UL, ULC Listed*
Features
Releasing control using the Autocall 4010ES Fire Alarm Control
Unit to provide:
• Coverage for multiple areas of Automatic Extinguishing Release and/
or Deluge and Preaction Sprinkler System Release including audible
escalation of events
• Control of compatible Listed/Approved 24 VDC automatic control
actuators, one per circuit; or two 12 VDC actuators in series per circuit
• Releasing appliance circuits (RACs) by connecting Notification appliance
circuits (NACs) to Suppression Release Peripherals for actuator
supervision and control
• Four, 3 Amp Notification Appliance Circuits (NACs) in the control unit
for use with Suppression Release Peripherals (SRP) and required
notification appliances
• Additional actuator circuit control and additional NACs are available
using 4009 IDNet Addressable NAC Extenders and Suppression
Release Peripherals
Audible Escalation of Events:
• Temporal or 20 bpm March Time pattern for first cross zone alarm
• 120 bpm March Time pattern indicates releasing timer active
• On steady indicates releasing timer expired and actuator is activated
• Requires NACs dedicated to conventional horn control (not SmartSync
operation) with strobes controlled on separate NACs
4009 IDNet NAC Extenders provide:
• Up to eight NACs for notification requirements and for NAC input to
Suppression Release Peripherals
• Control is via IDNet addressable communications
A4090-9005/A4090-9006 Suppression Release Peripheral (SRP)
with Dual Input Control Logic:
• Dual input control logic requires that both IDNet communications
commands and an activated NAC are present to initiate the desired
release
• Releasing Appliance Circuit (RAC) output provides wiring supervision
to the actuator including monitoring of coil continuity and short circuit
supervision to the coil supervision module
Suppression Release Peripheral control features:
• An on-board DC-DC regulator compensates for voltage drops to the
peripheral and ensures proper control circuit voltage over a wide
operating range
• Provides a single RAC for control of actuators for up to 2 A using a 3 A
NAC input (1 A using a 2 A NAC input)
Related system components
• 4010ES Series control unit with Releasing Appliqué
• Dedicated NAC output from 4010ES (or compatible NAC Extender)
• Coil supervision module, one per RAC
• Maintenance Switch, one per RAC
• Abort Switch connected via an addressable interface module
* Additional listings may be applicable; contact your local Product supplier for the latest status.
4010ES Automatic Extinguishing, Deluge and Preaction Sprinkler System Releasing
Figure 1: 4010ES Release Control
Simplified Block Diagram
Introduction
When combined with Suppression Release Peripherals, the 4010ES
series fire alarm control unit provides actuator supervision and control
for use in automatic extinguishing, and deluge or preaction releasing
systems. Hazard area initiating and notification devices are controlled
using either conventional or addressable circuits per standard 4010ES
capabilities. The necessary releasing system logic is implemented within
the 4010ES control unit as required for the local application.
Agency Listings
UL 864 - Control Units, System (UOJZ); Control Unit Accessories, System,
Fire Alarm (UOXX); Control Units, Releasing Device Service (SYZV); Smoke
Control System Equipment (UUKL)
UL 1076 - Proprietary Alarm Units (APOU)
UL 1730 - Smoke Detector Monitors and Accessories (UULH)
UL 2017 - Emergency Alarm System Control Units, CO detection (FSZI);
Process Equipment Management (QVAX)
ULC-S527 - Control Units, System, Fire Alarm (UOJZC); Control Unit
Accessories, System, Fire Alarm (UOXXC); Control Units, Releasing Device
Service (SYZVC); Smoke Control System Equipment (UUKLC)
4010ES Fire Control Units
Control
AC4010-0005 Rev. 10 5/2017