ELEQ TQ Installation Manual

Split-core current transformer

Advertisement

Quick Links

Technical Specifications
Safety and environmental conditions
CE marking
LV directive 2014/35/EU
RoHS directive (EU) 2015/863
Standard
EN 61010-2-032:2012
WEEE directive 2012/19/EU
This product is designed to be safe under the following
conditions:
Location
Indoor use
Altitude
Up to 2000m
Ambient temperature
-40°C .. +50°C
Storage temperature
-40°C .. +70°C
Relative humidity
5% .. 85%, non condensing
Pollution degree
2
Degree of protection
IP20
The TQ is only suitable for insulated primary conductors.
Specifications
Standard
Rated short-time thermal current (Ith)
Rated dynamic current (Idyn)
Rated continuous thermal current (Icth)
Rated insulation level
Rated frequency
Class of insulation
Material (housing)
Specifications per type
TQ120
Suitable for cable
Max. ø 45mm
Please be aware, product liability, fulfilment to requirements and
warranty are all expired when modifications on the product are made.
Printing and typographical reserved.
ELEQ reserves the right to carry out modifications on its products, in
order to improve them, without prior notice.
Safety instruction
All activities for installation, commissioning and maintenance
of this current transformer must be performed by qualified
personnel that have the knowledge of applicable safety
precautions. This guide assumes that the reader of this
document has sufficient electro-technical knowledge to
understand the content of this document.
General
The TQ split-core is a current transformer (CT) and can only
be used measuring electrical alternating currents. The TQ is
suitable only for mounting on insulated primary conductors in
a weather protected and dry location.
Explanation of symbols
IEC 61869-2:2012
100 x Ipr / 1s
2,5 x Ith
100%
0,72/3/-kV
50/60Hz
E (120°C)
PA, UL94: V2
This
product
is
designed
according
EN 61010-2-032:2012 standards and therefore this
product meets the requirements of the Low Voltage
Directive 2014/35/EU.
Do not apply around or remove from UNINSULATED
HAZARDOUS LIVE conductors, which may render
electric shock, electric burn, or arc flash.
Read the installation guide before mounting the
product. Unprofessional work activities on electrical
installations may result in a threat of danger to the life
and health of human beings and livestock!
Under no circumstances the secondary circuit of the
CT may be opened when the CT is closed and
current is flowing in the primary circuit. High voltages
may appear on the secondary leads when this circuit
is left open.
RoHS Directive (EU) 2015/863
ELEQ states that they only uses qualified components
in
their
products
from
manufacturers,
specifications meet or exceed the requirements of the
European Directive for the Restriction of use of
certain Hazardous Substances.
WEEE Directive 2012/19/EU
The 'crossed out wheeled bin' symbol indicates that
the equipment should not be disposed as unsorted
municipal waste. Contact a qualified recycler for
disposal.
84160 / EN2306
to
the
TQ Split-Core Current Transformer
Installation Guide
whose
TQ120
(4Q12xxx)
Read this installation guide before installing the product

Advertisement

loading
Need help?

Need help?

Do you have a question about the TQ and is the answer not in the manual?

Questions and answers

Summary of Contents for ELEQ TQ

  • Page 1 Technical Specifications General The TQ split-core is a current transformer (CT) and can only be used measuring electrical alternating currents. The TQ is Safety and environmental conditions suitable only for mounting on insulated primary conductors in CE marking LV directive 2014/35/EU a weather protected and dry location.
  • Page 2 CT (the two secondary terminals) must be short-circuited. Before changing the secondary circuit Connect the secondary leads (S1, S2) to the TQ the CT core shall be opened. terminals. Ensure that the leads are capable of carrying the current output of the CT.