Technical Details

Energy Monitor (INHEM1216)
Supported system configurations:
• Single phase, 2-wire systems
• Single-split phase, 3-wire systems
• 3-phase, 4-wire Wye systems with earthed (TN or TT) neutral (no-Delta)
• Fuse: 260VAC/0.3A (Fusible resistor: 10E, 1W, 5%, TH)
• Maximum voltage sense range: 264VAC L-N per channel Power usage: < 3 Watts
• Wi-Fi: 2.4 GHz IEEE 802.11b/g/n
• Ethernet: 10/100Base-T, IEEE 802.3
• Operating conditions: -40° - 122° F (-40° - 50° C) | 0-80% RH 3,000 meters above
sea level | Indoor | Dry location Pollution Degree 2
Terminals:
• Ethernet: Cat5e, RJ45, 600V insulation required
• WiFi: SMA coaxial cable, 50Ω impedance, 600V insulation required
• Voltage Terminals:
- ~100-240VAC line-to-neutral, 50/60Hz, 41mA, Overvoltage / Measurement
CAT III
- Field terminal torque value: 5Lb-In/0.56Nm 16AWG, UL1015, 600V, 105C copper-
only wiring
• Main Current Transformer Terminals:
- 3.3V, 1mA, Measurement CAT IV
- Field terminal torque value: 5Lb-In/0.56Nm 22AWG, UL1015, 600V, 105C
copper-only wiring
• Branch Current Transformer Terminals:
- 3.3V, 1mA, Measurement CAT III
- Field terminal torque value: 3Lb-In/0.2Nm 22AWG, UL1015, 600V, 105C
copper-only wiring
Main Current Transformers (INHEM010)
• Max Primary Current: 200A
• Max Voltage: 250V (Primary) / 333mV (Secondary)
• Burden Resistor: 5ohm, 1%, 1/4W
• Cable length: 1m
• Inside diameter: 22 mm
• Accuracy: ±2%
Branch Current Transformers (INHEM001)
• Max Primary Current: 50A
• Max Voltage: 250V (Primary) / 333mV (Secondary)
• Burden Resistor: 20ohm, 1%, 1/4W
• Cable length: 1m
• Inside diameter: 10 mm
• Accuracy: ±2%