PDU8000 DC Combiner Cabinet
User Manual
Figure 4-20 Extra length for easy plugging and unplugging
Figure 4-21 Neatly and loosely arranged
Laying Out Cables
Table 4-6 Layout rules
No.
1
2
3
4
5
6
7
8
Issue 02 (2022-08-10)
Layout Rule
The armoring layer of armored cables should be grounded.
The ground cable of the combiner cabinet should be securely
connected to the equipment room ground bar. The resistance
between the ground cable and the equipment room ground bar
should be less than 0.1 ohm.
Cables should be securely connected in the correct phase
sequence.
Cables should be arranged neatly and the cable insulation layer
should be intact.
Different types of cables should be routed separately.
Connection ports and cabling methods should facilitate
maintenance, cable routing, and capacity expansion.
Cable connectors prepared onsite should be secure, reliable, and
neat, and conform to specifications.
Power cables, ground cables, and signal cables should be securely
connected. Adapters must be securely plugged or screwed.