SAFETY General Safety This device should only be used in accordance with the instructions within this manual and in compli- ance with local, regional, and national laws and regulations. Only allow this device to be installed, oper- ated, maintained, and repaired by other people who have read and understood this manual. Ensure the manual is included with this device should it be passed to a third party.
Page 4
15.70 A V DC 48 V V DC 48 V AC OUTPUT BATTERY INPUT 230V V DC 48 V Output Voltage, Input Voltage Type, Ac 230V Battery Discharge Voltage, Battery 15.70 A Output Rated Current, Max AC Current, 15.70 A Discharge Current, Input Voltage Type, Output Frequency, Max AC ISC, Power Battery Discharge Power.
WARNING HIGH LIFE RISK DUE TO FIRE OR ELECTROCUTION. Sunsynk Single-Phase Hybrid Inverter can only be installed by a qualified licensed electrical contractor. This is not a DIY product. This chapter contains important safety and operating instructions. Read and keep this manual for future ...
PRODUCT INTRODUCTION This multifunctional inverter combines the functions of an inverter, solar charger and battery charger to offer uninterruptible power support with a portable size. Its comprehensive LCD display offers user-configurable and easily accessible button operations such as battery charging, AC/solar charging, and acceptable input voltage based on different applications.
Product Features INTERACTIVE Easy and simple to understand display Supporting Wi-Fi or GSM monitoring Visual power flow screen Smart settable 3-stage MPPT charging for optimized battery performance Auxiliary load function Parallel / multi invert function grid-tied and off-grid ...
Basic System Architecture The following illustration shows the basic application of this inverter. It also includes the following devices to have a Complete running system. Generator or Utility PV modules Consult with your system integrator for other possible system architectures depending on your requirements.
TECHNICAL SPECIFICATIONS Model SYNK-3.6K-SG03LP1 SYNK-5K-SG03LP1 Battery Input Date Battery Type Lead-acid or Li-Ion Battery Voltage Range 48Vd.c (40Vd.c ~ 60Vd.c) Max. Charging/Discharging Current 90Ad.c (max.) 120Ad.c (max.) Charging Curve 3 Stages / Equalization External Temperature Sensor Charging Strategy for Li-Ion Battery...
Page 11
Model SYNK-3.6K-SG03LP1 SYNK-5K-SG03LP1 Certifications and Standards VDE4105, IEC61727/62116, VDE0126, AS4777.2, CEI 0 21, EN50549- Grid Regulation 1, G98, G99, C10-11, UNE217002, NBR16149/NBR16150 IEC/EN 62109-1, IEC/EN 62109-2, IEC/EN 61000-6-1, IEC/EN 61000-6- EMC/Safety Regulation 2, IEC/EN 61000-6-3, IEC/EN 61000-6-4 General Data Operating Temperature Range -40~60 ºC, >45 ºC Derating...
INSTALLATION Parts List Check the equipment before installation. Please make sure nothing is damaged in the package. You should have received the items in the following package: Hybrid Inverter Wall Mounting Bracket Stainless Steel Anti-Collision Bolt M6*60x4 Stainless Steel Mounting Parallel Communication L-type Hexagon Wrench Screws M4*12 x2...
Selecting the Mounting Area This Hybrid Inverter is designed for outdoor use (IP65), DO NOT install the inverter in the following areas: Areas with high salt content, such as the marine environment. It will deteriorate the metal parts and possibly lead to water/dampness penetrating the unit.
Install the indoor unit on the wall where the floor height is higher than 1600mm. For proper heat dissipation, allow a clearance of approximately 500mm to the side, 500mm above and below the unit, and 1000mm to the front of the unit. WARNING For proper air circulation to dissipate heat, allow a clearance of approx.
Inverter Hanging Plate Installation Inverter hanging plate installation Battery Connection For safe operation and compliance, a separate DC over-current protector or disconnect device is required between the battery and the inverter. Switching devices may not be required in some applications, but over-current protectors are still required.
Page 16
WARNING All wiring/connecting must be performed by qualified personnel. Before making the final DC connection or closing the DC Breaker/disconnection device, ensure the inverter unit is wired correctly. A reverse-polarity connection on the battery will damage the inverter. Please follow the below steps to implement battery connection: Please choose a suitable battery cable with the correct connector which can well fit into the battery ...
Function Port Definition DIP Switch Inverter RS 485 / BMS 485 / DRMs METER HM G-V G-S parallel_1parallel_2 RS 485/METER: RS 485 port for battery communication. Batt Temp BMS 485/CAN: BMS port for battery Gen start-up Sensor N/O Relay communication. CT Coil DRMs: For Australia market only.
Recommended DC Battery Protection Inverter DC Isolator Fuses Two Pole Both cables must be the same length Max 100 AMP Max 200 AMP Connecting a Lithium Battery When connecting a Lithium Battery, follow the connection steps below and check ‘Setting up a Lithium Battery’...
Page 19
NOTE: When connecting more than one battery, ensure they are set in the configuration of ‘master and slave’. Depending on the battery type, the inverter should be capable of controlling the batteries BMS. Therefore, you need to set the protocol of the BMS on both the battery and the inverter. When using more than one battery, the first battery will be the master, and the other batteries will ...
Connecting the AC Before connecting to the grid, please install a separate AC breaker between the inverter and the grid. Also, it is recommended that installs an AC breaker between the backup load and inverter. This will ensure that the inverter can be securely disconnected during maintenance and fully protected from overcurrent. For the 3.6/5kW model, the recommended AC breaker for backup load is 40A.
PV Connection Before connecting to PV modules, please install a separate DC circuit breaker between the inverter and PV modules. It is very important for system safety and efficient operation to use appropriate cable for PV mod- ule connection. To reduce the risk of injury, please use the proper recommended cable size as below. Model Wire Size Cable (mm...
Installing the CT Coil The CT coil is one of the most important parts of the Sunsynk Parity inverter. This device reduces the power of the inverter to prevent feeding power to the grid. This feature is also known as “Zero Export”.
Page 25
L N PE L N PE L N PE Load Grid Inverter White wire Black wire Arrow pointing Grid to inverter The primary side of the CT needs to be clamped on the Grid live line. If the CT coil is fitted in the wrong way then this variable will have negative instead of positive values when the power is flowing into the...
Meter Connection System Connection for the CHNT Meter Load Grid PE L Inverter RS 485 / BMS 485 / DRMs METE R Breaker parallel_1 parallel_2 Grid Grid input Output RS 485 DDSU666 DIN-RAIL METER RS485A 230V 5(60) A 800imp/kWh RS485B CHNT DDSU666 Earth Connection (MANDATORY) An Earth Cable shall be connected to the earth plate on the grid size in order to prevent electric shock if the...
NOTE: Only for South Africa – Using a permanent PE/N bond on LOAD OUTPUT is recommended, and the supply power to the grid port needs to be taken from the mains before the main RCD to prevent RCD from tripping. The bond we recommend being done in the external box clearly marked “permanent PE/N bond“, and this has been advised by local authorities.
Inverter coil relay open contact DC Breaker for battery SYNK-3.6K-SG03LP1: 150A DC breaker SYNK-5K-SG03LP1: 150A DC breaker L N PE L N PE L N PE GV/GS AC Breaker for gen port SYNK-3.6K-SG03LP1: 40A AC breaker Load...
L N PE L N PE (slave) SYNK-3.6K-SG03LP1: 150A DC breaker Load Grid SYNK-5K-SG03LP1: 150A DC breaker AC Breaker for grid port SYNK-3.6K-SG03LP1: 40A AC breaker Breaker SYNK-5K-SG03LP1: 40A AC breaker AC Breaker for backup load port SYNK-3.6K-SG03LP1: 40A AC breaker...
OPERATION Switching ON/OFF Once the inverter has been correctly installed and the batteries have been connected, press the ON/OFF button (located on the left side of the case) to activate the system. When the system is connected without a battery but connected with either PV or grid and the ON/OFF button is switched off, the LCD will still illumi- nate (display will show off).
Home Page Press the Esc button any page to access the home page: 1. Customer name 2. Access the settings menu page 3. Access solar page 4. Access load page 5. Access battery page SOLAR/TURBINE AC load 6. Access grid page 7.
What this page displays: The system flow. Battery status. MPPTs power. Power distribution to load or grid. Setup Page To access Settings, click on the gear icon on the right top of the navigation menu. What this page displays: Serial number.
Basic Setup Set Time (Clock) To set time, click on the BASIC icon and then on ‘Time’ What this page displays: Time. Date. AM/PM. What you can do from this page: Adjust / set time. Adjust / set date. ...
Locked Inverter: This function is used to lock the inverter completely so no access can be gained. It will ask for a 5-digit code that only the Sunsynk Technical staff can assist with. Test mode (only for engineers): For engineers to conduct tests.
Inverter Remote Control To control the inverter remotely, tick the box that allows it. What this page displays: Remote control option. What you can do from this page: Allows remote control of the inverter. Battery Setup Page To configure battery settings, click on the BATTERY icon and then on ‘Batt type’. What this page displays: Lithium: This is BMS protocol.
NOTE: Recommended: AGM and Flooded: Ah battery size x 20% = Charge/Discharge amps. Lithium: Ah battery size x 50% = Charge/Discharge amps. Gel: follow manufacturer' s instructions. Generator & Battery Page To configure battery charging settings, click on the BATTERY icon and then on ‘Batt Charge’. What this page displays: Amps: Charge rate of 40A from the attached generator in Amps.
Page 40
1Amp 12V. Below is a simple reference circuit of an auto-start system that can auto-start generators on a boat. (Sunsynk will be releasing a new OS E406 ( Auto-Start ) for better generator control).
Battery Discharge Page To configure inverter’s shut-down settings, click on the BATTERY icon and then on ‘Shut Down’. SINGLE PHASE HI 3.6/5kW | Installer Manual...
Page 42
Activating Shutdown causes the inverter to enter standby-mode. It does not entirely shut down the inverter. Total shutdown occurs at voltages below 19V. The voltage displayed on the Sunsynk Parity Inverter will vary depending on whether the inverter is charging or discharging the batteries.
The batteries recommended for use with the Sunsynk systems are AGM Lead Acid or Lithium Battery Banks. At its core, an AGM is still a lead-acid battery. AGM stands for Absorbent Glass Mat, which refers to the tech- nology these devices use to create power. This fiberglass mat sits between the positive and negative lead plates of your battery.
Page 44
NOTE: With some types of lithium batteries, the BMS cannot be controlled by the Sunsynk inverter. In this case, treat the battery as a lead-acid type and set the charging and discharging protocol following the battery manufacturer's specifications.
Page 45
Inverter Brand Model Storage Notes or CAN Setup Inverter SS4074 To be used with V2 Logger http://solarmd.co.za/invert- SolarMD SS4037 er-compatibility-solarmd/ SS202 sunsynk-and-solar-md/ US2000B RS485 US3000 RS485 US2000C RS485 US3000C RS485 PYLON UP5000 RS485 US5000 RS485 Force L1 RS485...
Page 48
RS485 Inverter Brand Model Storage Notes or CAN Setup Inverter CLR5KWH CLW5KWH CLR10KWH COOLI CLW10KWH CLH10KWH ESS10240 VOLTA STAGE1 VOLTA STAGE2 VOLTA VOLTA STAGE3 VOLTA STAGE4 EVO 5.7KWH 48V-120Ah Yoshopo BB-LFP-100Ah-P 51.2V 100Ah Shanghai Green GTEM-48V2500 RS485 ...
RS485 Inverter Brand Model Storage Notes or CAN Setup Inverter Can be used with or with- BN52V-280-14.5K HC out BMAC https://www.bluenova. co.za/wp-content/up- BN52V-560-29K HC loads/2015/11/BN-User- Blue Nova HC Manual-HC_v102.pdf BN52V-840-43.6K HC BN52V-1120-58.2K HC CANH = Pin 7 BN52V-1400-72.8K HC CANL = Pin 8 BN52V-840-43.6K BR Blue Nova...
Page 50
If nothing ticked: This Mode allows the hybrid inverter to sell back any excess power produced by the solar panels to the grid. If the use time is active, the battery energy can also be sold into the grid. The PV energy will be used to power the load and charge the battery, and then excess energy will flow to the grid.
Page 51
Set the unit to charge the battery from the grid or generator ticking ‘Grid’ or ‘Gen’ and set what times this needs to occur. Set the time to discharge the unit to the load or export to the grid by unticking ‘Grid’ and ‘Gen’. ...
Page 52
Example: This example shows the battery being charged up to 100% by both the Grid and Solar PV from 8 a.m. to 11 a.m. and then being able to supply up to 4kW of battery-power to the ‘essential’ loads from the ‘Load’ Port until the battery SOC drops to 50%.
Example: During 01:00-05:00, when the battery SOC is lower than 80%, it will use the grid to charge the battery until the battery SOC reaches 80%. During 05:00-08:00 and 08:00-10:00, when battery SOC is higher than 40%, the hybrid inverter will discharge the battery until the SOC reaches 40%.
Page 54
What this page displays: Normal connect: The allowed grid voltage/frequency range when the inverter first time connects to the grid. Normal Ramp rate: It is the startup power ramp. Reconnect after trip: The allowed grid voltage/frequency range for the inverter connects the grid after ...
Page 55
What this page displays: FW: This series inverter is able to adjust inverter output power according to grid frequency. Droop f: The percentage of nominal power per Hz. For example: “Start freq f>50.2Hz, Stop freq f<50.2, Droop f=40%PE/Hz” when the grid frequency reaches 50.2Hz, the inverter will decrease its active power at Droop f of 40%.
Page 56
What this page displays: P(Q): It adjusts the inverter reactive power according to the set active power. P(PF): It adjusts the inverter PF according to the set active power. Lock-in/Pn 50%: When the inverter output active power is less than 50% rated power, it won't enter the ...
Select the corresponding meter type according to the meter installed in the system. The Sunsynk parity inverter can be wired standalone or where more power is required it can be connected in parallel either single or 3 phase configuration. The maximum number of inverters that can be paral- leled in a single phase utility grid is 16 and the maximum number that can be paralleled in a three phase utility grid is 15A.
Page 58
Each inverter will require a fuse isolator with surge protection and each group circuit will require an RCD. If the batteries as supplying power to the main load during the outage, then a change over switch will also be required or a split load can be used. The CT coils used to limit export power must only be connected to the master.
Page 59
If you need further help please refer to the Sunsynk website where you will find training videos and Fre- quently Asked Questions www.sunsynk.com. Firmware prior installation is important to be updated and all inverters in parallel or three phase system must be the same.
Connecting the DRM’s This can be selected under advance settings. This can be selected under advance settings. 1. DRM 1/5 5. Ref 0 2. DRM 2/6 6. D Ground 3. DRM 3/7 7. Net J 4-7 4. DRM 4/8 8. Net J 4-7 SINGLE PHASE HI 3.6/5kW | Installer Manual...
Advanced Function Setup Inverter Inverter load port shell Ground cable 230V external relay External relay coil open contact Grid peak shaving: When this is selected, the grid output power will be limited within the set value. If the load power exceeds the allowed value, it will take PV energy and stored battery energy to supple- ment.
Grid Power This page shows the Daily / Monthly / Yearly and total grid power export or consumed. Access this page by clicking on the ‘Solar/Turbine’ icon on the home page. SINGLE PHASE HI 3.6/5kW | Installer Manual...
Advanced Settings for Wind Turbines To configure wind turbine settings, click on the ADVANCE icon. This is for Wind Turbine 16.5 What this page displays: If one or both of the MPPTs are connected to a wind turbine. What you can do from this page: Select the MPPT to be used as a turbine input.
Most wind turbines are three-phase PM type. Therefore, either a wind turbine controller or a direct connec- tion to the MPPT via a simple protection circuit will be required. Dump Load or Diversion Load is an important part of an off-grid power system. When the battery ( Battery Bank ) is fully charged, and the water turbine / wind turbine / solar PV module is still generating, a dump load is a useful device to send spare electricity to.
Page 65
For Gen Input mode: Gen Input: Tick this box if using a Generator. Allowed Max. power from diesel generator. Peak shaving power: This is a technique used to reduce electrical power consumption during periods of maximum demand on the utility grid. This enables the user to save substantial amounts of money due to the expensive peak power charges.
Page 66
For Micro Inverter Input mode: Micro Inverter Input: To use the Generator input port as a micro-inverter on grid inverter input (AC coupled), this feature will also work with "Grid-Tied" inverters. Tick this box if intending to connect a sup- plementary inverter or micro inverter (Max.
OPERATION MODES Mode I: Basic AC cable DC cable COM cable Backup Load On-Grid Home Load Solar Battery Grid Mode II: Generator AC cable DC cable Solar Backup Load On-Grid Home Load Grid Battery Generator SINGLE PHASE HI 3.6/5kW | Installer Manual...
Mode III: With Aux-Load AC cable DC cable Solar Backup Load On-Grid Home Load Grid Battery Aux Load Mode IV: AC Couple On-Gen+AC couple AC cable DC cable On-Grid Home Load Grid Solar Backup Load Battery On-Grid Inverter SINGLE PHASE HI 3.6/5kW | Installer Manual...
Page 69
On-Load+AC couple AC cable DC cable On-Grid Inverter Backup Load Solar On-Grid Home Load Battery Grid Smart Load On-Grid+AC couple AC cable DC cable Backup Load Solar On-Grid Home Load On-Grid Inverter Battery Grid Smart Load WARNING The 1st priority power of the system is always the PV power, then 2nd and 3rd priority power will be the battery bank or grid according to the settings.
Mode V: Grid-Tied AC cable DC cable COM cable Backup Load On-Grid Home Load Solar Grid FAULT CODES To check the fault codes click on the FAULT CODES icon on the settings menu. If any of the fault messages listed in the following table appear on your inverter and the fault has not been removed after re-starting, please contact your local vendor or service centre.
Page 71
2. If the fault still exists, please get in touch with us for help. Inverter work mode changed Working Mode Change 1.Reset the inverter. 2.Seek help from Sunsynk. AC Slide over current fault. AC over current fault or 1.Check if the backup load power is within the range of the hardware inverter.
Page 72
Error Code Description Solutions No utility 1.Please confirm grid is lost or not; No AC grid 2. Check the grid connection; 3. Check the switch between inverter and grid in on or not; 4. If the fault still exists, please contact up for help. 1.
Page 73
Chapter 3, ‘Technical Specifications’. If you need further help please refer to the Sunsynk website where you will find training videos and frequent- ly asked questions www.sunsynk.com.
COMMISSIONING Start-Up / Shutdown Procedure The inverter must be installed by a qualified / licensed electrical engineer in accordance with the country's wiring regulations. Before switching on, the installation engineer must have completed the Earth Bond, RCD and earth leakage tests, checked that the solar panel Voc voltage does not exceed 480V and checked the battery voltage.
Ensure you are familiar This is the heart of the with this, if you fully under- See section ‘Program system this controller stand the controller you Charge / Discharge Times’ everything will fully appreciate the ca- pabilities of there inverter If paralleling inverters in 3 Phase check you phase If using a wind turbine...
Page 76
APPENDIX A The following table is the connection on battery side of SSLB1: Protocol Description Pin 1: CAN-H Pin 5: CAN-L Pin 2, 3, 4, 6, 7, 8: NC Pin 1: RS485B Pin 2: RS485A Pin 3, 6: GND RS485 Pin 7: RS485A Pin 8: RS485B Pin 4, 5: NC...
Page 77
Instantaneous APPENDIX E The Sunsynk inverter can be connected to the internet, but you need to add a data logger to do this. The inverter is compatible with Sunsynk Connect data-logger, which you can obtain from us with your distrib- utor.