4.5.2 Functions only available via IO-Link communication
• HIPC: number of overload processes (→ 9.6.2)�
• HIPS: threshold for the overload counter (→ 9.6.2)�
• Flash: via this standard command, the sensor can be localised in the plant�
When the command is used, the switching status LEDs flash and "IO-L" is
displayed� (Function only available in operating mode [3])�
• Application Specific Tag: freely definable text assigned to the unit�
• Function Tag: freely definable text describing the device function in the plant�
(Function only available in operating mode [3])�
• Location Tag: freely definable text describing the installation location in the
plant� (Function only available in operating mode [3])�
For more detailed information refer to the device-specific IO Device Description
PDF at www�ifm�com�

5 Installation

Before installing and removing the unit: Make sure that no pressure is
applied to the system�
► Insert the unit in a ¼ - 18 NPT process connection�
► Tighten firmly. Recommended tightening torque: ≤ 50 Nm
Depends on lubrication, seal and pressure load!
The sensor housing can be rotated by 345° with regard to the process connection�
Do not rotate past the end stop!