34
0x1609 (5641)*
Read/Write
0x160A (5642)*
Read/Write
0x160B (5643)
Read/Write
0x1610 (5648)
Read
0x1614 (5652)*
Read
0x1620 (5664)
Read/Write
*
RS-232C/485 Setting: This description for 0x1607 / 0x1609 register with bit.
MSB
15
14
13
12
Data Bit
**
Modbus Station: This description for 0x160A register with bit.
MSB
15
14
13
12
RS-232C Modbus station
1word
1word
1word
3words
1word
4words
11
10
9
8
Stop Bit
11
10
9
8
4 : 19200
5 : 38400
6 : 57600
7 : 115200
RS-485 Setting.
1 nibble : Data bit(0: 8bit(default), 1: 9bit)
2 nibble : Stop bit(0: 1bit(default), 1: 2bit)
3 nibble : Parity bit(0: none(default), 1: odd, 2: even)
4 nibble : Reserve
**Modbus Station.
High 1byte : Station No. of RS-232C (default: 1)
Low 1byte : Station No. of RS-485 (default: 1)
IP Setting Method.
BootP/DHCP disable
BootP:
DHCP:
Mac Address (1400 00F7 0101 = 00.14.F7.00.01.01)
Serial connection Method
0x0000 : Crevis Modbus/RTU (default)
0x8000 : RS232 Enable for CODESYS Function block
/ RTU Master. CODESYS Serial Port
Configuration Setting: COM Port 1
0x8001 : RS485 Enable for CODESYS Function block
/ RTU Master: CODESYS Serial Port
Configuration Setting: COM Port 2
RTC
1 word : 00ss (ss : sec)
2 word : hhmm (hh : hour, mm : min)
3 word : mmdd (mm : month, dd : day)
4 word : yyyy (yyyy : year)
(0010 0F28 0317 07E0 = 2016 - 03.23 - 15:40 - 16)
7
6
5
Parity Bit
7
6
5
RS-485 Modbus station
HX-RIO3 Series
0x0000
0x8000 (default)
0x8001
4
3
2
1
Reserved
4
3
2
1
LSB
0
LSB
0