Default I/O diagram of the inverter control unit
(UCU-22...24)
The table below describes the use of the connections in the inverter unit. Under normal
circumstances, the factory-made wiring should not be changed.
The wire size accepted by all screw terminals (for both stranded and solid wire) is
2
0.5 ... 2.5 mm
(22...12 AWG). The tightening torque is 0.45 N·m (4 lbf·in).
Terminal
XD2D
1
B
1
2
2
A
3
3
BGND
4
4
SHIELD
ON
XD2D.TERM
1
X485
5
B
5
6
6
A
7
7
BGND
8
8
SHIELD
ON
X485 BIAS
1
ON
X485 TERM
1
XCAN
9
CANH
9
10
10
CANL
11
11
CGND
12
12
SHIELD
XCAN TERM
1
ON
XRO1
11
NC1
11
12
12
COM1
13
13
NO1
XRO2
21
NC2
21
22
22
COM2
23
23
NO2
XRO3
Description
Drive-to-drive link
Drive-to-drive link. Refer to section
Drive-to-drive link termination switch.
RS485 connection
Not in use by default
X485 bias selection switch
X485 termination switch
CAN bus
Not supported
Control cable shield
CANopen termination switch
Relay output 1
Norm. closed
Common
Norm. open
Relay output 2
Norm. closed
Common
Norm. open
Relay output 3
Control units of the drive 159
The XD2D connector (page
XRO1: Ready (Energized = Ready)
250 V AC / 30 V DC, 2 A
XRO2: Running (Energized = Running)
250 V AC / 30 V DC, 2 A
163).