Do not use if the compartment is not secure. WE RECOMMEND THAT THE INSTALLATION OF YOUR BLAZE WOOD HEATER BE CARRIED OUT BY A Dispose of used button batteries immediately and QUALIFIED INSTALLER.
The dimensions given in the table and image represent the minimum clearance (in millimetres) to combustible materials, such as a mantelpiece with columns, when installed in a non-combustible fireplace. If a combustible mantelpiece is present, a Mantelpiece Shield must be installed (refer to section “2.3. Mantlepiece Shield”). CLEARANCES MASONRY INSTALLATION B520 B820 A (Width between mantelpiece columns) 900mm 1020mm B (Height to mantelpiece from hearth)
0.33W/m ºK) or brick. ● The dimensions can be larger than the minimum dimensions given here if desired. ● The floor protector may be laid directly on the combustible floor. ● For more details and variations on floor protectors refer to AS/NZS 2918 Clause 2.2, 3.3.1, & 3.3.2. CLEARANCES FLOOR PROTECTOR B520 B820 CEMENT CEMENT Hearth Material (or equivalent) BRICK BRICK SHEET SHEET E (Thickness)
2.3. MANTELPIECE SHIELD Slide lower shield until the front is 2mm inside from the edge of the mantelpiece. If If the installation contains a mantelpiece made the mantelpiece depth is greater than the of combustible material, the Mantelpiece Shield reach of the shield, slide to fully extended (which needs to be ordered separately) must be position.
ZERO CLEARANCE INSTALLATION CLEARANCES ZERO CLEARANCE INSTALLATION Refer to this section for clearance requirements and instructions if the heater is to be in a zero B520 B820 clearance installation. A (Rear internal) 40mm 40mm A licensed accredited installer should install all wood heaters.
Page 9
SIDE WALL CEMENT SHEET STEEL CHANNEL TOP VIEW ENCLOSURE CHANNEL ASSEMBLY VENTED OUTER CASING ZERO CLEARANCE BASE ON 900mm WIDE CEMENT SHEET FRONT VIEW...
5mm, measuring 900mm wide x 545mm deep. Any wider, and it will restrict the ventilation from the B520 installations require two vents, each with a lower vents past the appliance. minimum free area of 7350mm², fitted on either...
A 4mm thick facia can be installed on the unit The baffle plate should be installed before (supplied separately). Four facia options are installing the fire bricks. available for each model (B520 or B820). Place the baffle inside the firebox with the Fascia 4 Sided 50mm (50mm visible edges) slotted fold directed downwards and at the rear of the firebox (refer to following diagram for correct orientation).
INSTALLING THE FIRE BRICKS Place the bricks into the firebox as shown in the diagrams below for the B520 and B820. Once bricks are in, fit the retainer over the top to hold them in place. B520: ● Two full size (220 x 175 x 25) and one (220 x 140 x 25) along the back. ● One full size and one half size (220 x 85 x 25) along each side.