Parameter
(cont.)
3 Scald protection
Setting
Out
In
4 Max. speed of speed-controlled primary/heating circuit pump in standard mode, heating circuit 1
Setting
5 Screed drying
Setting
Not active
Temperature profile A
Temperature profile B
Temperature profile C
Temperature profile D
Temperature profile E
Temperature profile F
6 Minimum heating output
Setting
Explanations
The adjustable DHW temperature is limited to a maxi-
mum value.
0
Scald protection OFF
Danger
Risk of injury due to increased DHW tempera-
ture.
Inform the system user of the risk from the
raised outlet temperature at the draw-off points.
1
Scald protection on (max. DHW temperature 60 °C)
Note
Even with the scald protection switched on, higher
outlet temperatures may occur at the draw-off points
in the following cases:
While the appliance is being calibrated
■
Explanations
Maximum speed of the internal circulation pump in
heating mode with standard room temperature
...
Delivered condition specified by settings specific to
the heat generator
0 to 100
Maximum speed adjustable from 0 to 100 %
Explanations
0
Screed drying can be set in accordance with selecta-
ble temperature/time profiles. For individual profile
curves, see chapter "Function description".
2
3
4
5
6
7
Explanations
A limit can be set on the minimum heating output for
heating mode.
...
Delivered condition specified by settings specific to
the appliance
0 to 100
Adjustable from 0 to 100 %
System configuration (parameters)