Advertisement
WIRE-FREE INTERCONNECT: You do NOT need a home wi-fi system to use these units. Multiple wireless units create their own independent wireless alarm network.
The smoke alarm pattern is three long beeps with voice "Fire!," a 1.5 second pause, and three long beeps repeating.
The red LED blinks in time with the alarm pattern.
The smoke alarm takes precedence when both smoke and carbon monoxide are present.
For instance:
NOTE: See Section RECOGNIZING NUISANCE ALARMS, for nuisance alarm situations.
The carbon monoxide (CO) alarm pattern is four quick beeps with voice "Warning! Carbon Monoxide" repeating every 5 seconds. The red LED blinks in time with the alarm pattern.
CARBON MONOXIDE ALARM ACTIVATION INDICATES THE PRESENCE OF CARBON MONOXIDE (CO) AT HIGH CONCENTRATIONS WHICH CAN KILL YOU.
If problems are identified during this inspection, have the equipment serviced immediately. Note any combustion equipment not inspected by the technician and consult the manufacturer's instructions, or contact the manufacturer directly for more information about CO safety and the equipment. Make sure that motor vehicles are not, or have not been, operating in a garage attached or adjacent to the residence. never restart the source of a CO problem until it has been corrected. never ignore the sound of the alarm!
NOTE: See Section RECOGNIZING NUISANCE ALARMS, for nuisance alarm situations.
Operational Mode | Visual Indications | Audible Indications | Action/Nite: |
Normal (standby) | Green LED blink approx every 60 sec. | ||
Test (button press when no alarm condition is present) |
|
| Perform Test/Hush button press once a week to verify proper alarm operation * Push/release button before the countdown ends to cancel test. |
Smoke or Co Alarm Memory (unit has experienced a smoke or Co alarm event within the last hour) | Red and Amber LED alternate on 1 sec, every 10 sec. | After button push: Voice "Smoke previously detected" or "Carbon Monoxide previously detected" only on the initiating alarm unit. | Push test button to clear Alarm Memory. |
Smoke Alarm hush Mode, (SMArt hUSh® Control) | Red LED blinks every 2 sec. | After button push: Voice "Hush Mode Activated." Smoke alarm pattern stops. (If there is too much smoke to allow Hush: Voice "Too Much Smoke, Alarm cannot be Hushed" Smoke alarm pattern continues.) | This feature is to be used only when a known alarm condition, such as smoke from cooking, activates the alarm. |
Co alarm reset | None | After button push: CO alarm pattern stops. | Unit is confirming if CO is present or if it experienced a nuisance situation. Re-alarm means danger. Move to fresh air and call 911. |
Locate | None | After button push on non-initiating unit, only initiating unit continues alarm pattern. | Use this to quickly locate the alarm source and determine if alarm is nuisance or real. |
Smoke Alarm Hush Mode Canceled | None | Voice "Hush Mode Canceled." | When smoke levels drop below the alarm threshold, the voice message "Hush Mode Canceled" will occur. |
Initiating Alarm, (Multiple alarms in an interconnected system) | Green LED blinks once per sec indicating that this is the unit initiating the alarm in an interconnected, multiple alarm, system. | Unit in either Smoke or CO alarm mode. | During alarm, the initiating alarm red blink will be interrupted by a green blink. |
Trouble Condition | Visual Indications | Audible Indications | Action: |
Low battery | Amber LED blinks every 5 seconds | Chirp every 60 sec, voice every 30 sec: "Replace alarm." Voice stops after 5 mins. | *Remove, discharge, dispose unit, and replace as soon as possible. |
Fault Mode | Chirp every 30 sec. Voice every 30 sec: "Error, see trouble shooting guide" After 5 mins: no voice message | *See Cleaning Your Alarm section. * Push Test/Hush button once to attempt to reset the unit. *Red LED will blink out an error code (number of blinks) when Test/Hush button is push/released once. Report the number of blinks to customer service if needed. | |
End of Unit life | Double chirp every 30 sec. First 5 mins: Voice every 30 sec: "Replace alarm, press button to temporarily silence." Voice stops after 5 mins. After 7 days: Chirps continue. Voice every 30 sec for 5 mins: "Replace alarm." | * Push/release Test/Hush button to temporarily silence (see End of Unit Life Hush Mode section below) * Remove, discharge, dispose unit, and replace as soon as possible. | |
End of Unit life hush Mode (after push/ release test/hush button during end of life) | Voice "Temporarily Silenced." End of Unit Life chirps silenced for 24 hrs. (7 days after End of Unit Life chirps begin, the chirps cannot be silenced.) | * Remove, discharge, dispose unit, and replace as soon as possible. | |
Network error | Chime every 30 secs. Voice every 30 sec: "Connection lost, press button to temporarily silence." After 5 min: no voice messages ( | See next page for Network Error troubleshooting tips. | |
Network error hush (after button push during network error) | Voice "Temporarily Silenced." |
If you require further information please contact Product Support at 1-800-880-6788 or write us at: Kidde, 1016 Corporate Park Drive, Mebane, NC 27302. Our internet address is www.kidde.com.
If you have a unit (or units) in network error and you would like to silence them, you can push and release the Test/Hush button once on each unit in network error to silence them for 24 hours at a time.
NOTE: when you do this, the red LED will blink out an error code (number of blinks) when the Test/Hush button is push/released once. If the following steps are unsuccessful, it might be helpful to report the number of blinks to customer service.
Fix 1:
NOTE: If there is only one unit that is giving you trouble, rotating the alarm on the mounting plate may re-orient the wireless antenna and fix the problem.
NOTE: If the unit does not re-join the wireless network, press and hold the button on a known working unit (not the unit in network error) for 4-5 seconds. Then proceed to "Fix 2."
Fix 2:
NOTE: In a wireless alarm network, there is a Coordinator unit, which controls communication to the other units, which are called "RFDs". For best wireless range, the Coordinator should be located in a central location of the household. If "Fix 1" does not work or if there are multiple units in network error, the following steps will place the Coordinator of the wireless network at the center of the household.
Fix 3:
If "Fix 2" did not work, use this fix. The following steps will reset the entire wireless alarm network and place the Coordinator at the center of the household.
This alarm detects products of combustion using photoelectric technology and carbon monoxide using an electrochemical cell. Many times throughout this User Guide, we will refer to Carbon Monoxide as "CO."
Ten (10) years after the unit was installed, this unit will automatically alert you that it is time to replace the unit. This is called "End of Unit Life" mode. See Troubleshooting Guide. To help identify the date to replace the unit, a label has been affixed to the side of the alarm. Write the "Install date" in the space provided, and then write in the "Replace by" date (10 years from initial power up) in permanent marker on the label prior to installing the unit.
Two labels have been provided that have important information on what to do in case of a CO alarm. Place one label next to the alarm after it is mounted, and one near a fresh air source such as a door or window.
PLEASE READ CAREFULLY AND THOROUGHLY
This alarm is not intended to alert hearing impaired individuals.
PLEASE READ CAREFULLY AND THOROUGHLY
This alarm is designed to detect carbon monoxide gas from ANY source of combustion. It is NOT designed to detect any other gas.
This alarm will only indicate the presence of carbon monoxide gas at the sensor. Carbon monoxide gas may be present in other areas. Never restart the source of a CO problem until it has been fixed. NEVER IGNORE THE ALARM!
THIS PRODUCT IS INTENDED FOR USE IN ORDINARY INDOOR LOCATIONS OF FAMILY LIVING UNITS. IT IS NOT DESIGNED TO MEASURE COMPLIANCE WITH OCCUPATIONAL SAFETY AND HEALTH ADMINISTRATION (OSHA) COMMERCIAL OR INDUSTRIAL STANDARDS. IT IS NOT SUITABLE FOR INSTALLATION IN HAZARDOUS LOCATIONS AS DEFINED IN THE NATIONAL ELECTRIC CODE. IT IS NOT DESIGNED FOR USE IN A RECREATIONAL VEHICLE (RV) OR BOAT.
THIS DEVICE IS DESIGNED TO PROTECT INDIVIDUALS FROM ACUTE EFFECTS OF CARBON MONOXIDE EXPOSURE. IT MAY NOT FULLY SAFEGUARD INDIVIDUALS WITH SPECIFIC MEDICAL CONDITIONS. IF IN DOUBT, CONSULT A MEDICAL PRACTITIONER. INDIVIDUALS WITH MEDICAL PROBLEMS MAY CONSIDER USING WARNING DEVICES WHICH PROVIDE AUDIBLE AND VISUAL SIGNALS FOR CARBON MONOXIDE CONCENTRATIONS UNDER 30 PPM.
NFPA 72 states: "Smoke alarms in rooms with ceiling slopes greater than 1 ft in 8 ft (.3m in 2.4 m) horizontally shall be located on the high side of the room." NFPA 72 states: "A row of detectors shall be spaced and located within 3 ft (0.9m) of the peak of the ceiling measured horizontally."
Figure A
SINGLE FLOOR PLAN
Smoke Alarms for Required Protection
Smoke Alarms for Additional Protection
lonization Type Smoke Alarms with "Hush" Control or Photoelectric Type
MULTIPLE FLOOR PLAN
Figure B
Figure C
This equipment should be installed in accordance with the National Fire Protection Association's 72 (National Fire Protection Association, Batterymarch Park, Quincy, MA 02269).
Modern mobile homes have been designed and built to be energy efficient. Install smoke alarms as recommended above. In older mobile homes that are not well insulated compared to present standards, extreme heat or cold can be transferred from the outside to the inside through poorly insulated walls and roof. This may create a thermal barrier which can prevent the smoke from reaching an alarm mounted on the ceiling. In such units, install the smoke alarm on an inside wall with the top edge of the alarm a minimum of 4" (10 cm) and a maximum of 12" (30.5 cm) below the ceiling.
If you are not sure about the insulation in your mobile home, or if you notice that the outer walls and ceiling are either hot or cold compared to the room air temperature, install the alarm on an inside wall. NFPA 72 (National Fire Protection Association) requires smoke alarms be installed in each sleeping area.
TEST YOUR ALARM OPERATION AFTER MOBILE HOME HAS BEEN IN STORAGE OR UNOCCUPIED, AND AT LEAST ONCE A WEEK DURING USE.
NOTE: Smoke alarms are not to be used with detector guards unless the combination (alarm and detector guard) has been evaluated and found suitable for that purpose.
Upon initial power being applied (from rotating onto mounting plate or moving the red activation wheel to the "ON" position - see Figure D) these units are ready to connect to a network.
Figure D
NOTE: At any time during wireless alarm setup, if you have a problem, you can push and hold the Test/Hush button on any problem unit until you hear three (3) beeps (approx 8 sec), and then release the button. The unit will reset the unit's wireless settings (described in "Resetting a Device's Wireless Settings" Section). Once wireless settings are reset, the unit will prompt the user to follow Quickstart instructions.
NOTE: Wireless units will emit a series of LED blinks, tones, and voices as the unit(s) search for a wireless alarm setup. If you are intending to use wireless units without the wireless function, ignore tese notifications, and the wireless function will eventually turn off. You can turn the wireless function on again at a later date if desired. See "Adding Another Wireless Device to an Existing Wireless Alarm Network" Section.
NOTE: The battery activation is a one-time feature. After activation, the battery cannot be turned off, and can only be discharged at the end of product life. If the alarm is removed from the mounting plate, the battery will remain active. See Permanently Disable Alarm / Discharge Battery section.
These models have wireless alarm interconnect capability. When one interconnected unit sounds an alarm, all other compatible wireless units in the wireless alarm network will alarm.
COMPATIBLE WIRELESS INTERCONNECT UNITS
AC Models: P4010ACSCO-W, P4010LACS-W, P4010ACS-W
DC Models: P4010LDCS-W, P4010DCS-W, P4010DCSCO-W
Creating an interconnected wireless alarm network is a simple process, with intelligent "self-enrollment" features and user-friendly voice prompts.
NOTE: If no further steps are taken within 15 minutes of initial power up, a voice prompt, "No devices found, not connected" will be heard once, and the wireless function will turn off. The unit will then perform as a stand alone alarm. See "Resetting a Device's Wireless Settings" Section for re-activating wireless.
The alarm is now activated! After installation / activation, test your alarm as described in Operation and Testing section.
FAILURE TO PROPERLY INSTALL AND ACTIVATE THIS ALARM WILL PREVENT PROPER OPERATION OF THIS ALARM AND WILL PREVENT ITS RESPONSE TO FIRE HAZARDS.
For various reasons, you might want to add additional units to your existing wireless alarm network. Modifying your existing wireless alarm network is easy and user-friendly.
Figure H
The alarm is now activated! After installation / activation, test your alarm as described in Operation and Testing section.
FAILURE TO PROPERLY INSTALL AND ACTIVATE THIS ALARM WILL PREVENT PROPER OPERATION OF THIS ALARM AND PREVENT ITS RESPONSE TO FIRE HAZARDS.
If you encounter an issue at any point during the wireless network setup process, you may reset the device by following the directions below.
NOTE: If no further steps are taken within 15 minutes of resetting the unit's wireless settings, a voice prompt "No devices found, not connected" will be heard once, and the wireless function will turn off. The unit will then perform as a stand alone alarm. See "Adding Another Wireless Device to an Existing Wireless Alarm Network" Section for adding this device to an existing alarm network.
CO ALARM SENSOR RESPONSE TIMES
At 70 PPM, the unit must alarm within 60-240 minutes.
At 150 PPM, the unit must alarm within 10-50 minutes.
At 400 PPM, the unit must alarm within 4-15 minutes.
The alarm is operating once it is activated and testing is complete. When products of combustion (smoke or CO) are sensed, the unit sounds a loud alarm with voice messages. See "Smoke Alarm: What To Do When the Alarm Sounds" and "Carbon Monoxide Alarm: What To Do When the Alarm Sounds" Sections for alarm signal descriptions. In high levels of CO, the unit will go into alarm in a shorter period of time than at low levels of CO.
Test your alarm weekly by pressing and releasing the test button quickly. A quick beep will confirm the button has been pushed followed by voice prompts that will inform you of the upcoming test sequence. See Other Alarm Visual and Audible Indicators table. The alarm and voice (and any interconnected units) will sound if the electronic circuitry, horn, speaker, and battery are working. If the alarm or voice does not sound, or gives erratic or low volume sound, the unit must be replaced. See Permanently Disable Alarm / Discharge Battery section to determine how to prepare the unit for shipment or disposal.
DUE TO THE LOUDNESS OF THE ALARM, ALWAYS STAND ABOUT 2.5 FEET AWAY FROM THE UNIT OR USE EAR PROTECTION WHEN TESTING.
DO NOT USE AN OPEN FLAME TO TEST YOUR ALARM, YOU COULD DAMAGE THE ALARM OR IGNITE COMBUSTIBLE MATERIALS AND START A STRUCTURE FIRE.
This unit samples the ambient light conditions of the alarm's location and, if possible, determines a Night / Day cycle. A valid Night / Day cycle will delay unit chirps during the night until the next Day cycle begins.
POSSIBLE CHIRPING REASONS
End of Unit Life: will be delayed at night
Network Error: will be delayed at night
Low battery: will be delayed at night
When chirping begins during the next Day cycle, you can temporarily silence End of Unit Life or Network Error chirps by pressing the Test/ Hush button. Low Battery chirps cannot be silenced.
If a valid Night / Day cycle has not been established because the unit is located in either a constantly dark or lighted location, the chirps mentioned above will not be delayed at night. Moving the unit to a different location might allow the unit to determine a valid Night / Day cycle.
REPLACE UNIT AS SOON AS POSSIBLE WHEN IN END OF UNIT LIFE OR LOW BATTERY MODE.
HUSH®: If you know why the alarm is sounding, and you can verify that it is not a life threatening situation, you can push the button on the initiating unit (green LED flashing every second) to silence the alarm for 8-10 minutes. If the smoke is not too dense, that unit, and all interconnected units will silence. After the Hush® period, the smoke alarm will automatically reset and sound the alarm if particles of combustion are still present. You can use Hush® repeatedly until the air has been cleared of the condition causing the alarm.
NOTE: Dense smoke will override Hush® and sound a continuous alarm. If no fire is present, check to see if one of the reasons listed in "Locations to avoid" may have caused the alarm. If a fire is discovered, get out and call the fire department.
This alarm is designed to minimize nuisance alarms. Cigarette smoke will not normally cause the unit to alarm, unless the smoke is blown directly into the alarm. Combustion particles from cooking may set off the alarm if it is located too close to a cooking appliance. Large quantities of combustible particles are generated from spills or when broiling. Using the fan on a range hood which vents to the outside (non-recirculating type) will also help prevent nuisance alarms from occurring by removing these combustible products from the kitchen.
RESET: Pushing the button during CO alarm allows the unit to reset calculations and double check for the presence of CO. If the unit re-alarms within 6 minutes, it is sensing high levels of CO which can quickly become a dangerous situation.
Move to fresh air and call 911.
In an interconnected system (all units will be alarming together), a unit that detects smoke or CO and initiates an alarm is called the "initiating alarm unit." Initiating alarm units will be flashing the Green LED every second during alarm. Depending on unit locations, and the location of the source of smoke or CO, it is possible to have more than one initiating unit. If you suspect a nuisance alarm situation, you can use this feature to help you locate the initiating alarm unit(s) in a wireless alarm interconnect system. Push the button on any non-initiating wireless unit, and ALL wireless units EXCEPT the initiating alarm unit(s) will silence for two minutes. You can use the LOCATE feature repeatedly until you find the initiating alarm unit(s), or the air has been cleared of the condition causing the alarm.
NOTE: Hush® and Locate features are dependent on the type of models in your interconnect system. Non-wireless models cannot receive the wireless Locate feature and will continue to alarm until the initiating unit is Hushed or the Smoke/ CO condition clears.
ALTHOUGH RESET AND LOCATE FEATURE CAN BE USED FOR CO ALARM EVENTS, IT IS IMPOSSIBLE TO DETERMINE THE SOURCE OF A CO ALARM USING SIGHT OR SMELL. ALWAYS CONSIDER A CO ALARM EVENT AS DANGEROUS.
NOTE: This alarm is powered by a non-replaceable, sealed lithium battery system. No battery installation or replacement is necessary for the life of the alarm.
Constant exposure to high or low humidity or temperatures may reduce battery life.
NO SERVICEABLE PARTS INCLUDED. DO NOT ATTEMPT TO OPEN THE ALARM FOR ANY REASON! DO NOT TRY TO REPAIR THE ALARM YOURSELF.
This alarm is equipped with a low battery monitor circuit. If the battery capacity can no longer provide adequate power for all alarm functions, the low battery condition will occur. See Troubleshooting Guide. The unit must be replaced within 7 days of the first occurrence of the "Low Battery Warning" to provide continuous alarm protection.
FAILURE TO DISCHARGE ALARM BATTERY AS INSTRUCTED PRIOR TO DISPOSAL MAY CREATE POTENTIAL FOR LITHIUM BATTERY RELATED FIRE OR HAZARD.
DISCHARGING THE ALARM BATTERY IS PERMANENT
To Permanently Disable Alarm / Discharge Battery:
Carbon monoxide (CO) is a colorless, odorless, and tasteless poison gas that can be fatal when inhaled. CO inhibits the blood's capacity to carry oxygen.
Possible Sources of Co
Inside your home, appliances used for heating and cooking are the most likely sources of CO. Vehicles running in attached garages can also produce dangerous levels of CO. CO can be produced when burning any fossil fuel: gasoline, diesel, propane, natural gas, oil and wood. It can be produced by any fuel-burning appliance that is malfunctioning, improperly installed, or not ventilated correctly, such as: Furnaces/boilers, gas ranges/stoves, gas clothes dryers, water heaters, portable fuel burning space heaters, fireplaces, wood-burning stoves and certain swimming pool heaters. Blocked chimneys or flues, back drafting and changes in air pressure, corroded or disconnected vent pipes, or a loose or cracked furnace heat exchanger can also release CO into your building. Vehicles and other combustion engines running in an attached garage and using a charcoal/gas grill or hibachi in an enclosed area are all possible sources of CO.
The following conditions can result in transient Co situations:
Excessive spillage or reverse venting of fuel-burning appliances caused by outdoor ambient conditions such as: Wind direction and/or velocity, including high gusts of wind, heavy air in the vent pipes (cold/humid air with extended periods between cycles), negative pressure differential resulting from the use of exhaust fans, simultaneous operation of several fuel-burning appliances competing for limited internal air, vent pipe connections vibrating loose from clothes dryers, furnaces/boilers, or water heaters, obstructions in, or unconventional, vent pipe designs which can amplify the above situations, extended operation of unvented fuel-burning devices (range, oven, fireplace, etc.), temperature inversions which can trap exhaust gases near the ground, car idling in an open or closed attached garage, or near a home.
Co Safety Tips
Every year, have the heating system, vents, chimney and flue inspected and cleaned by a qualified technician. Always install appliances according to manufacturer's instructions and adhere to local building codes. Most appliances should be installed by professionals and inspected after installation. Regularly examine vents and chimneys for improper connections, visible rust, or stains, and check for cracks in furnace heat exchangers. Verify that the color of flame is blue on pilot lights and burners. An amber or orange flame is a sign that the fuel is not burning completely and may be releasing CO. Teach all household members what the alarm sounds like and how to respond. Fire Departments, most utility companies and HVAC contractors will perform CO inspections. Some contractors may charge for this service. It's advisable to inquire about any applicable fees prior to having the service performed. Kidde will not pay for, or reimburse the owner or user of this product, for any repair or dispatch calls related to the alarm sounding.
Symptoms of Co Poisoning
Initial carbon monoxide poisoning symptoms are similar to the flu with no fever and can include dizziness, severe headaches, nausea, vomiting and disorientation. Everyone is susceptible but experts agree that unborn babies, pregnant women, senior citizens and people with heart or respiratory problems are especially vulnerable. If symptoms of carbon monoxide poisoning are experienced seek medical attention immediately. CO poisoning can be determined by a carboxyhemoglobin test.
The following symptoms are related to CARBON MONOXIDE POISONING and should be discussed with ALL members of the household:
The above levels of exposure relate to healthy adults. Levels differ for those at high risk. Exposure to high levels of carbon monoxide can be fatal or cause permanent damage and disabilities. Many cases of reported carbon monoxide poisoning indicate that while victims are aware they are not feeling well, they become so disoriented they are unable to save themselves by either exiting the building, or calling for assistance. Also, young children and household pets may be the first affected. Familiarization with the effects of each level is important.
You can clean the interior of your alarm (sensing chamber) by using compressed air or a vacuum cleaner hose and blowing or vacuuming through the openings around the perimeter of the alarm. The outside of the alarm can be wiped with a damp cloth. Use only water to dampen the cloth, use of detergents or cleaners could damage the alarm.
If the alarm is in Fault mode and the Red LED is blinking a fault code of 10 or 14 flashes (after a Test/Hush button push), the alarm may be in need of cleaning. After cleaning, press the Test/Hush button. If the fault does not clear, the alarm needs to be replaced.
Storing the unit in a plastic bag during any of the above projects will protect the sensors from damage. When household cleaning supplies or similar contaminates are used, the area must be well ventilated.
REINSTALL THE ALARM AS SOON AS POSSIBLE TO ENSURE CONTINUOUS PROTECTION.
Here you can download full pdf version of manual, it may contain additional safety instructions, warranty information, FCC rules, etc.
Download Kidde P4010DCSCO-W - Smoke and Carbon Monoxide Alarm Manual
Advertisement
Need help?
Do you have a question about the P4010DCSCO-W and is the answer not in the manual?
Questions and answers