4.7.2
2-tube systems and are not designed to operate in the automatic Cool/Heat mode when more than one indoor unit is connected
to the same outdoor unit, but only in the cool or heat mode. Thus all indoor units connected to the same outdoor unit should be
changed from one mode to another at the same time. The same is applicable to the 3-tube SET-FREE FXG/FXN systems, for all
indoor units connected to the same CH Box.
However, operation in the Auto Cool/Heat mode is available through CSNET Manager.
In temperate seasons, CSNET Manager calculates the main need of the indoor units for each of the outdoor units in the systems
mentioned above, selects the mode needed for most of the units in the system and adjusts the remote controller accordingly.
With the aim of giving the system time to be established in a particular mode, its requirements are checked for at least 20 minutes
after the last change carried out. This process is continuous for as long as the indoor units are set to Auto.
If the systems are correctly designed, i.e. if all the indoor units of the same outdoor 2-tube unit have similar cooling and heating
demands, then it is possible to completely automate heating in the morning (for example), cooling in the afternoon and heating once
more at night.
Users maintain local control over the temperature in the room by the remote control.
There are two ways in which CSNET can decide whether the operation mode should be established in AUTO.
the unit is connected is 2 tube or 3 tube before deciding to change the operating mode.
Then, CSNET WEB calculates the difference to decide the best operation mode at that moment.
N O T E
2-tube models:
- SET-FREE FS3/FSG/FSN
- Mini SET-FREE FSVG/FSVN
- DC-Inverter HVRG/HVRN/HRN
- UTOPIA HG/HVG/HN/HNV
-
3-tube models:
-
60
PMML0409A rev.1 - 10/2016