Capacitor voltage transformer
Table of Contents

Advertisement

Instruction Manual
Example of wood blocking pieces
NEVER lift a transformer by its
primary terminal. Always lift it by
the four lifting holes on the
bottom tank and as per indicated
in the next pictures.
Horizontal packaging
1) Remove the upper cover.
2) Remove 3 side covers (except the side
on which the basetank is fixed with
screws)
© GE Grid Solutions
3) Remove the four screws at the
equipment feet.
4) Remove the green nylon slings
5) Remove the CVT and lift it following
the next steps:
- Use two slings, one at the neck of the
insulator and other at the lifting holes of
the basetank.
- Remove the CVT keeping it in horizontal
position
- Gradually put the CVT in vertical
position by lifting the sling placed in the
neck of the insulator. Keep always the
sling in vertical position. Handle with
care in order do not damage the bellow
flange.