Akr - 30 S; Akr - 30 / 50 / T; Akr - GE AKR Manual

Low voltage power circuit breakers
Table of Contents

Advertisement

Close Button
The AKR electrically operated breaker is furnished as
standard without operating handle and is closed by receipt of
a signal provided by the
remote momentary
closure of a
contact
of a relay
or switch
.
A close button escutcheon
,
mounted
,
momentary contact is
available
when specified
.
Fuse Roll Out
The AKR
-
75 and
-
100 draw out
AKRU breakers require a
separate
fuse roll
out
.
All fuse roll
outs accept
Class L fuses
800
-
4000 A
.
The draw
out
breaker elements used in conjunc
-
tion with these fuse roll out elements should be equipped
with an open fuse lock
out
device
.
The breaker
component
should have provisions for key interlock
.
Open Fuse Lock Out Device
The open fuse lock out device automatically trips the breaker
if one of the fuses opens
.
The breaker is locked open until
the reset button of the phase involved is reset
.
0 PEN
fUSE
LOCKOUT
CAT
.
NO
.
425 D
362
G
1
COIL NO
RESET
IN
121
C 7 S
23
CS
OPENING
OP
*
N
EUSE
INDICATES
PUSH TO RESET
Af
TER
REPLACING
E
USE
Remote Close Solenoid
( For manually
-
operated
AKR
-
30 H ,
-
50 , AKRT
-
50 H
breakers )
The solenoid provides a
means
to electrically close
the above breakers from a
remote location
.
It may
be
controlled by a switch or
pushbutton for five
-
cycle
closing
.
Breaker must be
charged locally
.
Available
ratings : See Table 39.2
,
page 39
not
available on
AKR -
30
S
.
Maintenance
Closing Handle
The maintenance closing
handle is furnished as
standard ( one handle for
up
to
five breakers
.
)
The
maintenance handle is
provided for the slow closing
motion required during
contact adjustment proce
-
dures ( not required on
manually operated AKR
-
75
and 100 breakers
.
)
Reverse Current Device
The reverse
current device
is available for dc breakers
only
.
It is designed
to
trip the
breaker if
current
reverses
direction
.
Operations Counter
This accessory
mounts
on
the breaker as a five digit
,
non - resettable
counter
actuated by the breaker
cam shaft
.