Turning On The Power; Error Code; Setting Method When Connecting A Single Split Type Indoor Unit; Connection Of Remote Controller Cable - Fujitsu Airstage UTY-VGGXZ1 Installation Manual

Network convertor
Hide thumbs Also See for Airstage UTY-VGGXZ1:
Table of Contents

Advertisement

cannot be used more than once.
*
Example: When SW110 is set to "1" and SW111 is set to "4", the con-
vertor address will be "14".
Convertor address
0
SW110
 0
Rotary switch
SW111
 0
Convertor address
8
SW110
0
Rotary switch
SW111
8
[DIP switch - SW103]
Group remote controller convertor setting
Set the switches as follows.
DIP switch - SW103
1
2
3
4
Fixed
Fixed
Fixed
Fixed
at ON
at ON
at ON
at ON
[DIP switch - SW107, SW108, SW109]
Set the switches as follows.
DIP switch-SW107
DIP switch-SW108
1
2
1
Fixed
Fixed
Fixed
at OFF
at OFF
at OFF
9.

TURNING ON THE POWER

CAUTION
Check that the power supply voltage is within the specifi ed range. If
the power supply voltage outside the specifi cation is input, it will cause
trouble.
(1)
Check the network convertor wiring and switch settings on the
circuit board.
(2)
Check the wiring and switch settings for the VRF system. For the
wiring and switch settings method, refer to the installation instruc-
tion sheet of each unit.
(3)
Turn on the power for the VRF system.
(4)
Turn on the power for the network convertor.
The network convertor is initialized for a period of
ten seconds after turned on the power.
D129 during this period.
After initial setting completely the operation mode will
is displayed on D129.
*
Network convertor does not operate during initialization. Do not
attempt control from the units.
*
An error code will appear on D129 in the event of a malfunction.
10.

ERROR CODE

Error code
Contents
No error (operation
mode)
Main PCB error
Remote controller
communication error
1
2
3
4
5
6
0
0
0
0
0
0
1
2
3
4
5
6
9
10
11
12
13
14
15
0
1
1
1
1
1
9
0
1
2
3
4
(  : Factory setting)
5
6
7
8
Fixed at
Fixed at
Fixed at
Fixed at
OFF
OFF
OFF
OFF
DIP switch-SW109
2
1
2
Fixed
Fixed
Fixed
at OFF
at OFF
at OFF
approximately
is displayed on
be started.
Error code
Contents
Network communi-
cation error
EEPROM error
Address setting er-
ror
SETTING METHOD WHEN CONNECTING A SINGLE SPLIT
TYPE INDOOR UNIT
11.

CONNECTION OF REMOTE CONTROLLER CABLE

7
0
7
When connecting the remote controller cable to the indoor unit, do not
connect it to the outdoor unit or the power terminal block. It may cause
a failure.
1
5
When connecting Indoor unit and
Network convertor with the Remote
controller cable, the following items
should be considered.
POWER
SUPPLY
NETWORK CONVERTOR
There are 2 methods to connect the remote controller cable to the
indoor unit. One is the connection using contained connecting cable,
and the other is the connection the remote controller cable is connected
to the exclusive terminal block of the indoor unit.
Exclusive terminal block for remote controller connection method is dif-
ferent depending on each model. Modify the remote controller cable as
per below description and connect it.
(For the details, refer to the installation manual of the indoor unit to be
used.)
WHEN CONNECTING TO THE CONNECTOR
(1)
Connect the remote controller cable to the connecting cable, and insert
it to the connector.
Connecting cable
Remote controller cable
Modify the cable as per below methods.
Use a tool to cut off the terminal on the end of the remote controller
cable, and then remove the insulation from the cut end of the cable
as shown in Fig. 1.
Connect the remote controller cable and connecting cable as
shown in Fig. 2.
Be sure to insulate the connection between the cables.
Fig. 1
Remote
controller cable
White
Red
CAUTION
Indoor unit
remote controller
cable
K K
K
RC UNIT
UNIT
Indoor unit
Connector
PCB
Terminal block
to outdoor unit /
power supply
Fig. 2
White
Connector
Red
Black
Insulated
connection
Connecting
cable
Black
En-6