Figure 20 Breaking Characteristics Of Distribution Board Circuit Protectors - Fujitsu ETERNUS AB Series Site Planning Manual

Hide thumbs Also See for ETERNUS AB Series:
Table of Contents

Advertisement

1.
ETERNUS AB/HB Installation
Outlet/Socket Specifications
Breaking Characteristics
The breaking characteristics (*1) of the distribution board circuit protectors must be the long-time
delay type and must be equivalent to or slower than the D (IEC/EN60898-1) shown in
If the distribution board's circuit protectors have a breaking characteristic that is faster than D, the
breaker may trip when a power supply unit in the storage system fails. When the breaker trips, a
shutoff occurs on multiple power supply units connected to the same connection line as the failed
power supply unit.
*1:
Relationship between the size of excess current and operation time

Figure 20 Breaking Characteristics of Distribution Board Circuit Protectors