Electrical Wiring - Airxcel Coleman-Mach 48000 Series Installation, Operation And Maintenance Instructions

Table of Contents

Advertisement

Available languages

Available languages

Follow the steps below to secure the Heat Pump to the
roof. Refer to Figure 4.
1. Locate the Heat Pump mount gasket over the 14"
to 15" square opening in the roof.
2. Install the ceiling assembly mount frame using the
four bolts found with the ceiling assembly.
V. ELECTRICAL WIRING
ROUTING 115 VAC WIRING
Following Airxcel's high voltage wiring specifications
and all local and national electrical codes, route the
roof top unit 115 VAC supply wiring from its power
source
to
the
wirebox.
Specifications
based
Protection Device Amperage – (see upper unit
nameplate)
1. U.L. requires copper conductors only with minimum
#12 AWG when using the minimum recommended
overcurrent protection device. Higher rated devices or
longer wiring runs will require #10 AWG or greater
copper conductors.
2. To prevent voltage drops greater than 10% during
starting loads, adhere to the following guideline:
For lengths greater than 50', use #10 AWG or
larger copper conductors. Match to the overcurrent
protection device provided.
Circuit Protection – Refer to upper unit nameplate.
Electrical
Wiring
Specification is
Protection Device rated higher than the minimum
required (see upper unit nameplate).
Follow all local and NEC (National Electrical Code)
for proper sizing of wire AWG based on
Overcurrent Protection Device selected and the
length of the wiring run to the Heat Pump.
DANGER – SHOCK HAZARD
MAKE SURE THAT ALL POWER SUPPLY TO
THE
UNIT
IS
DISCONNECTED
PERFORMING ANY WORK ON THE UNIT TO
AVOID THE POSSIBILITY OF SHOCK INJURY
OR DAMAGE TO THE EQUIPMENT.
High
Voltage
on
Minimum
Overcurrent
High
Voltage
based
on
Overcurrent
BEFORE
3.
Proper tension has been achieved for each bolt
when any portion of each gasket indicating tab has
been pulled down even with the roof. See Figure
4. The upper unit has now been properly installed
with optimum gasket compression.
WHEN USING NON-METALLIC SHEATH CABLES
(ROMEX,
EXPOSE 4-6 INCHES OF THE SUPPLY LEADS.
STRIP THE INDIVIDUAL WIRE LEAD ENDS FOR
Wiring
WIRE CONNECTION (ABOUT 3/4" BARE WIRE).
INSERT
ELECTRICAL CONNECTOR CLAMP.
MUST PROTRUDE PAST THE CLAMP BUSHING
INSIDE THE BOX AS ILLUSTRATED.
SHEATH
BEFORE
CABLE!! DO NOT OVERTIGHTEN!!
THIS COULD RESULT IN PINCHING THROUGH
THE PLASTIC WIRE INSULATION AND CAUSE
SHORTING OR "HOT" WIRES TO GROUND
(SHOCK HAZARD).
FOR STRAIN RELIEF OF THE WIRES. SLIGHT
PRESSURE
ACCOMPLISH THIS.
IF OTHER THAN NON-METALLIC CABLES ARE
Wiring
USED
APPROPRIATE
OR CLAMPS SHOULD BE USED.
IN NO CASE SHOULD CLAMPING OR PINCHING
ACTION BE APPLIED TO THE INDIVIDUAL SUPPLY
LEADS (NEUTRAL AND "HOT" WIRES).
TO PREVENT THE POSSIBILITY OF SHOCK
INJURY, THE WHITE WIRE MUST BE CONNECTED
TO NEUTRAL IN THE SERVICE BOX ENTRANCE
AND THE MECHANICAL GROUND LUG MUST BE
CONNECTED TO A GROUNDING LUG EITHER IN
THE SERVICE BOX OR THE MOTOR GENERATOR
COMPARTMENT.
4
Figure 4
DANGER!
ETC.),
STRIP
SHEATH
THE
SUPPLY
WIRES
CABLE
IS
CENTERED
TIGHTENING
CLAMP
THE CLAMP IS INTENDED
IS
USUALLY
SUFFICIENT
FOR
SUPPLY
STRAIN RELIEF CONNECTORS
DANGER – SHOCK HAZARD
BACK
TO
INTO
THE
SHEATH
MAKE SURE
IN
CLAMP
ON
SHEATH
TO
CONDUCTORS,

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the Coleman-Mach 48000 Series and is the answer not in the manual?

Questions and answers

Eric Jacobson
April 21, 2025

I need to power two of these 48000 units for my rv, but cannot find what BTU capacity they have. Can you tell me this and maybe recommend generator size I need?

RUTH Mary ROTTON
April 24, 2025

Which Mach is my rv ac? Model #48254C969, Serial #140710032

Table of Contents

Save PDF