Series TY-B — 57, 80, and 115 K-factor
Upright and Pendent Sprinklers
Special Response, Standard Coverage
IMPORTANT
Refer to Technical Data Sheet
TFP2300 for warnings pertaining to
regulatory and health information.
Always refer to Technical Data
Sheet TFP700 for the "INSTALLER
WARNING" that provides cautions
with respect to handling and instal-
lation of sprinkler systems and com-
ponents. Improper handling and
installation can permanently damage
a sprinkler system or its compo-
nents and cause the sprinkler to fail
to operate in a fire situation or cause
it to operate prematurely.
Scan the QR code or enter the URL
in a web browser to access the most
up-to-date electronic version of this
document. Data rates may apply.
docs.jci.com/tycofire/tfp672
Page 1 of 4
General
Description
The Series TY-B, 57, 80, and 115 K-fac-
tor, Upright and Pendent Sprinklers
described in this data sheet are special
response - standard coverage, decora-
tive 4 mm glass bulb type spray sprin-
klers designed for use in accordance
with the installation rules recognized by
the applicable Approval agency (e.g.,
VdS).
NOTICE
The Series TY-B Sprinklers described
herein must be installed and main-
tained in compliance with this docu-
ment, as well as with the applicable
standards recognized by the Approval
agency, in addition to the standards of
any other authorities having jurisdiction.
Failure to do so may impair the perfor-
mance of these devices.
The owner is responsible for main-
taining their fire protection system
and devices in proper operating con-
dition. Contact the installing contrac-
tor or product manufacturer with any
questions.
Sprinkler
Identification
Numbers (SINs)
TY2149 Upright 57K
TY2249 Pendent 57K
TY3141 Upright 80K
TY3241 Pendent 80K
TY4141 Upright 115K
TY4241 Pendent 115K
AUGUST 2022
Worldwide
www.tyco-fire.com
Contacts
Technical
Data
Approvals
VdS Approved (CEA 4001)
Maximum Working Pressure
12,1 bar
Discharge Coefficient
K = 57 lpm/bar
½
K = 80 lpm/bar
½
K = 115 lpm/bar
½
Temperature Ratings
57°C, 68°C, 79°C, 93°C, and 141°C
Finishes
Refer to Table A
Physical Characteristics
Frame . . . . . . . . . . . . . . . . . . . . . . . . . . . .Bronze
Button . . . . . . . . . . . . . . . . . . . . . . Brass/Copper
Sealing Assembly . . Beryllium Nickel w/TEFLON
Bulb . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Glass
Compression Screw . . . . . . . . . . . . . . . . .Bronze
Deflector . . . . . . . . . . . . . . . . . . . . . . . . . Copper
Operation
The glass bulb contains a fluid which
expands when exposed to heat. When
the rated temperature is reached, the
fluid expands sufficiently to shatter the
glass bulb, allowing the sprinkler to
activate and water to flow.
TFP672