hz Available voltage range 187—264 V Capacity Btu/h class 7,000 9,000 12,000 18,000 Input power Running current 0.15 0.19 0.30 HIGH 318 (540)
  • Page 13: Slim Duct Type

    2-2. Slim duct type Model name ADUH07LUAS1 ADUH09LUAS1 ADUH12LUAS1 Power supply 208/230 V ~ 60 Hz Available voltage range 187—264 V Capacity Btu/h class 7,000 9,000 12,000 Input power Running current 0.30 0.35 HIGH 324 (550) 353 (600) 382 (650) 288 (490) 324 (550) 353 (600)
  • Page 14 Model name ADUH18LUAS1 ADUH24LUAS1 Power supply 208/230 V ~ 60 Hz Available voltage range 187—264 V Capacity Btu/h class 18,000 24,000 Input power Running current 0.44 0.66 HIGH 553 (940) 783 (1330) 518 (880) 730 (1240) Cooling 483 (820) 647 (1100) QUIET 441 (750) 606 (1030)
  • Page 15: Wall Mounted Type (Asu7-15Rlf1)

    2-3. Wall mounted type (ASU7-15RLF1) Model name ASU7RLF1 ASU9RLF1 ASU12RLF1 ASU15RLF1 Power supply 208/230 V ~ 60 Hz Available voltage range 187—264 V Capacity Btu/h class 7,000 9,000 12,000 14,000 Input power Running current 0.13 0.15 0.19 0.25 HIGH 330 (560) 353 (600) 388 (660) 430 (730)
  • Page 16: Wall Mounted Type (Asuh07-15Lpas)

    2-4. Wall mounted type (ASUH07-15LPAS) Model name ASUH07LPAS ASUH09LPAS ASUH12LPAS ASUH15LPAS Power supply 208/230 V ~ 60 Hz Available voltage range 187—264 V Capacity Btu/h class 7,000 9,000 12,000 14,000 Input power Running current 0.18 0.20 0.24 0.35 HIGH 383 (650) 412 (700) 412 (700) 453 (770)
  • Page 17: Wall Mounted Type (Asuh18-24Lpas)

    2-5. Wall mounted type (ASUH18-24LPAS) Model name ASUH18LPAS ASUH24LPAS Power supply 208/230 V ~ 60 Hz Available voltage range 187—264 V Capacity Btu/h class 18,000 24,000 Input power Running current 0.32 0.46 HIGH 530 (900) 642 (1,090) 471 (800) 530 (900) Cooling 377 (640) 471 (800)
  • Page 18: Floor Type

    2-6. Floor type Model name AGU9RLF AGU12RLF AGU15RLF Power supply 208/230 V ~ 60 Hz Available voltage range 187—264 V Capacity Btu/h class 9,000 12,000 14,000 Input power Running current 0.15 0.18 0.20 HIGH 312 (530) 353 (600) 383 (650) 259 (440) 288 (490) 306 (520)
  • Page 19: Dimensions

    3. Dimensions 3-1. Compact cassette type ¢ Models: ACUH07LUAS1, ACUH09LUAS1, ACUH12LUAS1, and ACUH18LUAS1 Unit: in (mm) Grid type grille Hanging bolt position 24-7/16 (620) 20-7/8 (530) IR receiver 2-15/16 (75) View A Drain hose 1-3/5 11-1/4 11-1/4 5-5/16 9-13/16 (40)
  • Page 20 ¢ Installation space requirement Unit: in (mm) Strong and durable ceiling 11 (262) or more 40 (1,000) 40 (1,000) or more or more 99 (2,500) or more Obstruction Floor Maximum height from floor to ceiling [Unit: in (mm)] Standard 107 (2,700) High ceiling 119 (3,000) 3-way direction setting:...
  • Page 21: Slim Duct Type

    3-2. Slim duct type ¢ Models: ADUH07LUAS1, ADUH09LUAS1, and ADUH12LUAS1 Unit: in (mm) 22-5/8 (574) 2 (51) View A Rear view Drain port 3-15/16 (100) x 6 = 23-5/8 (600) 1-7/8 (47) 25-9/16 (650) 2-3/16 (55) 3-1/16 (78) 28-7/8 (734) 3-1/2 (89) 1-7/8 (48) 4-11/16 (119)
  • Page 22 ¢ Model: ADUH18LUAS1 Unit: in (mm) 2 (51) 30-1/2 (774) Rear view View A Drain port 1-7/8 (47) 3-15/16 (100) × 8 = 31-1/2 (800) 2-3/16 (55) 33-7/16 (850) 3-1/16 (78) 36-3/4 (934) 3-7/16 3-1/2 (89) (87) 4-11/16 (119) Top view 2-3/16 6-7/16 (56)
  • Page 23 ¢ Model: ADUH24LUAS1 Unit: in (mm) 38-3/8 (974) 2 (51) Rear view View A Drain port 3-15/16 (100) x 10 = 39-3/8 (1,000) 1-7/8 (47) 2-3/16 (55) 3-1/16 (78) 41-5/16 (1,050) 44-5/8 (1,134) 3-1/2 (89) 4-11/16 (119) 3-7/16 (87) Top view 6-9/16 (167) 2-3/16 (56) 1-11/16 (43)
  • Page 24 ¢ Installation space requirement Provide sufficient installation space for product safety. In ceiling-concealed installations: Unit: in (mm) 12 (300) or more Strong and durable ceiling 1 (20) or more Indoor unit Left Right side side 1 (20) or more 16 (400) 6 (150) Service access Ceiling...
  • Page 25 ¢ Maintenance space requirement For future maintenance and maintenance access, provide sufficient maintenance space. NOTE: Do not place any wiring or illumination in the maintenance space, as they will impede ser- vice. Unit: in (mm) Maintenance access Unit Control 12 (300) or more Maintenance space - 19 -...
  • Page 26: Wall Mounted Type

    3-3. Wall mounted type ¢ Models: ASU7RLF1, ASU9RLF1, ASU12RLF1, and ASU15RLF1 Unit: in (mm) 33-1/16 (840) 8 (203) (33-1/16 (840)) 13-7/8 (353) 3-1/16 (78) 1-3/4 (45) 14-5/16 (364) Ø2-9/16 (Ø65) Ø2-9/16 (Ø65) for pipe inlet for pipe inlet 3-7/16 4-9/16 12-3/8 (315) 12-5/8 (321) (88)
  • Page 27  Installation space requirement Unit: in (mm) Outline of unit 1 (25) or more 3 (52) or more 3 (70) 6 (130) or more 60 (1,500) or more or more - 21 - 3-3. Wall mounted type 3. Dimensions...
  • Page 28 ¢ Models: ASUH07LPAS, ASUH09LPAS, ASUH12LPAS, and ASUH15LPAS Unit: in (mm) 32-13/16 (834) 8-3/4 (222) 1/8 (3.0) (32-13/16 [834]) 2-5/8 (67) 12-7/8 (327) 12-7/8 (327) 4-7/16 (113) Outline of indoor unit for pipe inlet Ø 2-9/16 (65) for pipe inlet Ø 2-9/16 (65) 2-7/16 (62) 2-1/2 (64) 1-7/8 (48)
  • Page 29  Installation space requirement Provide sufficient installation space for product safety. Unit: in (mm) 2 (40) or more 3 (70) or more Wall hook bracket 5 (107) or more Outline of the indoor unit 8 (183) or more 60 (1,500) or more A: Install so that the flare connection part is outdoors.
  • Page 30 ¢ Models: ASUH18LPAS and ASUH24LPAS Unit: in (mm) 38-9/16 (980) 9-7/16 (240) 16-7/16 (417) 19 (482) 20-1/16 (510) 3-1/16 16-1/4 (413) 15-3/4 (400) 3-9/16 (77) (90) Outline of indoor unit for pipe inlet for pipe inlet Ø3-1/8 (80) Ø3-1/8 (80) 3-9/16 2-13/16 2-1/16 (52)
  • Page 31  Installation space requirement Provide sufficient installation space for product safety. Unit: in (mm) 2 (40) or more Wall hook bracket 3 (70) or more Outline of the indoor unit 7 (160) or more 5 (117) or more 60 (1,500) or more - 25 - 3-3.
  • Page 32: Floor Type

    3-4. Floor type ¢ Models: AGU9RLF, AGU12RLF, and AGU15RLF Unit: in (mm) 7-7/8 (200) 29-1/8 (740) Side view Front view ¢ Installation space requirement Unit: in (mm) 4 (100) or more 4 (80) or more 4 (80) or more 2 (50) or more 5 (150) or less - 26 -...
  • Page 33: Wiring Diagrams

    4. Wiring diagrams 4-1. Compact cassette type ¢ Models: ACUH07LUAS1, ACUH09LUAS1, ACUH12LUAS1, and ACUH18LUAS1 - 27 - 4-1. Compact cassette type 4. Wiring diagrams...
  • Page 34: Slim Duct Type

    4-2. Slim duct type ¢ Models: ADUH07LUAS1, ADUH09LUAS1, ADUH12LUAS1, ADUH18LUAS1, and ADUH24LUAS1 - 28 - 4-2. Slim duct type 4. Wiring diagrams...
  • Page 35: Wall Mounted Type

    4-3. Wall mounted type ¢ Models: ASU7RLF1, ASU9RLF1, ASU12RLF1, and ASU15RLF1 - 29 - 4-3. Wall mounted type 4. Wiring diagrams...
  • Page 36 ¢ Models: ASUH07LPAS, ASUH09LPAS, ASUH12LPAS, and ASUH15LPAS - 30 - 4-3. Wall mounted type 4. Wiring diagrams...
  • Page 37 ¢ Models: ASUH18LPAS and ASUH24LPAS - 31 - 4-3. Wall mounted type 4. Wiring diagrams...
  • Page 38: Floor Type

    4-4. Floor type ¢ Models: AGU9RLF, AGU12RLF, and AGU15RLF - 32 - 4-4. Floor type 4. Wiring diagrams...
  • Page 39: Air Velocity And Temperature Distributions

    5. Air velocity and temperature distributions 5-1. Compact cassette type ¢ Model: ACUH07LUAS1 (4-way air outlet) Fan speed Operation mode Ceiling mode Measuring conditions HIGH STANDARD (ft) Unit: ft/s (m/s) 1 (0.25) 2 (0.5) 3 (1.0) 7 (2.0) 3 (1.0) 7 (2.0)
  • Page 40 ¢ Model: ACUH09LUAS1 (4-way air outlet) Fan speed Operation mode Ceiling mode Measuring conditions HIGH STANDARD Unit: ft/s (m/s) (ft) 1 (0.25) 2 (0.5) 3 (1.0) 7 (2.0) Top view Horizontal louver: Upward 1 (0.25) 3 (1.0) 1 (0.25) 7 (2.0) 3 (1.0) 2 (0.5) 1 (0.25)
  • Page 41 ¢ Model: ACUH12LUAS1 (4-way air outlet) Fan speed Operation mode Ceiling mode Measuring conditions HIGH STANDARD (ft) Unit: ft/s (m/s) 1 (0.25) 2 (0.5) 3 (1.0) 7 (2.0) 7 (2.0) 3 (1.0) 2 (0.5) 2 (0.5) Top view Horizontal louver: Upward 1 (0.25) 7 (2.0) 1 (0.25)
  • Page 42 ¢ Model: ACUH18LUAS1 (4-way air outlet) Fan speed Operation mode Ceiling mode Measuring conditions HIGH STANDARD Unit: ft/s (m/s) (ft) 1 (0.25) 2 (0.5) 3 (1.0) 7 (2.0) 7 (2.0) 2 (0.5) 2 (0.5) 3 (1.0) 3 (1.0) Top view Horizontal louver: Upward 1 (0.25) 1 (0.25)
  • Page 43: Slim Duct Type

    5-2. Slim duct type ¢ Model: ADUH07LUAS1 NOTE: This data is measured after installing optional Auto louver grille kit. Fan speed Operation mode Measuring conditions HIGH • Air velocity distribution (ft) Unit: ft/s (m/s) Top view 7 (2) 3 (1) 2 (0.5) Horizontal louver: Up Vertical louver: Center...
  • Page 44 Fan speed Operation mode Measuring conditions HIGH HEAT • Air velocity distribution (ft) Unit: ft/s (m/s) 7 (2) Side view Horizontal louver: Down 3 (1) Vertical louver: Center 2 (0.5) (ft) • Air temperature distribution (ft) Unit: °F (°C) 86 (30) 82 (28) Side view 79 (26)
  • Page 45 ¢ Model: ADUH09LUAS1 NOTE: This data is measured after installing optional Auto louver grille kit. Fan speed Operation mode Measuring conditions HIGH • Air velocity distribution (ft) Unit: ft/s (m/s) Top view 7 (2) 3 (1) 2 (0.5) Horizontal louver: Up Vertical louver: Center (ft) (ft)
  • Page 46 Fan speed Operation mode Measuring conditions HIGH HEAT • Air velocity distribution (ft) Unit: ft/s (m/s) 7 (2) Side view Horizontal louver: Down Vertical louver: Center 3 (1) 2 (0.5) (ft) • Air temperature distribution (ft) Unit: °F (°C) 86 (30) Side view 82 (28) Horizontal louver: Down...
  • Page 47 ¢ Model: ADUH12LUAS1 NOTE: This data is measured after installing optional Auto louver grille kit. Fan speed Operation mode Measuring conditions HIGH • Air velocity distribution (ft) Unit: ft/s (m/s) Top view 7 (2) 3 (1) 2 (0.5) Horizontal louver: Up Vertical louver: Center (ft) (ft)
  • Page 48 Fan speed Operation mode Measuring conditions HIGH HEAT • Air velocity distribution (ft) Unit: ft/s (m/s) 7 (2) Side view Horizontal louver: Down 3 (1) Vertical louver: Center 2 (0.5) (ft) • Air temperature distribution (ft) Unit: °F (°C) 86 (30) Side view 82 (28) Horizontal louver: Down...
  • Page 49 ¢ Model: ADUH18LUAS1 NOTE: This data is measured after installing optional Auto louver grille kit. Fan speed Operation mode Measuring conditions HIGH • Air velocity distribution (ft) Unit: ft/s (m/s) Top view 7 (2) 3 (1) 2 (0.5) Horizontal louver: Up Vertical louver: Center (ft) (ft)
  • Page 50 Fan speed Operation mode Measuring conditions HIGH HEAT • Air velocity distribution (ft) Unit: ft/s (m/s) 7 (2) Side view Horizontal louver: Down Vertical louver: Center 3 (1) 2 (0.5) (ft) • Air temperature distribution (ft) Unit: °F (°C) 86 (30) Side view 82 (28) Horizontal louver: Down...
  • Page 51 ¢ Model: ADUH24LUAS1 NOTE: This data is measured after installing optional Auto louver grille kit. Fan speed Operation mode Measuring conditions HIGH • Air velocity distribution (ft) Unit: ft/s (m/s) Top view 3 (1) 7 (2) 2 (0.5) Horizontal louver: Up Vertical louver: Center (ft) (ft)
  • Page 52 Fan speed Operation mode Measuring conditions HIGH HEAT • Air velocity distribution (ft) Unit: ft/s (m/s) 7 (2) Side view Horizontal louver: Down Vertical louver: Center 3 (1) 2 (0.5) (ft) • Air temperature distribution (ft) Unit: °F (°C) 86 (30) Side view Horizontal louver: Down 82 (28)
  • Page 53: Wall Mounted Type

    5-3. Wall mounted type ¢ Model: ASU7RLF1 Fan speed Operation mode Measuring conditions HIGH Unit: ft/s (m/s) (ft) 7 (2.0) Top view 3 (1.0) 2 (0.5) Horizontal louver: Up Vertical louver: Center (ft) Unit: ft/s (m/s) (ft) 3 (1.0) 7 (2.0) 2 (0.5) Top view Horizontal louver: Up...
  • Page 54 ¢ Model: ASU9RLF1 Fan speed Operation mode Measuring conditions HIGH Unit: ft/s (m/s) (ft) 7 (2.0) Top view 3 (1.0) 2 (0.5) Horizontal louver: Up Vertical louver: Center (ft) (ft) Unit: ft/s (m/s) 3 (1.0) 7 (2.0) 2 (0.5) Top view Horizontal louver: Up Vertical louver: Left &...
  • Page 55 ¢ Model: ASU12RLF1 Fan speed Operation mode Measuring conditions HIGH Unit: ft/s (m/s) (ft) 7 (2.0) Top view 3 (1.0) 2 (0.5) Horizontal louver: Up Vertical louver: Center (ft) Unit: ft/s (m/s) (ft) 3 (1.0) 7 (2.0) 2 (0.5) Top view Horizontal louver: Up Vertical louver: Left &...
  • Page 56 ¢ Model: ASU15RLF1 Fan speed Operation mode Measuring conditions HIGH Unit: ft/s (m/s) (ft) Top view 7 (2.0) 3 (1.0) 2 (0.5) Horizontal louver: Up Vertical louver: Center (ft) (ft) Unit: ft/s (m/s) 7 (2.0) 2 (0.5) 3 (1.0) Top view Horizontal louver: Up 3 (1.0) Vertical louver: Left &...
  • Page 57 ¢ Models: ASUH07LPAS, ASUH09LPAS, and ASUH12LPAS Fan speed Operation mode Measuring conditions HIGH (ft) Unit: ft/s (m/s) Top view 7 (2.0) 5 (1.5) 3 (1.0) 2 (0.5) Horizontal louver: Up Vertical louver: Center (ft) (ft) Unit: ft/s (m/s) 8 (2.5) 7 (2.0) 2 (0.5) 3 (1.0)
  • Page 58 ¢ Model: ASUH15LPAS Fan speed Operation mode Measuring conditions HIGH (ft) Unit: ft/s (m/s) Top view 5 (1.5) 3 (1.0) 7 (2.0) 2 (0.5) Horizontal louver: Up Vertical louver: Center (ft) (ft) Unit: ft/s (m/s) 8 (2.5) 7 (2.0) 2 (0.5) 3 (1.0) Top view Horizontal louver: Up...
  • Page 59 ¢ Model: ASUH18LPAS Fan speed Operation mode Measuring conditions HIGH Unit: ft/s (m/s) (ft) Top view 7 (2.0) 3 (1.0) 2 (0.5) Horizontal louver: Up Vertical louver: Center (ft) Unit: ft/s (m/s) (ft) 7 (2.0) 2 (0.5) 3 (1.0) Top view Horizontal louver: Up Vertical louver: Left &...
  • Page 60 ¢ Model: ASUH24LPAS Fan speed Operation mode Measuring conditions HIGH Unit: ft/s (m/s) (ft) Top view 7 (2.0) 3 (1.0) 2 (0.5) Horizontal louver: Up Vertical louver: Center (ft) (ft) Unit: ft/s (m/s) 7 (2.0) 2 (0.5) 3 (1.0) Top view Horizontal louver: Up Vertical louver: Left &...
  • Page 61: Floor Type

    5-4. Floor type ¢ Models:AGU9RLF, AGU12RLF, and AGU15RLF Fan speed Operation mode Fan select Measuring conditions HIGH Upper and lower (ft) Unit: ft/s (m/s) 3(1.0) 2(0.5) Top view Horizontal louver: Up Vertical louver: Center UPPER LOWER (ft) Unit: ft/s (m/s) (ft) 2(0.5) 3(1.0)
  • Page 62: Fan Performance

    6. Fan performance NOTE: Airflow and capacity/outlet temperature curve data are measured based on the same condi- tions mentioned in "Specifications". 6-1. Slim duct type ¢ Model: ADUH07LUAS1 0.44 (110) 0.40 (100) Hi (SP mode 09) 0.36 (90) SP mode 09 upper limit 0.32 (80) 0.28 (70)
  • Page 63  Characteristics of air volume and capacity • Cooling Capacitty (600) (700) (400) (500) (800) Airflow (CFM [m 3 /h]) • Heating Capacitty (600) (700) (400) (500) (800) Airflow (CFM [m 3 /h]) - 57 - 6-1. Slim duct type 6.
  • Page 64 ¢ Model: ADUH09LUAS1 0.44 (110) 0.40 (100) Hi (SP mode 09) 0.36 (90) SP mode 09 upper limit 0.32 (80) 0.28 (70) Quiet (SP mode 09) 0.24 (60) SP mode 09 lower limit 0.20 (50) 0.16 (40) Normal SP upper limit 0.12 (30) Quiet (Normal SP) Hi (Normal SP)
  • Page 65  Characteristics of air volume and capacity • Cooling Capacity (600) (700) (400) (500) (800) Airflow (CFM [m 3 /h]) • Heating Capacity (600) (700) (400) (500) (800) Airflow (CFM [m 3 /h]) - 59 - 6-1. Slim duct type 6.
  • Page 66 ¢ Model: ADUH12LUAS1 0.44 (110) 0.40 (100) SP mode 09 upper limit Hi (SP mode 09) 0.36 (90) 0.32 (80) 0.28 (70) 0.24 (60) Quiet (SP mode 09) SP mode 09 lower limit 0.20 (50) 0.16 (40) Normal SP upper limit 0.12 (30) Quiet (Normal SP) Hi (Normal SP)
  • Page 67  Characteristics of air volume and capacity • Cooling Capacity (600) (700) (500) (800) (900) Airflow (CFM [m 3 /h]) • Heating Capacity (600) (700) (500) (800) (900) Airflow (CFM [m 3 /h]) - 61 - 6-1. Slim duct type 6.
  • Page 68 ¢ Model: ADUH18LUAS1 0.44 (110) SP mode 09 0.40 (100) upper limit 0.36 (90) Hi (SP mode 09) Quiet (SP mode 09) 0.32 (80) 0.28 (70) 0.24 (60) SP mode 09 lower limit Normal SP 0.20 (50) upper limit Quiet (Normal SP) 0.16 (40) 0.12 (30) SP mode 00...
  • Page 69  Characteristics of air volume and capacity • Cooling Capacity (800) (900) (1,100) (1,000) (700) Airflow (CFM [m 3 /h]) • Heating Capacity (800) (900) (1,100) (1,000) (700) Airflow (CFM [m 3 /h]) - 63 - 6-1. Slim duct type 6.
  • Page 70 ¢ Model: ADUH24LUAS1 0.32 (80) 0.28 (70) SP mode 05 upper limit 0.24 (60) Hi (SP mode 05) Quiet (SP mode 05) 0.20 (50) 0.16 (40) Normal SP upper limit 0.12 (30) Quiet (Normal SP) 0.08 (20) SP mode 05 lower limit SP mode 00 Hi (Normal SP)
  • Page 71  Characteristics of air volume and capacity • Cooling Capacitty (1,100) (1,200) (1,300) (1,500) (800) (900) (1,000) (1,400) (1,600) Airflow (CFM [m 3 /h]) • Heating Capacitty (1,100) (1,200) (1,300) (1,500) (800) (900) (1,000) (1,400) (1,600) Airflow (CFM [m 3 /h]) - 65 - 6-1.
  • Page 72: Airflow

    • 3.6 m /h = 1 l/s • 1.699 m /h = 1 CFM 7-1. Compact cassette type Airflow Model Operation mode Fan speed HIGH Cooling QUIET ACUH07LUAS1 HIGH Heating QUIET HIGH Cooling QUIET ACUH09LUAS1 HIGH Heating QUIET HIGH Cooling...
  • Page 73: Slim Duct Type

    7-2. Slim duct type Airflow Model Operation mode Fan speed HIGH Cooling QUIET ADUH07LUAS1 HIGH Heating QUIET HIGH Cooling QUIET ADUH09LUAS1 HIGH Heating QUIET HIGH Cooling QUIET ADUH12LUAS1 HIGH Heating QUIET HIGH Cooling QUIET ADUH18LUAS1 HIGH Heating QUIET HIGH 1330 1240 Cooling 1100...
  • Page 74: Wall Mounted Type

    7-3. Wall mounted type Airflow Model Operation mode Fan speed HIGH Cooling QUIET ASU7RLF1 HIGH Heating QUIET HIGH Cooling QUIET ASU9RLF1 HIGH Heating QUIET HIGH Cooling QUIET ASU12RLF1 HIGH Heating QUIET HIGH Cooling QUIET ASU15RLF1 HIGH Heating QUIET - 68 - 7-3.
  • Page 75 Airflow Model Operation mode Fan speed HIGH Cooling QUIET ASUH07LPAS HIGH Heating QUIET HIGH Cooling QUIET ASUH09LPAS HIGH Heating QUIET HIGH Cooling QUIET ASUH12LPAS HIGH Heating QUIET HIGH Cooling QUIET ASUH15LPAS HIGH Heating QUIET HIGH Cooling QUIET ASUH18LPAS HIGH Heating QUIET HIGH 1,090...
  • Page 76: Floor Type

    7-4. Floor type Airflow Model Operation mode Fan speed HIGH Cooling QUIET AGU9RLF HIGH Heating QUIET HIGH Cooling QUIET AGU12RLF HIGH Heating QUIET HIGH Cooling QUIET AGU15RLF HIGH Heating QUIET - 70 - 7-4. Floor type 7. Airflow...
  • Page 77: Noise Level Curve

    8. Noise level curve 8-1. Compact cassette type ¢ Model: ACUH07LUAS1  Cooling  Heating NC-65 NC-65 NC-60 NC-60 NC-55 NC-55 NC-50 NC-50 NC-45 NC-45 NC-40 NC-40 HIGH HIGH NC-35 NC-35 NC-30 NC-30 NC-25 NC-25 QUIET QUIET NC-20 NC-20 NC-15...
  • Page 78 ¢ Model: ACUH12LUAS1  Cooling  Heating NC-65 NC-65 NC-60 NC-60 NC-55 NC-55 NC-50 NC-50 HIGH NC-45 NC-45 HIGH NC-40 NC-40 NC-35 NC-35 NC-30 NC-30 NC-25 NC-25 QUIET QUIET NC-20 NC-20 NC-15 NC-15 1,000 2,000 4,000 8,000 1,000 2,000 4,000 8,000 Octave band center frequency, Hz Octave band center frequency, Hz...
  • Page 79: Slim Duct Type

    8-2. Slim duct type ¢ Model: ADUH07LUAS1  Cooling  Heating NC-65 NC-65 NC-60 NC-60 NC-55 NC-55 NC-50 NC-50 NC-45 NC-45 NC-40 NC-40 NC-35 NC-35 HIGH HIGH NC-30 NC-30 NC-25 NC-25 NC-20 NC-20 QUIET QUIET NC-15 NC-15 1,000 2,000 4,000 8,000 1,000 2,000...
  • Page 80 ¢ Model: ADUH12LUAS1  Cooling  Heating NC-65 NC-65 NC-60 NC-60 NC-55 NC-55 NC-50 NC-50 NC-45 NC-45 NC-40 NC-40 NC-35 NC-35 HIGH HIGH NC-30 NC-30 NC-25 NC-25 QUIET QUIET NC-20 NC-20 NC-15 NC-15 1,000 2,000 4,000 8,000 1,000 2,000 4,000 8,000 Octave band center frequency, Hz Octave band center frequency, Hz...
  • Page 81 ¢ Model: ADUH24LUAS1  Cooling  Heating NC-65 NC-65 NC-60 NC-60 NC-55 NC-55 NC-50 NC-50 NC-45 NC-45 NC-40 HIGH NC-40 HIGH NC-35 NC-35 NC-30 NC-30 QUIET NC-25 QUIET NC-25 NC-20 NC-20 NC-15 NC-15 1,000 2,000 4,000 8,000 1,000 2,000 4,000 8,000 Octave band center frequency, Hz Octave band center frequency, Hz...
  • Page 82: Wall Mounted Type

    8-3. Wall mounted type ¢ Model: ASU7RLF1  Cooling  Heating NC-65 NC-65 NC-60 NC-60 NC-55 NC-55 NC-50 NC-50 NC-45 NC-45 HIGH HIGH NC-40 NC-40 NC-35 NC-35 NC-30 NC-30 NC-25 NC-25 QUIET NC-20 NC-20 NC-15 NC-15 QUIET 1,000 2,000 4,000 8,000 1,000 2,000...
  • Page 83 ¢ Model:ASU12RLF1  Cooling  Heating NC-65 NC-65 NC-60 NC-60 NC-55 NC-55 NC-50 NC-50 HIGH HIGH NC-45 NC-45 NC-40 NC-40 NC-35 NC-35 NC-30 NC-30 NC-25 NC-25 QUIET NC-20 NC-20 QUIET NC-15 NC-15 1,000 2,000 4,000 8,000 1,000 2,000 4,000 8,000 Octave band center frequency, Hz Octave band center frequency, Hz ¢...
  • Page 84 ¢ Models: ASUH07LPAS and ASUH09LPAS  Cooling  Heating NC-65 NC-65 NC-60 NC-60 NC-55 NC-55 NC-50 NC-50 HIGH NC-45 NC-45 HIGH NC-40 NC-40 NC-35 NC-35 NC-30 NC-30 NC-25 NC-25 NC-20 NC-20 QUIET NC-15 NC-15 QUIET 1,000 2,000 4,000 8,000 1,000 2,000 4,000 8,000...
  • Page 85 ¢ Models: ASUH18LPAS  Cooling  Heating NC-65 NC-65 NC-60 NC-60 NC-55 NC-55 NC-50 NC-50 HIGH HIGH NC-45 NC-45 NC-40 NC-40 NC-35 NC-35 NC-30 NC-30 NC-25 NC-25 NC-20 QUIET NC-20 QUIET NC-15 NC-15 1,000 2,000 4,000 8,000 1,000 2,000 4,000 8,000 Octave band center frequency, Hz Octave band center frequency, Hz...
  • Page 86: Floor Type

    8-4. Floor type ¢ Model: AGU9RLF  Cooling  Heating NC-65 NC-65 NC-60 NC-60 NC-55 NC-55 NC-50 NC-50 HIGH HIGH NC-45 NC-45 NC-40 NC-40 NC-35 NC-35 NC-30 NC-30 NC-25 NC-25 NC-20 NC-20 NC-15 NC-15 QUIET QUIET 1,000 2,000 4,000 8,000 1,000 2,000 4,000...
  • Page 87 ¢ Model: AGU15RLF  Cooling  Heating NC-65 NC-65 NC-60 NC-60 NC-55 NC-55 NC-50 NC-50 HIGH HIGH NC-45 NC-45 NC-40 NC-40 NC-35 NC-35 NC-30 NC-30 NC-25 NC-25 NC-20 NC-20 QUIET NC-15 NC-15 QUIET 1,000 2,000 4,000 8,000 1,000 2,000 4,000 8,000 Octave band center frequency, Hz Octave band center frequency, Hz...
  • Page 88: Sound Level Check Point

    8-5. Sound level check point ¢ Compact cassette type Microphone 60 in (1.5 m) Microphone - 82 - 8-5. Sound level check point 8. Noise level curve...
  • Page 89 ¢ Slim duct type 79 in (2 m) 40 in (1 m) Measuring duct Measuring duct Set the static pressure as rating in this area Microphone Microphone Side view Front view ¢ Wall mounted type Microphone Microphone 40 in (1 m) NOTE: Detailed shape of the actual indoor unit might be slightly different from the one illustrated above.
  • Page 90: Electrical Characteristics

    9. Electrical characteristics Power supply Indoor rated Voltage Input power Type Model name ACUH07LUAS1 0.19/0.19 18/18 0.15/0.15 ACUH09LUAS1 0.19/0.19 18/18 0.15/0.15 Compact cassette ACUH12LUAS1 0.24/0.24 22/22 0.20/0.20 ACUH18LUAS1 0.41/0.38 39/39 0.32/0.30 ADUH07LUAS1 0.40/0.38 33/33 0.32/0.30 ADUH09LUAS1 0.40/0.38 49/49 0.32/0.30 Slim duct ADUH12LUAS1 0.47/0.44...
  • Page 91: Safety Devices

    Indoor unit Fan motor thermal Terminal thermal Float Model name PCB* fuse type protector fuse switch Activate: 212 ±27°F (100 ±15°C) ACUH07LUAS1 Fan motor stop ACUH09LUAS1 Compact 250 V, 5 A ― ○ cassette Reset: 203 ±18°F ACUH12LUAS1 (95 ±10°C) ACUH18LUAS1 Fan motor restart Activate: 275 ±27°F...
  • Page 92: External Input And Output (Compact Cassette Type And Slim Duct Type Indoor Unit)

    11. External input and output (Compact cassette type and slim duct type indoor unit) • Compact cassette type Indoor unit PCB Rotary switch CN65 External input and output PCB CN47 (Ext. out) Terminal (Ext. in) • Slim duct type CN47 (Ext. out) Terminal (Ext.
  • Page 93: 11-1.External Input

    11-1. External input With using external input function, some functions on this product can be controlled from an external device. • “Operation/Stop” mode or "Forced stop" mode can be selected with function setting of indoor unit. • A twisted pair cable (22AWG) should be used. Maximum length of cable is 492 ft (150 m). •...
  • Page 94: 11-2.External Output

    11-2. External output Use an external output cable with appropriate external dimension, depending on the number of ca- bles to be installed. • A twisted pair cable (22AWG) should be used. Maximum length of cable is 82 ft (25 m). •...
  • Page 95: 11-3.Combination Of External Input And Output

    11-3. Combination of external input and output By combining the function setting of the indoor unit and rotary switch setting of the External input and output PCB, you can select various combinations of functions. Combination examples of external input and output are as follows: External input External input Function...
  • Page 96 External output External input Function and output Indoor unit Mode External input and output PCB setting PCB (Rotary Output CN47 Output 1 Output 2 Output 3 Indoor unit fan 60-00 Operation/Stop Operation/Stop Error status operation status Indoor unit fan External heater 60-00 Operation/Stop Error status...
  • Page 97 ¢ Input signal type • Indoor unit Input signal type is only "Edge". Edge • External input and output PCB The input signal type can be selected. Signal type (edge or pulse) can be switched by the DIP switch 2 (SW2) on the External input and output PCB.
  • Page 98: 11-4.Details Of Function

    11-4. Details of function ¢ Control input function  When function setting is "Operation/Stop" mode 1 • In the case of "Edge" input Rotary SW of Function External input and External input Input signal Command setting / output PCB Off → On Operation Input of indoor unit Terminal...
  • Page 99  When function setting is "Forced stop" mode • In the case of "Edge" input Rotary SW of Function External input and External input Input signal Command setting / output PCB Off → On Forced stop Input of indoor unit Terminal On →...
  • Page 100  When function setting is "Operation/Stop" mode 2 • In the case of "Edge" input Rotary SW of Function External input and External input Input signal Command setting / output PCB Off → On Operation Stop Input of indoor unit Terminal (Remote On →...
  • Page 101 ¢ Forced thermostat off function Function Rotary SW of External External input Input signal Command setting / input and output PCB 60-00 / 2 60-02 / 4 60-05 / 7 Off → On Thermostat off 60-06 / 8 External input and output Input 1 60-08 / A 60-09 / B...
  • Page 102 ¢ Error status Function Rotary SW of External External output Output signal Command setting / input and output PCB Low → High Error 60-09 / B Output of indoor unit CN47 High → Low Normal 60-00 / 2 Off → On Error 60-01 / 3 60-02 / 4...
  • Page 103 ¢ Indoor unit fan operation status Function Rotary SW of External External output Output signal Command setting / input and output PCB Low → High Fan run 60-10 / C Output of indoor unit CN47 High → Low Fan stop 60-00 / 2 Off →...
  • Page 104 ¢ External heater output Function setting Indoor unit Control Primary heater Auxiliary heater Control switching external heaters No. 61 Auxiliary heater control 1 Heat pump 61-00 External device* Auxiliary heater control 2 Heat pump External device 61-01 Heat pump prohibition External device None 61-02...
  • Page 105  Installation configuration of individual connection External heating device is installed individually. (No use of indoor unit fan) • Cassette type ON / OFF Example of heating device: - Floor heating device • Duct type On/Off Example of heating device: - Floor heating device - 99 - 11-4.
  • Page 106 WARNING • Cassette type Operation Condition • Heater is off as shown in following diagram of heating temperature. • Other than heating mode Heater off • Error occurred • Forced thermostat off CN65 SW101 CN47 • Duct type DIP Switch 101-3 must be in the ON position when ducted electric heat application is be- ing used.
  • Page 107 Return air • Inappropriate designing and installation of external heater may cause a fire by emitted heat from the external heater. • Fujitsu General Ltd. is not responsible for inappropriate designing or installation of external heating device. - 101 - 11-4.
  • Page 108  Auxiliary equipment control by room temperature Auxiliary equipment control is switchable by room temperature. Auxiliary equipment switching is per- formed for each room temperature divided to following 3 zones. Zone A Ts +0.9°F (0.5 °C) Ts: Setting temperature Ts -0.9°F (0.5 °C) Tr: Room temperature Zone B Zone C...
  • Page 109  Auxiliary heater control 1 Operation Condition Heater on Heater is on as shown in following diagram of heating temperature. • Heater is off as shown in following diagram of heating temperature. • Other than heating mode Heater off • Error occurred •...
  • Page 110  Heat pump prohibition control Perform heating by external heater only. Indoor unit is continuous thermostat off. • Compact cassette type Operation Condition Heater is on as shown in following diagram of heating Heater on temperature. • Heater is off as shown in following diagram of heating temperature.
  • Page 111 • Operation status – Compact cassette type Heating operation 0.9°F (0.5°C) Set temp. Room temperature -0.9°F (-0.5°C) Air conditioner 12 V Heater 3 min or more – Slim duct type Heating operation 0.9°F (0.5°C) Set temp. Room temperature -0.9°F (-0.5°C) Air conditioner 12 V Heater...
  • Page 112  Auxiliary heater control by outdoor temperature 1 This control selects heat pump or external heater according to the outdoor temperature. When out- door temperature is high, the heating is performed by using heat pump only. • Compact cassette type Operation Condition Heater is on as shown in following diagram of heating...
  • Page 113 • Outdoor temperature zone Outdoor temp. Heat pump only zone     (Heat pump) B + 3.6°F (2°C): 46.4°F (8°C) B: 42.8°F (6°C)*   Combination zone   (Heat pump + Heater) A + 3.6°F ( 2°C): -0.4°F (-18°C) A: -4°F (-20°C)* Heat pump prohibition zone  ...
  • Page 114  Auxiliary heater control by outdoor temperature 2 This control selects heat pump or external heater according to the outdoor temperature. Even when outdoor temperature is high, the heating is performed by using both of heat pump and external heater. •...
  • Page 115 • Outdoor temperature zone Outdoor temp. Combination zone     ( Heat pump + Heater) A + 3.6°F ( 2°C): -0.4°F (-18°C) A: -4°F (-20°C)* Heat pump prohibition zone     (Heater) *: Adjustable by function setting 666666 • Operation status –...
  • Page 116  Auxiliary heater control by outdoor temperature 3 This control selects heat pump or external heater according to the outdoor temperature. Even when outdoor temperature is high, the heating is performed by using both of heat pump and external heater. •...
  • Page 117 • Outdoor temperature zone Outdoor temp. Heat pump only zone (Heat pump) B + 3.6°F (2°C): 46.4°F (8°C) B: 42.8°F (6°C)* Combination zone (Heat pump + Heater) *: Adjustable by function setting 676767 • Operation status – Compact cassette type Heat pump only zone 46.4°F (8°C) 42.8°F (6°C)
  • Page 118  Auxiliary heat pump control • External heater output – Compact cassette type Operation Condition Heater is on as shown in following diagram of heating Heater on temperature. • Heater is off as shown in following diagram of heating temperature. •...
  • Page 119  Auxiliary heat pump control by outdoor temperature 1 • External heater output – Compact cassette type Operation Condition Heater is on as shown in following diagram of heating Heater on temperature. • Heater is off as shown in following diagram of heating temperature.
  • Page 120 • Outdoor temperature zone Outdoor temp. Combination zone     ( Heat pump + Heater) A + 3.6°F ( 2°C): -0.4°F (-18°C) *A: -4°F (-20°C)   Heater only zone   *: Adjustable by function setting 67 • Operation status – Compact cassette type 46.4°F (8°C) 42.8°F (6°C) Outdoor temperature...
  • Page 121  Auxiliary heat pump control by outdoor temperature 2 • External heater output – Compact cassette type Operation Condition Heater is on as shown in following diagram of heating Heater on temperature. • Heater is off as shown in following diagram of heating temperature.
  • Page 122 • Outdoor temperature zone Outdoor temp. Heater only zone B + 3.6°F (2°C): 46.4°F (8°C) *B: 42.8°F (6°C) Combination zone (Heat pump + Heater) *: Adjustable by function setting 67 • Operation status – Compact cassette type Heat pump prohibition zone 46.4°F (8°C) 42.8°F (6°C) Outdoor temperature...
  • Page 123  Auxiliary heat pump control by outdoor temperature 3 • External heater output – Compact cassette type Operation Condition Heater is on as shown in following diagram of heating Heater on temperature. • Heater is off as shown in following diagram of heating temperature.
  • Page 124 • Outdoor temperature zone Outdoor temp. Heater only zone     B + 3.6°F (2°C): 46.4°F (8°C) B: 42.8°F (6°C)*   Combination zone   (Heat pump + Heater) A + 3.6°F (2°C): -0.4°F (-18°C) A: -4°F (-20°C)*   Heater only zone  ...
  • Page 125 ¢ Heating thermostat on for humidifier Indoor unit Function External output setting Situation Mode Rotary SW Heating Indoor unit fan Heating thermostat on operation thermostat on no. 60 status 60-05 CN47 Example of 60-06 CN312 individual Not used 60-07 CN311 connection 60-08 CN310...
  • Page 126: External Input And Output (Rlf1 Series Wall Mounted Type And Floor Type Indoor Unit)

    12. External input and output (RLF1 series wall mounted type and floor type indoor unit) External input External output Indoor unit type Operation Fresh air Auxiliary heater Error status Control input status output control output output output Wall mounted ● ●...
  • Page 127 • Circuit diagram example • Contact capacity: DC 24 V or more, 10 mA or more. Indoor unit Connected unit control PCB • *1: PCB of Communication kit is used for wall mounted (ASU7RLF1, ASU9RLF1, ASU12RLF1, and Connector Example: Switch ASU15RLF1) type.
  • Page 128 • Optional part Indoor unit type Part name Model name ASU7RLF1, ASU9RLF1, ASU12RLF1, Wall mounted UTY-XWZXZ5 External connect ASU15RLF1 Floor AGU9RLF, AGU12RLF, AGU15RLF UTY-XWZXZ5 UTY-XWZXZ5 Indoor unit type Part name Model name ASU7RLF1, ASU9RLF1, ASU12RLF1, Wall mounted Communication kit UTY-XCBXZ2 ASU15RLF1 Floor AGU9RLF, AGU12RLF, AGU15RLF...
  • Page 129: 12-2.External Output

    12-2. External output Use an external output cable with appropriate external dimension, depending on the number of ca- bles to be installed. ¢ Operation status output Indoor unit type Connector Wall mounted ASU7RLF1, ASU9RLF1, ASU12RLF1, ASU15RLF1 CNB01 Floor AGU9RLF, AGU12RLF, AGU15RLF CN20 Air conditioner operation status signal can be output.
  • Page 130 • Optional part Indoor unit type Part name Model name ASU7RLF1, ASU9RLF1, ASU12RLF1, Wall mounted UTY-XWZXZ5 External connect ASU15RLF1 Floor AGU9RLF, AGU12RLF, AGU15RLF UTY-XWZXZ5 UTY-XWZXZ5 Indoor unit type Part name Model name ASU7RLF1, ASU9RLF1, ASU12RLF1, Wall mounted Communication kit UTY-XCBXZ2 ASU15RLF1 Floor AGU9RLF, AGU12RLF, AGU15RLF...
  • Page 131 ¢ Error status output Indoor unit type Connector Wall mounted ASU7RLF1, ASU9RLF1, ASU12RLF1, ASU15RLF1 CNB02 Floor AGU9RLF, AGU12RLF, AGU15RLF CN21 Air conditioner error status signal can be output. • Circuit diagram example Indoor unit Connected unit control PCB *1 Connector Example: Example: Display DC 24 V...
  • Page 132: External Input And Output (Lpas Series Wall Mounted Type Indoor Unit)

    13. External input and output (LPAS series wall mounted type indoor unit) External input and output PCB Indoor unit PCB CN47 (Ext. out) CN65 (Ext. in/out PCB) CN46 (Ext. in) SW301 SW302 Rotary switch CN314 CN313 CN312 CN311 CN310 CN308 Input External input External output...
  • Page 133: 13-1.External Input

    13-1. External input With using external input function, some functions on this product can be controlled from an external device. • “Operation/Stop” mode or "Forced stop" mode can be selected with function setting of indoor unit. • A twisted pair cable (22AWG) should be used. Maximum length of cable is 492 ft (150 m). •...
  • Page 134 ¢ External Input and Output PCB The indoor unit Operation/Stop can be set by using the input connector on the PCB. • Input select: Use either one of these types of connectors according to the application. (Both types of connec- tors cannot be used simultaneously.) –...
  • Page 135: 13-2.External Output

    13-2. External output Use an external output cable with appropriate external dimension, depending on the number of ca- bles to be installed. ¢ Indoor unit • A twisted pair cable (22AWG) should be used. Maximum length of cable is 82 ft (25 m). •...
  • Page 136 ¢ External Input and Output PCB • A twisted pair cable (22AWG) should be used. Maximum length of cable is 82 ft (25 m). • Output voltage: High DC 12 V±2 V, Low 0 V. • Permissible current: 50 mA •...
  • Page 137: 13-3.Combination Of External Input And Output

    13-3. Combination of external input and output By combining the function setting of the indoor unit and rotary switch setting of the External Input and Output PCB, you can select various combinations of functions. Combination examples of external input and output are as follows: External input Indoor unit External Input and Output PCB...
  • Page 138 External output Indoor unit External Input and Output PCB Function Rotary Mode setting CN47 CN310 CN311 CN312 Indoor unit fan 60-00 Operation/Stop Operation/Stop Error status operation status Indoor unit fan External heater 60-00 Operation/Stop Error status operation status output Cooling Indoor unit fan External heater 60-01...
  • Page 139: 13-4.Details Of Function

    13-4. Details of function ¢ Control input function • When function setting is “Operation/Stop” mode 1 – In the case of “Edge” input: Function Rotary SW on External External input Input signal Command setting Input and Output PCB Off → On Operation External Input and 46-00...
  • Page 140 • When function setting is “Forced stop” mode – In the case of “Edge” input: Function Rotary SW on External External input Input signal Command setting Input and Output PCB Off → On Forced stop External Input and 46-02 CN313 Output PCB On →...
  • Page 141 • When function setting is “Operation/Stop” mode 2 – In the case of “Edge” input: Function Rotary SW on External External input Input signal Command setting Input and Output PCB Off → On Operation Stop External Input and 46-03 CN313 (Remote Output PCB On →...
  • Page 142 • Forced thermostat off function Rotary SW on External External input Input signal Command Input and Output PCB Off → On Thermostat off External Input and Output PCB CN313 On → Off Normal operation Input Compressor Room temp. Set temp. - 136 - 13-4.
  • Page 143 ¢ Control output function • Operation/Stop status Rotary SW on External Output External output Command Input and Output PCB signal Off → On Operation External Input and Output PCB CN310 On → Off Stop The output is low when the unit is stopped. Operation Indoor unit Stop...
  • Page 144 ¢ External heater output Function setting Indoor unit Wired R. C. Control Primary heater Auxiliary heater Control switching external heaters Sensor activation* No. 61 Auxiliary heater Heat pump 61-00 — External device* control 1 Auxiliary heater Heat pump External device 61-01 —...
  • Page 145 • Design and install external heater appropriately with considering its protection. • Inappropriate designing and installation of external heater may cause a fire by emitted heat from the external heater. • Fujitsu General Ltd. is not responsible for inappropriate designing or installation of external heating device. - 139 - 13-4.
  • Page 146  Auxiliary heater control 1 Operation Condition Heater on Heater is on as shown in following diagram of heating temperature. • Heater is off as shown in following diagram of heating temperature. • Other than heating mode Heater off • Error occurred •...
  • Page 147  Heat pump prohibition control Perform heating by external heater only. Indoor unit is continuous thermostat off. Operation Condition Heater on Heater is on as shown in following diagram of heating temperature. • Heater is off as shown in following diagram of heating temperature. •...
  • Page 148  Auxiliary heater control by outdoor temperature 1 This control selects heat pump or external heater according to the outdoor temperature. When out- door temperature is high, the heating is performed by using heat pump only. Operation Condition Heater on Heater is on as shown in following diagram of heating temperature.
  • Page 149 • Operation status 46.4°F (8°C) 42.8°F (6°C) Outdoor temperature (Factory setting) -0.4°F (-18°C) -4°F (-20°C) Heat pump Heat pump Combination zone prohibition only zone Outdoor temperature zone * zone Comp. On/Off 12 V Heater * The outdoor temperature zone transition from one to another will stay in that zone for minimum of 30 min. NOTE: In following operations, compressor will be on in heat pump prohibition zone.
  • Page 150  Auxiliary heater control by outdoor temperature 2 This control selects heat pump or external heater according to the outdoor temperature. Even when outdoor temperature is high, the heating is performed by using both of heat pump and external heater. Operation Condition Heater on...
  • Page 151 • Operation status 46.4°F (8°C) 42.8°F (6°C) Outdoor temperature (Factory setting) -0.4°F (-18°C) -4°F (-20°C) Heat pump Combination zone Outdoor temperature zone * prohibition zone Comp. On/Off 12 V Heater * The outdoor temperature zone transition from one to another will stay in that zone for minimum of 30 min. NOTE: In following operations, compressor will be on in heat pump prohibition zone.
  • Page 152  Auxiliary heater control by outdoor temperature 3 This control selects heat pump or external heater according to the outdoor temperature. Even when outdoor temperature is high, the heating is performed by using both of heat pump and external heater. Operation Condition Heater on...
  • Page 153 • Operation status Heat pump only zone 46.4°F (8°C) 42.8°F (6°C) Outdoor temperature (Factory setting) -0.4°F (-18°C) -4°F (-20°C) Combination zone Outdoor temperature zone * Comp. On/Off 12 V Heater * The outdoor temperature zone transition from one to another will stay in that zone for minimum of 30 min. NOTE: In following operations, compressor will be on in heat pump prohibition zone.
  • Page 154  Auxiliary heat pump control • External heater output Operation Condition Heater on Heater is on as shown in following diagram of heating temperature. • Heater is off as shown in following diagram of heating temperature. • Other than heating mode Heater off •...
  • Page 155  Auxiliary heat pump control by outdoor temperature 1 • External heater output Operation Condition Heater on Heater is on as shown in following diagram of heating temperature. • Heater is off as shown in following diagram of heating temperature. •...
  • Page 156 • Operation status 46.4°F (8°C) 42.8°F (6°C) Outdoor temperature (Factory setting) -0.4°F (-18°C) -4°F (-20°C) Heat pump Combination zone Outdoor temperature zone * prohibition zone Comp. On/Off 12 V Heater * The outdoor temperature zone transition from one to another will stay in that zone for minimum of 30 min. NOTE: In following operations, compressor will be on in heat pump prohibition zone.
  • Page 157  Auxiliary heat pump control by outdoor temperature 2 • External heater output Operation Condition Heater on Heater is on as shown in following diagram of heating temperature. • Heater is off as shown in following diagram of heating temperature. •...
  • Page 158 • Operation status Heat pump prohibition zone 46.4°F (8°C) 42.8°F (6°C) Outdoor temperature (Factory setting) -0.4°F (-18°C) -4°F (-20°C) Combination zone Outdoor temperature zone * Comp. On/Off 12 V Heater * The outdoor temperature zone transition from one to another will stay in that zone for minimum of 30 min. NOTE: In following operations, compressor will be on in heat pump prohibition zone.
  • Page 159  Auxiliary heat pump control by outdoor temperature 3 • External heater output Operation Condition Heater on Heater is on as shown in following diagram of heating temperature. • Heater is off as shown in following diagram of heating temperature. •...
  • Page 160 • Operation status Heat pump prohibition zone 46.4°F (8°C) 42.8°F (6°C) Outdoor temperature (Factory setting) -0.4°F (-18°C) -4°F (-20°C) Combination zone Outdoor temperature zone * Comp. On/Off 12 V Heater * The outdoor temperature zone transition from one to another will stay in that zone for minimum of 30 min. NOTE: In following operations, compressor will be on in heat pump prohibition zone.
  • Page 161 ¢ Heating thermostat on for humidifier Indoor unit Function External output setting Situation Mode Rotary SW Heating Indoor unit fan Heating thermostat on operation thermostat on no. 60 status 60-05 CN47 Example of 60-06 CN312 individual Not used 60-07 CN311 connection 60-08 CN310...
  • Page 162: Group Connection

    14. Group connection Wiring regulation on the remote controllers in the multi-split systems are reviewed and allowed for group connection. Example of group connection Indoor unit Indoor unit Outdoor unit *Exterior of each device shown above might be different from the actual one. NOTES: •...
  • Page 163: 14-1.Precautions On Creating A Group Connection

    14-1. Precautions on creating a group connection Take precautions on items described in this section when creating a group connection in the multi- split system. CAUTION Group connection to other refrigerant system between the multi-split systems with same communi- cation system as shown below is strictly prohibited. Indoor unit Indoor unit Indoor unit...
  • Page 164 • Central Remote Controller (UTY-DMMUM) and individual remote controller (e.g. UTY-RVNUM) cannot be connected simultaneously. Indoor unit Indoor unit Indoor unit Indoor unit Indoor unit Indoor unit Outdoor unit Outdoor unit Individual Individual remote remote To terminal controller Central Central controller block (CN93) remote...
  • Page 165: 14-2.Remote Controller Address Setting Procedure For Wireless Remote Controllers

    • Required parts for group connection – Optional part: Indoor unit type Communication Kit ASU7RLF1, ASU9RLF1, Wall mounted UTY-XCBXZ2 ASU12RLF1, ASU15RLF1 As for the optional parts, refer to Chapter 18-3. "Others" on page 228. – Service part: Wire with connector (Service part no. 9705932012) Wiring example for multiple remote control or group control: Crimping terminal and its insulation cap (Locally purchased)
  • Page 166: Remote Controller

    15. Remote controller 15-1. Wireless remote controller (AR-REG1U) ¢ Overview Signal transmitter FAN button MODE button MIN. HEAT button TEMP. ECONOMY button SWING button button SET button POWERFUL button ON TIMER button REG1U OFF TIMER button Start/Stop button REG1U TIMER SELECT button RESET button SLEEP TIMER button °C / °F switching button...
  • Page 167 ¢ Specifications  Controller Unit: in (mm) Top view 11/16 2-3/8 (61) (17) Front view Side view Size (H × W × D) in (mm) 8-1/16 × 2-3/8 × 11/16 (205 × 61 × 17) Weight oz (g) 4.4 (124) (without batteries) ...
  • Page 168: 15-2.Wireless Remote Controller (Ar-Rpb1U)

    15-2. Wireless remote controller (AR-RPB1U) ¢ Overview a MODE button • Switches operation mode (AUTO, COOL, DRY, FAN, and HEAT). • Starts/ends the remote controller custom code (max. 4 types) change. b FAN SPEED button • Press the FAN SPEED button while the air conditioner is operating, to control fan speed.
  • Page 169 ¢ Specifications  Controller Unit: in (mm) Top view 1-3/4 (45) 11/16 (17.5) Front view Side view Size (H × W × D) in (mm) 6-3/8 × 1-3/4 × 11/16 (162 × 45 × 17.5) Weight oz (g) 2.3 (65.5) (without batteries) ...
  • Page 170: 15-3.Wireless Remote Controller (Uty-Lntu: Optional Part)

    15-3. Wireless remote controller (UTY-LNTU: Optional part) ¢ Overview Signal transmitter MODE button FAN button MIN. HEAT button TEMP. SWING button button SET button Economy button ON TIMER button OFF TIMER button Start/Stop button TIMER SELECT button RESET button SLEEP TIMER button TEST RUN button TIMER CANCEL button CLOCK ADJUST button...
  • Page 171 ¢ Specifications  Controller Unit: in (mm) Top view 11/16 2-3/8 (61) (17) Front view Side view Size (H × W × D) in (mm) 8-1/16 × 2-3/8 × 11/16 (205 × 61 × 17) Weight oz (g) 4.4 (124) (without batteries) ...
  • Page 172: 15-4.Ir Receiver Kit With Wireless Remote Controller (Uty-Lbtum: Optional Part)

    15-4. IR receiver kit with Wireless remote controller (UTY- LBTUM: Optional part) ¢ Overview Signal transmitter FAN button MODE button MIN. HEAT button TEMP. SWING button button SET button Economy button ON TIMER button OFF TIMER button Start/Stop button TIMER SELECT button RESET button SLEEP TIMER button TEST RUN button...
  • Page 173 ¢ Specifications  Controller Unit: in (mm) Top view 11/16 2-3/8 (61) (17) Front view Side view Size (H × W × D) in (mm) 8-1/16 × 2-3/8 × 11/16 (205 × 61 × 17) Weight oz (g) 4.4 (124) (without batteries) ...
  • Page 174  IR receiver Unit: in (mm) 7/16 9/16 (13.6) 2-1/4 (57.4) 9/16 (13.6) (11.5) (18.5) 5/16 (7.2) 5/16 (7.2) 5/16 (8.5) 3-9/16 (90) 11/16 (17) Front view Side view Rear view Size (H × W × D) in (mm) 5-11/16 × 3-9/16 × 1-3/16 (145 × 90 × 30) Weight oz (g) 5 (150)
  • Page 175: 15-5.Wired Remote Controller (Uty-Rnnum: Optional Part)

    15-5. Wired remote controller (UTY-RNNUM: Optional part) ¢ Overview a START/STOP button Starts and stops operation. b SET TEMP. button Selects the setting temperature. c MODE button Selects the operating mode (AUTO , HEAT ,FAN COOL , and DRY d FAN button Selects the fan speed AUTO ,QUIET , LOW...
  • Page 176 ¢ System diagram 1 remote controller: 2 remote controllers: Indoor unit Indoor unit A, B, C: Remote controller cable A ≤ 1,640 ft (500 m);B + C ≤ 1,640 ft (500 Primary Secondary Remote controllers Remote controller ¢ Electrical wiring 1 remote controller: 2 remote controllers: Indoor unit...
  • Page 177 ¢ Specifications Dimensions and other specifications on the wired remote controller are as follows. Unit: in (mm) 4-3/4 (120) 11/16 (18) Front view Side view Size (H × W × D) in (mm) 4-3/4 × 4-3/4 × 11/16 (120 × 120 × 18) Weight oz (g) 5.6 (160)
  • Page 178 2. Connect the remote controller cable. • Connect the cable made in step 1. to the terminal (*1) of optional communication kit. • Connect the cable from the terminal (*2) of communication kit to the indoor unit PCB. CNC01 (for ASU7-15RLF1: UTY-XCBXZ2) CND01 (for ASU7-15RLF1: UTY-XCBXZ2) Terminal (*2)
  • Page 179: 15-6.Wired Remote Controller (Uty-Rnruz*: Optional Part)

    15-6. Wired remote controller (UTY-RNRUZ*: Optional part) ¢ Overview a Remote temperature sensor (inside) b On/off button Operable only while displaying the “Monitor mode” screen. Office Fri 10:00AM Mode Set Temp. c LED lamp (operation indicator) Cool 80°F Custom Auto Auto Heat 74°F...
  • Page 180 ¢ System diagram 1 remote controller: 2 remote controllers: Indoor unit Indoor unit A, B, C: Remote controller cable A ≤ 1,640 ft (500 m);B + C ≤ 1,640 ft (500 Primary Secondary Remote controllers Remote controller ¢ Electrical wiring 1 remote controller: 2 remote controllers: Indoor unit...
  • Page 181 ¢ Specifications Dimensions and other specifications on the wired remote controller are as follows. [Unit : mm] 20.4 Model name UTY-RNRUZ* Display 3.8-inch FSTN LCD (255 × 160 dots) with touch panel Dimensions (H × W × D) in (mm) 4-3/4 × 4-3/4 × 13/16 (120 × 120 × 20.4) Weight oz (g) 8 (220)
  • Page 182: 15-7.Simple Remote Controller (Uty-Rsnum: Optional Part)

    15-7. Simple remote controller (UTY-RSNUM: Optional part) ¢ Overview a START/STOP button Starts and stops operation. b Display backlight button Lights during operation. c Operation lamp Lights during operation. d FAN button Selects the fan speed (AUTO ,HIGH , MED , and QUIET ).
  • Page 183 ¢ System diagram 1 remote controller: 2 remote controllers: Indoor unit Indoor unit A, B, C: Remote controller cable A ≤ 1,640 ft (500 m);B + C ≤ 1,640 ft (500 Primary Secondary Remote controllers Remote controller ¢ Electrical wiring 1 remote controller: 2 remote controllers: Indoor unit...
  • Page 184 ¢ Specifications Dimensions and other specifications on the wired remote controller are as follows. Unit: in (mm) 2-15/16 (75) 9/16 (14) 1-15/16 (49) 7/16 (11) hole x 2 1-9/16 (39) 1/4 (6) 2-3/8 (60) 3/16 (4) 5/16 (8) hole x 2 Front View Side View Rear View...
  • Page 185  Pattern A 1. Modify the remote controller cable as follows: • Use a tool to cut off the terminal on the end of the remote controller cable and then re- move the insulation from the cut end of the cable as shown in following figure. •...
  • Page 186 2. Connect the remote controller cable. • Connect the cable made in step 1. to the indoor unit PCB. Connecting cable Remote controller cable Indoor unit PCB ¢ Optional parts The optional communication kit is necessary for connecting the wired remote controller to some models in wall-mounted type.
  • Page 187: 15-8.Simple Remote Controller (Uty-Rsry And Uty-Rhry: Optional Parts)

    15-8. Simple remote controller (UTY-RSRY and UTY-RHRY: Optional parts) ¢ Overview a LED lamp Lights during operation. b Louver button Adjusts the airflow direction. c START/STOP button Starts and stops operation. d FAN control button Switches the fan speed as follows: Auto High Quiet...
  • Page 188 ¢ System diagram 1 remote controller: 2 remote controllers: Indoor unit Indoor unit A, B, C: Remote controller cable A ≤ 1,640 ft (500 m);B + C ≤ 1,640 ft (500 Primary Secondary Remote controllers Remote controller ¢ Electrical wiring 1 remote controller: 2 remote controllers: Indoor unit...
  • Page 189 ¢ Specifications Dimensions and other specifications on the wired remote controller are as follows. Unit: in (mm) 1-3/16 1-3/16 (30.0) (30.0) Hole: 3/8 × 3/16 (9 × 4.5) 2-15/16 (75) 7/8 (23.0) 3/4 (19) Hole: 4/16 × 3/16 (6 × 4.5) Hole: 1/2 ×...
  • Page 190: Function Settings

    16. Function settings To adjust the functions of this product according to the installation environment, various types of function settings are available. NOTE: Incorrect settings can cause a product malfunction. 16-1. Compact cassette type indoor unit (setting by DIP switch) By using some components on the PCB, you can change the function settings.
  • Page 191: 16-2.Slim Duct Type Indoor Unit (Setting By Dip Switch)

    16-2. Slim duct type indoor unit (setting by DIP switch) By using some components on the PCB, you can change the function settings. Related components on the PCB and the applicable settings: Component Setting content Drainage function setting DIP switch SW101 Auto louver grille setting Fan delay setting...
  • Page 192 ¢ DIP switch setting • SW101-Switch 1: Drainage function setting Switch 1 Drainage function Factory setting Disabled Enabled ♦ • SW101-Switch 2: Auto louver grille setting When Auto louver grille kit (optional parts) is attached, set to “Enabled”. Switch 2 Auto louver grille setting Factory setting Enabled...
  • Page 193: 16-3.Indoor Unit (Setting By Wireless Remote Controller)

    16-3. Indoor unit (setting by wireless remote controller) Some function settings can be changed on the remote controller. After confirming the setting proce- dure and the content of each function setting, select appropriate functions for your installation envi- ronment. ¢ Setting procedure by AR-REG1U The function number and the associated setting value are displayed on the LCD of the remote con- troller.
  • Page 194 STEP 2: Selecting the function number and setting value 1. Press the SET TEMP. ( ) buttons to select the function num- Function number ber. To switch between the left and right digits, press the MIN. HEAT button. 2. Press the POWERFUL button to proceed the setting value. To re- turn the function number selection, press the POWERFUL button again.
  • Page 195  Remote controller temperature unit To change the displayed temperature unit, press the °C/°F switching button to select the preferred temperature unit. (Factory setting is “°F”.) - 189 - 16-3. Indoor unit (setting by wireless remote controller) 16. Function settings...
  • Page 196 ¢ Setting procedure by AR-RPB1U The function number and the associated setting value are displayed on the LCD of the remote con- troller. Follow the instructions written in the local setup procedure supplied with the remote controller, and select appropriate setting according to the installation environment. Before connecting the power supply of the indoor unit, reconfirm following items: •...
  • Page 197 STEP 2: Selecting the function number and setting value 1. Press the TEMP./SELECT ( ) buttons to select the function Function number number. To switch between the left and right digits, press the MODE button. 2. Press the FAN SPEED button to proceed the setting value. To re- turn the function number selection, press the FAN SPEED button again.
  • Page 198  Custom code setting on AR-RPB1U To interconnect the air conditioner and the wireless remote controller, assignment of the custom code for the wireless remote controller is required. NOTE: Air conditioner cannot receive a signal if the air conditioner has not been set for the custom code.
  • Page 199: 16-4.Indoor Unit (Setting By Wired Remote Controller)

    16-4. Indoor unit (setting by wired remote controller) • The function settings of the control of the indoor unit can be changed by this procedure according to the installation conditions. Incorrect settings can cause the indoor unit malfunction. • After the power is turned on, perform the “Function setting” according to the installation conditions using the remote controller.
  • Page 200 ¢ UTY-RNNUM  Button name and function During address setting mode, indoor unit reject the any operation command from remote controller. Function number Refer to Function details Remote controller address Setting number Refer to Function details Λ SET TEMP. “V” and “ ”...
  • Page 201 Confirm the setting by pressing the TIMER SET button. The data will be transferred to the indoor unit. Not good Good ● Data is not set up on the indoor unit Data is correctly set up on the indoor unit correctly (-- is displayed.) (Flashing display changes to illuminated display.) ●...
  • Page 202 ¢ UTY-RNRUZ*  Setting procedure by using wired remote controller UTY-RNRUZ* The function number and the associated setting value are displayed on the LCD of the remote con- troller. Follow the instructions written in the local setup procedure supplied with the remote controller, and select appropriate setting according to the installation environment.
  • Page 203 “Function No.” screen is displayed. Set the “Function No.” with Function No. Cancel When the “OK” is touched, the display returns to the “Function Setting” screen. Touch the “Function No.” on the “Function Setting” screen. Function Setting Address [002–01] Function No. [30] Setting No.
  • Page 204 Touch the “Yes” of the verification screen. Function Setting Function setting will be performed. OK? In case of “ERROR” In case of “OK” Function Setting Function Setting Address [002–01] Address [002–01] Function No. [30] Function No. [30] Setting No. [01] Setting No.
  • Page 205: 16-5.Indoor Unit (Setting By Simple Remote Controller)

    16-5. Indoor unit (setting by simple remote controller) • The function settings of the control of the indoor unit can be changed by this procedure according to the installation conditions. Incorrect settings can cause the indoor unit malfunction. • After the power is turned on, perform the “Function setting” according to the installation conditions using the remote controller.
  • Page 206 ¢ UTY-RSNUM  Button name and function During address setting mode, indoor unit reject the any operation command from remote controller. Function number Setting number Refer to Function details Refer to Function details Remote controller address START/STOP button Transmits function setting FAN button SET TEMP.
  • Page 207 Select the setting number by pressing the SET TEMP. or SET TEMP. button. The setting number indicator flashes during setting number selection. Setting number Example) Function number : 30, Setting number : 01 Confirm the setting by pressing the TIMER SET button. The data will be transferred to the indoor unit.
  • Page 208  Resetting the power after setting up function of all indoor units NOTES: • If the reset is not performed, function cannot be read correctly. • After all the functions have been set, the circuit breaker needs to be switched off for at least 2 minutes.
  • Page 209 ¢ UTY-RSRY  Setting procedure by using wired remote controller The function number and the associated setting value are displayed on the LCD of the remote con- troller. Follow the instructions written in the local setup procedure supplied with the remote controller, and select appropriate setting according to the installation environment.
  • Page 210 Select the item number to be set with the SET TEMP. or SET TEMP. button, and press button to switch to the setting screen. Select the “13” in Menu 2-F1 settings. Then, press the button. Select the 2-wire remote controller address with the SET TEMP. or SET TEMP.
  • Page 211 Setting results are displayed after data transmission. Press the button to return to the 2-wire remote controller address selection screen of step 9. If setting has been completed, press the FAN button to return to the Menu 2-F1 item se- lection screen.
  • Page 212: 16-6.Function Details

    16-6. Function details ¢ Contents of function setting Each function setting listed in this section is adjustable in accordance with the installation environ- ment. NOTE: Setting will not be changed if invalid numbers or setting values are selected.  Function setting list Wall mounted Compact Function...
  • Page 213 1) Filter sign Select appropriate intervals for displaying the filter sign on the indoor unit according to the estimated amount of dust in the air of the room. If the indication is not required, select "No indication" (03). Function number Setting value Setting description Factory setting...
  • Page 214 5) Static pressure Select the appropriate static pressure according to the installation conditions. Function number Setting value Setting description Factory setting 0 in.WG (0 Pa) 0.04 in.WG (10 Pa) 0.08 in.WG (20 Pa) 0.12 in.WG (30 Pa) 0.16 in.WG (40 Pa) 0.20 in.WG (50 Pa) 0.24 in.WG (60 Pa) 0.28 in.WG (70 Pa)
  • Page 215 6) Room temperature control for indoor unit sensor NOTE: Before performing this setting, refer to Function 95. NOTE: If the remote sensor unit option is selected, perform this setting. Depending on the installed environment, correction of the room temperature sensor may be re- quired.
  • Page 216 7) Room temperature control for wired remote controller sensor NOTE: Before performing this setting, refer to Function 95. Depending on the installed environment, correction of the wire remote temperature sensor may be required. Select the appropriate control setting according to the installed environment. To change this setting, set Function 42 to “Both“...
  • Page 217 9) Room temperature sensor switching (Only for wired remote controller) When using the wired remote controller temperature sensor, change the setting to "Both" (01). Function number Setting value Setting description Factory setting Indoor unit ♦ Both 00: Sensor on the indoor unit is active. 01: Sensors on both indoor unit and wired remote controller are active.
  • Page 218 13) Indoor unit fan control for energy saving for cooling Enables or disables the power-saving function by controlling the indoor unit fan rotation when the outdoor unit is stopped during cooling operation. Function number Setting value Setting description Factory setting Disable ♦* Enable...
  • Page 219 15) Control switching of external heaters Sets the control method for external heater to be used. For details, refer to “External heater output” in “External input and output" for each product type. Function Factory Setting value Setting description number setting Auxiliary heater control 1 ♦...
  • Page 220 16) Operating temperature switching of external heaters Sets the temperature conditions when the external heater is ON. For details, refer to “External heater output” in “External input and output" for each product type. • For compact cassette type and slim duct type indoor unit Setting description Setting value of function 61: Function...
  • Page 221 17) Outdoor temperature zone boundary temperature A Setting required if changing of the outdoor temperature setting for heat pump prohibition zone is re- quired when auxiliary heater control by outdoor temperature 1 and 2 are performed on the indoor unit. For details, refer to “External heater output”...
  • Page 222 19) Standby time for auxiliary equipment operation Sets the standby time until the auxiliary equipment operation starts during primary equipment opera- tion. For details, refer to “External input and output" for each product type. Function number Setting value Setting description Factory setting Disable ♦...
  • Page 223 24) Room temperature control for wired remote controller sensor NOTE: Before performing this setting, refer to Function 95. Depending on the installed environment, correction of the room temperature sensor may be re- quired. Select the appropriate control setting according to the installed environment. To change this setting, set Function 42 to "Both"...
  • Page 224: 16-7.Wired Remote Controller (Uty-Rnnum)

    16-7. Wired remote controller (UTY-RNNUM) Prohibited Dual remote controller setting Prohibited DIP switch 1 °F/°C switch Prohibited Memory backup setting * Do not use DIP switch 2. ¢ Switch location Front case (back side) DIP switch 2 DIP switch 1 ¢...
  • Page 225  SW6: Memory backup setting Set to “ON” to use batteries for the memory backup. When batteries are not used, all of settings stored in memory will be deleted if there is a power failure. Memory backup Factory setting Disable ♦...
  • Page 226: 16-8.Simple Remote Controller (Uty-Rsnum)

    16-8. Simple remote controller (UTY-RSNUM) Prohibited Dual remote controller setting °F/°C switch DIP switch Prohibited Prohibited Prohibited ¢ Switch location DIP Switch ¢ DIP switch setting  SW2: Dual remote controller setting Set the remote controller SW2 according to the following table. Primary unit Secondary unit Number of remote controller...
  • Page 227: Accessories

    17. Accessories 17-1. Compact cassette type ¢ Models: ACUH07LUAS1, ACUH09LUAS1, ACUH12LUAS1, and ACUH18LUAS1 Part name Exterior Q’ty Part name Exterior Q’ty Operating manual Drain hose insulation Installation manual Hose band Coupler heat insulation Template (Carton top) (large) Special nut A...
  • Page 228: 17-2.Slim Duct Type

    17-2. Slim duct type ¢ Models: ADUH07LUAS1, ADUH09LUAS1, ADUH12LUAS1, ADUH18LUAS1, and ADUH24LUAS1 Part name Exterior Q’ty Part name Exterior Q’ty Operating manual Cable tie (large) Installation manual Cable tie (medium) Filter (small) Installation template (Other than 18 model) 2 (18 model) Filter (large) Washer (For 18/24 models)
  • Page 229: 17-3.Wall Mounted Type

    17-3. Wall mounted type ¢ Models: ASU7RLF1, ASU9RLF1, ASU12RLF1, and ASU15RLF1 Part name Exterior Q’ty Part name Exterior Q’ty Operating manual Cloth tape Installation manual Tapping screw (large) Wall hook bracket Tapping screw (small) Remote controller Air cleaning filter Battery Filter holder Seal A •...
  • Page 230 ¢ Models: ASUH07LPAS, ASUH09LPAS, ASUH12LPAS, ASUH15LPAS, ASUH18LPAS, and ASUH24LPAS Part name Exterior Q’ty Part name Exterior Q’ty Operating manual Tapping screw (large) Installation manual Tapping screw (small) Remote controller Battery Remote controller Wall hook bracket holder Cloth tape Ion deodorization filter Filter holder Apple-catechin filter Seal A...
  • Page 231: 17-4.Floor Type

    17-4. Floor type ¢ Models: AGU9RLF, AGU12RLF, and AGU15RLF Part name Exterior Q’ty Part name Exterior Q’ty Operating manual Cable tie Installation manual Cloth tape Wall hook bracket Tapping screw (large) Remote controller Tapping screw (small) Battery Air cleaning filter Remote controller holder - 225 -...
  • Page 232: Optional Parts

    18. Optional parts 18-1. Controllers ¢ Lineup Type Indoor unit type Wired remote controller Wireless remote controller UTY-RNNUM UTY-RNRUZ* UTY-LNTU AR-REG1U AR-RPB1U Compact cassette — ◌ ◌ — — Slim duct — ◌ — — — ASU7RLF1 ASU9RLF1 ◌*1 — —...
  • Page 233: 18-2.Cassette Grille

    ¢ Parts IR receiver kit with Wireless Wired remote controller remote controller Office Fri 10:00AM Mode Set Temp. Cool 80°F Custom Auto Auto Heat 74°F Cool 84°F Room Temp. Away 76°F Heat 68°F Vacation Status Menu UTY-RNNUM UTY-RNRUZ* UTY-LBTUM Wireless remote controller REG1U UTY-LNTU AR-REG1U...
  • Page 234: 18-3.Others

    18-3. Others ¢ Lineup Type External Modbus Communic WLAN Adapter Switch Indoor unit type Convertor Converter ation Kit Controller UTY- UTY- UTY- UTY-TERX UTY-VKSX UTY-VMSX TFSXZ2 TFSXF1 XCBXZ2 Compact cassette ◌ — ◌ ◌ ◌ — Slim duct ◌ — ◌...
  • Page 235 Type Insulation Air Outlet Kit for Fresh Air Auto Louver Grille Kit Shutter Indoor unit type High Intake Kit Plate Humidity UTD- UTD- UTD- UTR-YDZB UTZ-KXGC UTZ-VXAA GXTA-W GXTB-W GXTC-W Compact cassette — — — ◌ ◌ ◌ ADUH07LUAS1 ADUH09LUAS1 ◌...
  • Page 236 ¢ Parts Exterior Part name Model name Summary Thermo-sensor for sensing the Remote Sensor UTY-XSZX temperature of arbitrary place in the Unit room. Width: 26-7/8 in (683 mm) Auto Louver For 07, 09, and 12 models UTD-GXTA-W Grille Kit Width: 34-3/4 in (883 mm) Auto Louver UTD-GXTB-W Grille Kit...
  • Page 237 Exterior Part name Model name Summary Use to connect with optional devices Communication UTY-XCBXZ2 and air conditioner PCB. Use to connect with external devices External Input and air conditioner PCB. UTY-XCSX and Output PCB External Input Use to connect with external devices UTY-XCSXZ2 and Output PCB and air conditioner PCB.
  • Page 238 NOTE: Combined use of following optional parts and WLAN Adapter (UTY-TFSXZ2) is not allowed. • External Input and Output PCB (UTY-XCSX) • External Input and Output PCB (UTY-XCSXZ2) • Modbus Converter • KNX Convertor • External Switch Controller - 232 - 18-3.
  • Page 239: Indoor Unit Installation Precautions

    19. Indoor unit installation precautions NOTE: The information listed below are general precautions. Some models also include items that do not apply. 19-1. Places where prohibited for use • Places where there is a danger of combustible gas leakage. • Places where sulfur gas, chlorine gas, acid, alkali, or other matter which effects equipment is gen- erated.
  • Page 240 Condition Contents Countermeasures (Reference) When inside the When the indoor unit is installed where the inside of the 1. Add heat insulating material to ceiling is high ceiling is 86 °F (30 °C) RH80% or greater, the dew point the outside of the indoor unit temperature temperature of the outer perimeter may become higher cabinet.
  • Page 241 Condition which requires addition of outside heat insulation Relative humidity 80 % Dry bulb temperature 86 °F (30 °C) Figure 19-1 Moist air curve Slit of heat insulating material Heat insulation reinforcement material Flare connection facing upward (locally purchased) To indoor unit Covered gas pipe (heat insulation...
  • Page 242 - 236 - 19-2. Points to remember when installing 19. Indoor unit installation precautions...
  • Page 243: Part 2. Outdoor Unit

    Part 2. OUTDOOR UNIT MULTI-SPLIT TYPE: AOU45RLXFZ...
  • Page 244: Specifications

    1. Specifications Type Inverter, Heat pump Model name AOU45RLXFZ Power source 1Ø 208/230 V 60 Hz Available voltage range 187—264V Number 2 to 5 Connectable indoor unit Total capacity range 34,000 to 54,000 Btu/h Non-Duct Duct Combination of indoor unit ASU9RLF1 x 5 ADUH09LUAS1 x 5 Btu/h...
  • Page 245 Type Inverter, Heat pump Model name AOU45RLXFZ NOTES: • Specifications are based on the following conditions: – Power source of specifications : 230 V – Cooling: Indoor temperature of 80°FDB (26.7°CDB)/67°FWB (19.4°CWB), and outdoor temperature of 95 °FDB (35°CDB)/75°FWB (23.9°CWB). –...
  • Page 246: Dimensions

    2. Dimensions 2-1. Model: AOU45RLXFZ Unit: in (mm) 6-9/16 (166) 6-1/16 (154) 25-9/16 (650) 3 (76) 3-3/16 (81) 3-15/16 (100) Top view 1-5/16 14-9/16 3-3/4 (95) (33) (370) 9/16 (14) 38-3/16 (970) 7/8 (22.2) (cable port) 1-2/16 (27.8) (22.2) (cable port) (cable port) 3 (76.3) 7/8 (22.2)
  • Page 247: Installation Space

    3. Installation space 3-1. Model: AOU45RLXFZ ¢ Space requirement Provide sufficient installation space for product safety.  Single outdoor unit installation • When the upper space is open: Unit: in (mm) When there are obstacles at the rear only. When there are obstacles at the rear and sides.
  • Page 248  Multiple outdoor unit installation • When the upper space is open: Unit: in (mm) When there are obstacles at the rear only. When there are obstacles at the front only. 10 (250) or more 60 (1,500) or more 10 (250) or more 12 (300) or more...
  • Page 249  Outdoor unit installation in multi-row Unit: in (mm) Single parallel unit arrangement Multiple parallel unit arrangement 20 (500) 20 (500) or more or more 119 (3,000) 138 (3,500) or more or more 24 (600) or more 24 (600) or more 60 (1,500) or more 60 (1,500) or more 10 (250)
  • Page 250: Refrigerant Circuit

    4. Refrigerant circuit 4-1. Model: AOU45RLXFZ CONDENSER STRAINER STRAINER SOLENOID VALVE PRESSURE SENSOR FUSIBLE PLUG MUFFLER CHARGING CHARGING VALVE VALVE EXPANSION EXPANSION EXPANSION EXPANSION EXPANSION VALVE VALVE VALVE VALVE VALVE STRAINER STRAINER STRAINER STRAINER STRAINER HEAT EXCHANGER HEAT EXCHANGER HEAT EXCHANGER HEAT EXCHANGER HEAT EXCHANGER Indoor unit A...
  • Page 251: Wiring Diagram

    5. Wiring diagram 5-1. Model: AOU45RLXFZ - 245 - 5-1. Model: AOU45RLXFZ 5. Wiring diagram...
  • Page 252: Capacity Table

    6. Capacity table 6-1. Combinations ¢ Model: AOU45RLXFZ  Cooling Rated capacity for each indoor Maximum capacity for each in- Total capacity Combination of indoor unit Input power [kW] unit [kBtu/h] door unit [kBtu/h] [kBtu/h] Type of in- Unit door unit Unit Unit Total...
  • Page 253 Rated capacity for each indoor Maximum capacity for each in- Total capacity Combination of indoor unit Input power [kW] unit [kBtu/h] door unit [kBtu/h] [kBtu/h] Type of in- Unit door unit Unit Unit Total Min. Rated Max. Min. Rated Max. —...
  • Page 254 Rated capacity for each indoor Maximum capacity for each in- Total capacity Combination of indoor unit Input power [kW] unit [kBtu/h] door unit [kBtu/h] [kBtu/h] Type of in- Unit door unit Unit Unit Total Min. Rated Max. Min. Rated Max. —...
  • Page 255 ¢ Model: AOU45RLXFZ  Heating Rated capacity for each indoor Maximum capacity for each in- Total capacity Combination of indoor unit Input power [kW] unit [kBtu/h] door unit [kBtu/h] [kBtu/h] Type of in- Unit door unit Unit Unit Total Min. Rated Max.
  • Page 256 Rated capacity for each indoor Maximum capacity for each in- Total capacity Combination of indoor unit Input power [kW] unit [kBtu/h] door unit [kBtu/h] [kBtu/h] Type of in- Unit door unit Unit Unit Total Min. Rated Max. Min. Rated Max. —...
  • Page 257 Rated capacity for each indoor Maximum capacity for each in- Total capacity Combination of indoor unit Input power [kW] unit [kBtu/h] door unit [kBtu/h] [kBtu/h] Type of in- Unit door unit Unit Unit Total Min. Rated Max. Min. Rated Max. —...
  • Page 258: Cooling Capacity

    6-2. Cooling capacity ¢ Model: AOU45RLXFZ NOTE: Values mentioned in the table are calculated based on the maximum capacity.  Unit: kBtu/h, °F TC: Total Capacity (kBtu/h), IP: Input Power (kW) Indoor temperature Indoor unit connect- Outdoor temperature 64 °FDB 70 °FDB 75 °FDB 80 °FDB...
  • Page 259 Indoor temperature Indoor unit connect- Outdoor temperature 64 °FDB 70 °FDB 75 °FDB 80 °FDB 85 °FDB 90 °FDB ing capacity 54 °FWB 60 °FWB 63 °FWB 67 °FWB 71 °FWB 73 °FWB kBtu/h °FDB 37.6 1.71 42.5 1.74 44.8 1.76 48.0 1.78...
  • Page 260 Indoor temperature Indoor unit connect- Outdoor temperature 64 °FDB 70 °FDB 75 °FDB 80 °FDB 85 °FDB 90 °FDB ing capacity 54 °FWB 60 °FWB 63 °FWB 67 °FWB 71 °FWB 73 °FWB kBtu/h °FDB 34.3 1.51 38.7 1.53 40.8 1.55 43.7 1.56...
  • Page 261 Indoor temperature Indoor unit connect- Outdoor temperature 64 °FDB 70 °FDB 75 °FDB 80 °FDB 85 °FDB 90 °FDB ing capacity 54 °FWB 60 °FWB 63 °FWB 67 °FWB 71 °FWB 73 °FWB kBtu/h °FDB 28.4 1.11 32.1 1.13 33.9 1.14 36.3 1.15...
  • Page 262  Unit: kW, °C TC: Total Capacity (kW), IP: Input Power (kW) Indoor temperature Indoor unit connect- Outdoor temperature 17.8 °CDB 21.1 °CDB 23.9 °CDB 26.7 °CDB 29.4 °CDB 32.2 °CDB ing capacity 12.2 °CWB 15.6 °CWB 17.2 °CWB 19.4 °CWB 21.7 °CWB 22.8 °CWB kBtu/h...
  • Page 263 Indoor temperature Indoor unit connect- Outdoor temperature 17.8 °CDB 21.1 °CDB 23.9 °CDB 26.7 °CDB 29.4 °CDB 32.2 °CDB ing capacity 12.2 °CWB 15.6 °CWB 17.2 °CWB 19.4 °CWB 21.7 °CWB 22.8 °CWB kBtu/h °CDB -10.0 11.02 1.71 12.46 1.74 13.13 1.76 14.00...
  • Page 264 Indoor temperature Indoor unit connect- Outdoor temperature 17.8 °CDB 21.1 °CDB 23.9 °CDB 26.7 °CDB 29.4 °CDB 32.2 °CDB ing capacity 12.2 °CWB 15.6 °CWB 17.2 °CWB 19.4 °CWB 21.7 °CWB 22.8 °CWB kBtu/h °CDB -10.0 10.04 1.51 11.35 1.53 11.97 1.55 12.80...
  • Page 265 Indoor temperature Indoor unit connect- Outdoor temperature 17.8 °CDB 21.1 °CDB 23.9 °CDB 26.7 °CDB 29.4 °CDB 32.2 °CDB ing capacity 12.2 °CWB 15.6 °CWB 17.2 °CWB 19.4 °CWB 21.7 °CWB 22.8 °CWB kBtu/h °CDB -10.0 8.33 1.11 9.41 1.13 9.92 1.14 10.60...
  • Page 266 • TC: Total Capacity (kBtu/h), SHC: Sensible Heat Capacity (kBtu/h). • The data is based on the following conditions: Pipe length: 24.6 ft (7.5 m), Height difference: 0 ft (0 m) [Outdoor unit - Indoor unit] MODEL: ACUH07LUAS1 Indoor temperature (°FDB / °FWB) Outdoor temperature 64.0 / 54.0...
  • Page 267 • TC: Total Capacity (kW), SHC: Sensible Heat Capacity (kW). • The data is based on the following conditions: Pipe length: 24.6 ft (7.5 m), Height difference: 0 ft (0 m) [Outdoor unit - Indoor unit] MODEL: ACUH07LUAS1 Indoor temperature (°CDB / °CWB) Outdoor temperature 17.8 / 12.2...
  • Page 268 ¢ Slim duct type  Unit: kBtu/h, °F • TC: Total Capacity (kBtu/h), SHC: Sensible Heat Capacity (kBtu/h). • The data is based on the following conditions. • Pipe length: 24.6 ft (7.5 m), Height difference: 0 ft (0 m) [Outdoor unit - Indoor unit] MODEL: ADUH07LUAS1 Indoor temperature (°FDB / °FWB) Outdoor temperature...
  • Page 269 MODEL: ADUH18LUAS1 Indoor temperature (°FDB / °FWB) Outdoor temperature 64.0 / 54.0 70.0 / 60.0 75.0 / 63.0 80.0 / 67.0 85.0 / 71.0 90.0 / 73.0 (°FDB) 14.0 15.05 9.37 17.01 10.69 17.93 12.30 19.20 13.82 20.52 15.12 21.16 17.32 23.0 15.05...
  • Page 270  Unit: kW, °C • TC: Total Capacity (kW), SHC: Sensible Heat Capacity (kW). • The data is based on the following conditions: Pipe length: 24.6 ft (7.5 m), Height difference: 0 ft (0 m) [Outdoor unit - Indoor unit] MODEL: ADUH07LUAS1 Indoor temperature (°CDB / °CWB) Outdoor temperature...
  • Page 271 MODEL: ADUH18LUAS1 Indoor temperature (°CDB / °CWB) Outdoor temperature 17.8 / 12.2 21.1 / 15.6 23.9 / 17.2 26.7 / 19.4 29.4 / 21.7 32.2 / 22.8 (°CDB) -10.0 4.41 2.75 4.99 3.13 5.26 3.61 5.63 4.05 6.02 4.43 6.20 5.08 -5.0 4.41...
  • Page 272 ¢ Wall mounted type  Unit: kBtu/h, °F • TC: Total Capacity (kBtu/h), SHC: Sensible Heat Capacity (kBtu/h). • The data is based on the following conditions. • Pipe length: 24.6 ft (7.5 m), Height difference: 0 ft (0 m) [Outdoor unit - Indoor unit] MODEL: ASU7RLF1 Indoor temperature (°FDB / °FWB) Outdoor temperature...
  • Page 273 MODEL: ASUH07LPAS Indoor temperature (°FDB / °FWB) Outdoor temperature 64.0 / 54.0 70.0 / 60.0 75.0 / 63.0 80.0 / 67.0 85.0 / 71.0 90.0 / 73.0 (°FDB) 14.0 5.88 4.12 6.65 4.70 7.01 5.41 7.50 6.08 8.02 6.64 8.27 7.61 23.0 5.88...
  • Page 274 MODEL: ASUH18LPAS Indoor temperature (°FDB / °FWB) Outdoor temperature 64.0 / 54.0 70.0 / 60.0 75.0 / 63.0 80.0 / 67.0 85.0 / 71.0 90.0 / 73.0 (°FDB) 14.0 15.05 10.03 17.01 11.43 17.93 13.16 19.20 14.78 20.52 16.17 21.16 18.53 23.0 15.05...
  • Page 275  Unit: kW, °C • TC: Total Capacity (kW), SHC: Sensible Heat Capacity (kW). • The data is based on the following conditions: Pipe length: 24.6 ft (7.5 m), Height difference: 0 ft (0 m) [Outdoor unit - Indoor unit] MODEL: ASU7RLF1 Indoor temperature (°CDB / °CWB) Outdoor temperature...
  • Page 276 MODEL: ASUH07LPAS Indoor temperature (°CDB / °CWB) Outdoor temperature 17.8 / 12.2 21.1 / 15.6 23.9 / 17.2 26.7 / 19.4 29.4 / 21.7 32.2 / 22.8 (°CDB) -10.0 1.72 1.21 1.95 1.38 2.05 1.58 2.20 1.78 2.35 1.95 2.42 2.23 -5.0 1.72...
  • Page 277 MODEL: ASUH18LPAS Indoor temperature (°CDB / °CWB) Outdoor temperature 17.8 / 12.2 21.1 / 15.6 23.9 / 17.2 26.7 / 19.4 29.4 / 21.7 32.2 / 22.8 (°CDB) -10.0 4.41 2.94 4.99 3.35 5.26 3.86 5.63 4.33 6.02 4.74 6.20 5.43 -5.0 4.41...
  • Page 278 ¢ Floor type  Unit: kBtu/h, °F • TC: Total Capacity (kBtu/h), SHC: Sensible Heat Capacity (kBtu/h). • The data is based on the following conditions: Pipe length: 24.6 ft (7.5 m), Height difference: 0 ft (0 m) [Outdoor unit - Indoor unit] MODEL: AGU9RLF Indoor temperature (°FDB / °FWB) Outdoor temperature...
  • Page 279  Unit: kW, °C • TC: Total Capacity (kW), SHC: Sensible Heat Capacity (kW). • The data is based on the following conditions: Pipe length: 24.6 ft (7.5 m), Height difference: 0 ft (0 m) [Outdoor unit - Indoor unit] MODEL: AGU9RLF Indoor temperature (°CDB / °CWB) Outdoor temperature...
  • Page 280: Heating Capacity

    6-3. Heating capacity ¢ Model: AOU45RLXFZ NOTE: Values mentioned in the table are calculated based on the maximum capacity.  Unit: kBtu/h, °F TC: Total Capacity (kBtu/h), IP: Input Power (kW) Indoor temperature Indoor unit connect- Outdoor temperature ing capacity 60 °FDB 65 °FDB 70 °FDB...
  • Page 281 Indoor temperature Indoor unit connect- Outdoor temperature ing capacity 60 °FDB 65 °FDB 70 °FDB 75 °FDB 78 °FDB kBtu/h °FDB °FWB 33.1 4.70 32.3 4.80 31.5 4.90 30.8 5.00 30.0 5.10 37.3 4.70 36.5 4.80 35.6 4.90 34.7 5.00 33.8 5.10 41.6...
  • Page 282 Indoor temperature Indoor unit connect- Outdoor temperature ing capacity 60 °FDB 65 °FDB 70 °FDB 75 °FDB 78 °FDB kBtu/h °FDB °FWB 28.0 3.93 27.3 4.01 26.6 4.10 26.0 4.18 25.3 4.26 31.5 3.93 30.8 4.01 30.0 4.10 29.3 4.18 28.5 4.26 35.1...
  • Page 283  Unit: kW, °C TC: Total Capacity (kW), IP: Input Power (kW) Indoor temperature Indoor unit connect- Outdoor temperature ing capacity 15.6 °CDB 18.3 °CDB 21.1 °CDB 23.9 °CDB 25.6 °CDB kBtu/h °CDB °CWB -15.0 -16.1 9.70 4.70 9.47 4.80 9.20 4.90 9.01...
  • Page 284 Indoor temperature Indoor unit connect- Outdoor temperature ing capacity 15.6 °CDB 18.3 °CDB 21.1 °CDB 23.9 °CDB 25.6 °CDB kBtu/h °CDB °CWB -15.0 -16.1 9.70 4.70 9.47 4.80 9.20 4.90 9.01 5.00 8.78 5.10 -10.0 -11.1 10.94 4.70 10.68 4.80 10.40 4.90 10.16...
  • Page 285 Indoor temperature Indoor unit connect- Outdoor temperature ing capacity 15.6 °CDB 18.3 °CDB 21.1 °CDB 23.9 °CDB 25.6 °CDB kBtu/h °CDB °CWB -15.0 -16.1 7.98 3.83 7.79 3.91 7.60 3.99 7.41 4.07 7.22 4.15 -10.0 -11.1 8.99 3.83 8.78 3.91 8.50 3.99 8.35...
  • Page 286  Unit: kBtu/h, °F • TC: Total Capacity (kBtu/h). • The data is based on the following conditions: Pipe length: 24.6 ft (7.5 m), Height difference: 0 ft (0 m) [Outdoor unit - Indoor unit] MODEL: ACUH07LUAS1 Indoor temperature (°FDB) Outdoor temperature 60.0 65.0...
  • Page 287  Unit: kW, °C • TC: Total Capacity (kW). • The data is based on the following conditions: Pipe length: 24.6 ft (7.5 m), Height difference: 0 ft (0 m) [Outdoor unit - Indoor unit] MODEL: ACUH07LUAS1 Indoor temperature (°CDB) Outdoor temperature 15.6 18.3...
  • Page 288 ¢ Slim duct type  Unit: kBtu/h, °F • TC: Total Capacity (kBtu/h). • The data is based on the following conditions: Pipe length: 24.6 ft (7.5 m), Height difference: 0 ft (0 m) [Outdoor unit - Indoor unit] MODEL: ADUH07LUAS1 Indoor temperature (°FDB) Outdoor temperature 60.0...
  • Page 289 MODEL: ADUH24LUAS1 Indoor temperature (°FDB) Outdoor temperature 60.0 65.0 70.0 75.0 78.0 (°FDB) (°FWB) 17.66 17.24 16.82 16.40 15.98 14.0 12.0 19.92 19.44 18.97 18.49 18.02 23.0 19.0 22.17 21.64 21.11 20.59 20.06 32.0 28.0 25.83 25.21 24.60 23.98 23.37 41.0 37.0 29.49...
  • Page 290  Unit: kW, °C • TC: Total Capacity (kW). • The data is based on the following conditions: Pipe length: 24.6 ft (7.5 m), Height difference: 0 ft (0 m) [Outdoor unit - Indoor unit] MODEL: ADUH07LUAS1 Indoor temperature (°CDB) Outdoor temperature 15.6 18.3...
  • Page 291 MODEL: ADUH24LUAS1 Indoor temperature (°CDB) Outdoor temperature 15.6 18.3 21.1 23.9 25.6 (°CDB) (°CWB) -15.0 -16.1 5.18 5.05 4.93 4.81 4.68 -10.0 -11.1 5.84 5.70 5.56 5.42 5.28 -5.0 -7.2 6.50 6.34 6.19 6.03 5.88 -2.2 7.57 7.39 7.21 7.03 6.85 8.64 8.44...
  • Page 292 ¢ Wall mounted type  Unit: kBtu/h, °F • TC: Total Capacity (kBtu/h). • The data is based on the following conditions: Pipe length: 24.6 ft (7.5 m), Height difference: 0 ft (0 m) [Outdoor unit - Indoor unit] MODEL: ASU7RLF1 Indoor temperature (°FDB) Outdoor temperature 60.0...
  • Page 293 MODEL: ASUH07LPAS Indoor temperature (°FDB) Outdoor temperature 60.0 65.0 70.0 75.0 78.0 (°FDB) (°FWB) 5.15 5.03 4.91 4.78 4.66 14.0 12.0 5.81 5.67 5.53 5.39 5.26 23.0 19.0 6.47 6.31 6.16 6.00 5.85 32.0 28.0 7.53 7.35 7.17 7.00 6.82 41.0 37.0 8.60...
  • Page 294 MODEL: ASUH18LPAS Indoor temperature (°FDB) Outdoor temperature 60.0 65.0 70.0 75.0 78.0 (°FDB) (°FWB) 13.25 12.93 12.62 12.30 11.99 14.0 12.0 14.94 14.58 14.23 13.87 13.51 23.0 19.0 16.63 16.23 15.84 15.44 15.04 32.0 28.0 19.37 18.91 18.45 17.99 17.53 41.0 37.0 22.12...
  • Page 295  Unit: kW, °C • TC: Total Capacity (kW). • The data is based on the following conditions: Pipe length: 24.6 ft (7.5 m), Height difference: 0 ft (0 m) [Outdoor unit - Indoor unit] MODEL: ASU7RLF1 Indoor temperature (°CDB) Outdoor temperature 15.6 18.3...
  • Page 296 MODEL: ASUH07LPAS Indoor temperature (°CDB) Outdoor temperature 15.6 18.3 21.1 23.9 25.6 (°CDB) (°CWB) -15.0 -16.1 1.51 1.47 1.44 1.40 1.37 -10.0 -11.1 1.70 1.66 1.62 1.58 1.54 -5.0 -7.2 1.90 1.85 1.80 1.76 1.71 -2.2 2.21 2.16 2.10 2.05 2.00 2.52 2.46...
  • Page 297 MODEL: ASUH18LPAS Indoor temperature (°CDB) Outdoor temperature 15.6 18.3 21.1 23.9 25.6 (°CDB) (°CWB) -15.0 -16.1 3.88 3.79 3.70 3.61 3.51 -10.0 -11.1 4.38 4.27 4.17 4.07 3.96 -5.0 -7.2 4.87 4.76 4.64 4.53 4.41 -2.2 5.68 5.54 5.41 5.27 5.14 6.48 6.33...
  • Page 298 ¢ Floor type  Unit: kBtu/h, °F • TC: Total Capacity (kBtu/h). • The data is based on the following conditions: Pipe length: 24.6 ft (7.5 m), Height difference: 0 ft (0 m) [Outdoor unit - Indoor unit] MODEL: AGU9RLF Indoor temperature (°FDB) Outdoor temperature 60.0...
  • Page 299  Unit: kW, °C • TC: Total Capacity (kW). • The data is based on the following conditions: Pipe length: 24.6 ft (7.5 m), Height difference: 0 ft (0 m) [Outdoor unit - Indoor unit] MODEL: AGU9RLF Indoor temperature (°CDB) Outdoor temperature 15.6 18.3...
  • Page 300: Capacity Compensation Rate For Pipe Length And Height Difference

    7. Capacity compensation rate for pipe length and height difference Height difference H Indoor unit is higher than outdoor unit Indoor unit is lower than outdoor unit Outdoor unit Indoor unit Outdoor unit Indoor unit Connection pipe Connection pipe 7-1. Model: AOU45RLXFZ NOTE: Values mentioned in the table are calculated based on the maximum capacity.
  • Page 301 ¢ Indoor unit: 9,000 Btu Pipe length COOLING — — — 0.956 0.942 0.928 — — 0.977 0.963 0.950 0.936 Indoor unit is higher than outdoor unit *1 — 0.988 0.981 0.967 0.954 0.940 0.999 0.992 0.985 0.971 0.957 0.943 1.007 1.000 0.993...
  • Page 302 ¢ Indoor unit: 14,000 Btu Pipe length COOLING — — — 0.955 0.937 0.922 — — 0.974 0.962 0.945 0.930 Indoor unit is higher than outdoor unit *1 — 0.988 0.978 0.966 0.948 0.934 0.997 0.992 0.982 0.970 0.952 0.937 1.005 1.000 0.990...
  • Page 303 ¢ Indoor unit: 24,000 Btu Pipe length COOLING — — — 0.978 0.969 0.953 — — 0.986 0.986 0.977 0.961 Indoor unit is higher than outdoor unit *1 — 0.988 0.990 0.990 0.981 0.965 0.989 0.992 0.994 0.994 0.984 0.968 0.997 1.000 1.002...
  • Page 304: Additional Charge Calculation

    8. Additional charge calculation 8-1. Model: AOU45RLXFZ Refrigerant type R410A lb oz 8 lb 13 oz Refrigerant amount 4,000 ¢ Refrigerant charge 164 (50) 0.22 oz/ft Total pipe length ft (m) 197 (60) 230 (70) 262 (80) (Max.) or less (20 g/m) Additional charge lb oz (g)
  • Page 305: Airflow

    9. Airflow 9-1. Model: AOU45RLXFZ  Cooling 4,200 1,167 2,472  Heating 4,200 1,167 2,472 - 299 - 9-1. Model: AOU45RLXFZ 9. Airflow...
  • Page 306: Operation Noise (Sound Pressure)

    10. Operation noise (sound pressure) 10-1. Noise level curve ¢ Model: AOU45RLXFZ  Cooling  Heating NC-65 NC-65 NC-60 NC-60 NC-55 NC-55 RATING RATING NC-50 NC-50 NC-45 NC-45 QUIET QUIET NC-40 NC-40 NC-35 NC-35 NC-30 NC-30 NC-25 NC-25 NC-20 NC-20 NC-15 NC-15 1,000...
  • Page 307: Electrical Characteristics

    11. Electrical characteristics Model name AOU45RLXFZ Voltage 208/230 ~ Power supply Frequency 28.9 Starting current 20.1 CKT. BKR Wiring spec. * Power cable *: Selected sample based on Japan Electrotechnical Standards and Codes Committee E0005. As the regulations of wire size and circuit breaker differ in each country or region, select appropriate de- vices complied to the regional standard.
  • Page 308: Safety Devices

    12. Safety devices Model Type of protection Protection form AOU45RLXFZ 250 V, 10 A 250 V, 5 A Current fuse (PCB) 400 V, 5 A Circuit protection 250 V, 3.15 A Protector 500 V, 45 A (PCB) 239±27 °F Activate (115±15 °C) Fan motor stop Fan motor protection...
  • Page 309: Function Settings

    13. Function settings 13-1. Setting methods WARNING Never touch electrical components such as the terminal blocks or reactor except the switch on the display board. It may cause a serious accident such as electric shock. CAUTION • Once refrigerant charging is completed, be sure to open the valve prior to performing the local settings.
  • Page 310 ¢ Setting method 1. Be sure to disconnect the power supply or turn off the breaker. 2. Change the DIP switch setting according to the required setting. • Various settings can be adjusted by changing DIP switches and push switches on the board of the outdoor unit.
  • Page 311 ¢ Description of display LED display lamp Function or operation method • Turns on when the power supply is ON (Including when error occurs). (1) POWER/MODE Green • Indicate the MODE by the number of flashes when the installation function is active. (2) ERROR Flashes at high-speed when there is an error.
  • Page 312: 13-2.Outdoor Unit Low Noise Operation Function (Option)

    13-2. Outdoor unit low noise operation function (option) Change the outdoor unit low noise operation by using this setting. Optional Central remote controller is necessary to use this function. SET2-1 Setting Factory setting Lower ♦ CAUTION • When the low noise operation function is working, cooling and heating capacity will decrease. •...
  • Page 313: Check And Test

    14. Check and test 14-1. Check run • The check run is a function to screen and detect any wiring errors. • After carrying out the check run, you can use the automatic wiring correction function to correct the wiring. •...
  • Page 314 ¢ Operating procedure for check run CAUTION Initiate check run after more than 12 hours after the power supply is connected. NOTE: Be sure that the indoor unit and outdoor unit are not operating before starting the check run. 1. Press the "CHECK" switch for 3 seconds or more. CHECK 2.
  • Page 315 4. After the check run is completed, results will be displayed. Fill the displayed results in the result table accordingly. • If the connection is correct (Example: When 4 indoor units are connected) After the number of connected units are displayed, the LED for each unit will light up in order from A to D.
  • Page 316 [How to record the contents] • Fill the displayed results according to the following example. Example: When piping A to D is connected but the wires for B and C are connected in reverse. <Displayed results> The LEDs will light up in 7 second intervals in the following order. POWER ERROR MONITOR...
  • Page 317 NOTES: • *1: By using this function, the wiring is automatically corrected according to the piping. • *2: When correcting the wiring manually, please disconnect the power supply or turn off the breaker during results display, and then change the wiring manually according to the obtained test results.
  • Page 318 ¢ Check run judgment failure display If check run cannot be performed, the following is displayed. In this case, the check run will stop. Please check by using the cooling test run of the indoor unit.  Temperature out of range judgment POWER ERROR MONITOR...
  • Page 319: 14-2.Test Run

    14-2. Test run CAUTION Always connect the power supply 12 hours prior to the start of the operation in order to protect the compressor. 1. Indoor unit a. Is the drain normal? b. Is there any abnormal noise and vibration during operation? 2.
  • Page 320 5. Press "TEST RUN" switch for more than 3 seconds. POWER ERROR MONITOR MODE POWER/MODE LED will turn on, and test run stops. - 314 - 14-2. Test run 14. Check and test...
  • Page 321: 14-3.Error Code

    14-3. Error code If an error occurs, the LED will light up to display the error location and the error code. ¢ In the event of an error The error LED blink quickly. POWER ERROR MONITOR MODE blink (High-speed) ¢ Error location display LEDs A to F of MONITOR light up and display the error location.
  • Page 322 ¢ Error code display While the error is occurring, briefly press SW1. The error code is displayed. Example: Coil error (Error cord = 9A.1) POWER ERROR MONITOR MODE Blink [A(10)] (High-speed) (9-blink) Display mode LED on: LED off: Blink: (0.5s Light on / 0.5s Light off) Number of blinking: ( )
  • Page 323 Error code Error type 11.3 Serial communication error 11.4 Serial communication error during operation 16.5 Communication error between controller and outdoor unit 22.1 Indoor unit capacity error 5U.1 Indoor unit error 62.1 PCB model information error 62.3 EEPROM access error 62.8 EEPROM data corruption error 63.1...
  • Page 324: 14-4.Pump Down

    14-4. Pump down WARNING During the pump down operation, make sure that compressor is off before you remove the refriger- ant pipe. Do not remove the connection pipe while the compressor is in operation with valve open. This may cause abnormal pressure in the refrigeration cycle that leads to breakage and even injury. ¢...
  • Page 325 7. Disconnect the power supply or turn off the breaker. NOTE: If the pump down is not stopped by pressing the switch as in step 6, it will stop auto- matically after 15 minutes and the LED will light as follows. If the pump down is com- plete, disconnect the power supply or turn off the breaker.
  • Page 326: Accessories

    15. Accessories Part name Exterior Q’ty Part name Exterior Q’ty Installation manual Drain cap Adapter K 1/2 in (12.70 mm) Drain pipe 2 set 3/8 in (9.52 mm) Adapter L Cable tie with clip 1/2 in (12.70 mm) 2 set (Large) 5/8 in (15.88 mm) Adapter H...
  • Page 327: Optional Parts

    16. Optional parts Exterior Part name Model name Summary For 2 units combination system It can exchange liquid pipe size Ø1/4 in. (Ø6.35mm) for Ø3/8 in. (Ø9.52mm) Adapter Kit UTP-MU45A2 If you choose the combination of ASUH24LPAS and ASU7-15RLF1, you need this kit. Set temperatures on timers to best meet individuals’...
  • Page 328: Outdoor Unit Installation Precautions

    17. Outdoor unit installation precautions NOTE: The information listed below are general precautions. Some models also include items that do not apply. 17-1. Places where prohibited for use • Places where there is a danger of combustible gas leakage. • Places where sulfur gas, chlorine gas, acid, alkali, or other matter which effects equipment is gen- erated.