Micropelt MVA008 User Manual And Device Specification

Micropelt MVA008 User Manual And Device Specification

Radiator thermostat

Advertisement

Quick Links

Copyright Micropelt
Radiator Thermostat
MVA008 (EN)
EnOcean EEP A5-20.01
EU868MHz
User Manual and Device Specification
 
 
The Micropelt MVA008 product series is designed for use with radiators and M30x1.5 valve threads.
For inquiries please visit us at:
Customer Service Portal
Email: info@micropelt.com  Telephone +49 7665 932183 0

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the MVA008 and is the answer not in the manual?

Questions and answers

Summary of Contents for Micropelt MVA008

  • Page 1 EnOcean EEP A5-20.01 EU868MHz User Manual and Device Specification     The Micropelt MVA008 product series is designed for use with radiators and M30x1.5 valve threads. For inquiries please visit us at: Customer Service Portal Email: info@micropelt.com  Telephone +49 7665 932183 0...
  • Page 2: Table Of Contents

    10 MVA008 Battery recharging ................................22 10.1 Flow chart instructions MVA008 and MVA009:..........................23 10.2 Video instruction charge startup (MVA008 without cover prints, is identical to MVA009): ............24 10.3 Charging curve LiFePO4 cell in the MVA EnOcean series: ......................24 11 MVA008 Product-ID and Label .................................25 12 MVA008 Technical Data..................................26...
  • Page 3: Mva008 Revision History

                                                            Datei Geändert 2023-03-28 by Fritz Volkert Micropelt_MVA004_1DSMVA004_0720v13e.docx MVA008 Revision History – 3...
  • Page 4: Mva008 Intended Use

    2 MVA008 Intended use The Micropelt MVA product series has been designed for use with controlling water-filled heating radiators. Any other use – including control of floor heating systems – is not permitted and can result in malfunctions or damage. It is important to comply with the safety notice included in these operating instructions.
  • Page 5: Mva008 Safety

    When operating the device in a workplace environment, be sure to observe the workplace regulations that may apply.   In case of questions, please contact: Micropelt - a brand of EH4 GmbH. Email: info@micropelt.com. Telephone +49 7665 932183 0 MVA008 Safety – 5...
  • Page 6: Mva008 General Description

    At its user interface, MVA008 has a red and a green LED. Two internal temperature sensors are used with its internal temperature controller and freeze protection (ambient sensor) and the automatic radio duty cycle control of 2, 5 or 10 minutes (flow temperature sensor).
  • Page 7: Mva008 Operating Instructions

    LED. green flash followed The device will turn the by triple red flash Left OR Right and motor back to mounting hold 5 seconds   position and switch off. until single green flash MVA008 Operating Instructions – 7...
  • Page 8 (normal 10-second radio never been operation with communication interval. paired. successful It contacts the Mounting or communication) or controller / gateway motor problems immediately after RESET. 3x red (communication error, mounting error) MVA008 Operating Instructions – 8...
  • Page 9: Mva008 Notes On Radio Operation

    In addition, the actuator enters the safe position. Once the radio contact to the room controller recovers, the actuator reverts to requesting instructions from the controller every 10 minutes. MVA008 Notes on radio operation – 9...
  • Page 10: Mva008 Communication Profile Eep A5-20-01

    Temperature sensor failure   DB0.7…DB0.4 Not used (set to “zero”) DB2.1 (DWO) Window open detection   DB0.3 (LRNB) LRN Bit, defined for data telegram DB2.0 (ACO) Motor failure   DB0.2…DB0.0 Not used (set to “zero”) MVA008 Communication profile EEP A5-20-01 – 10...
  • Page 11: Setpoint Selection (Db1.2, Rcu To Mva004)

    7.6 Example of a radio protocol Radio protocol of valve actuator MVA to server /controller /gateway Example in HEX "0x32 0x70 0x89 0x08" • DB3.7…DB3.0 = 0x32 = 50: valve position is 50% MVA008 Communication profile EEP A5-20-01 – 11...
  • Page 12 0 = Normal operation 1 = Service on ENIE DB2.6   0 = no energy input 1 = Energy input enabled (Harvesting active) DB2.5   0 = Energy storage low 1 = Energy storage sufficiently charged MVA008 Communication profile EEP A5-20-01 – 12...
  • Page 13 0 = not used 1 = not used                   DIRECTION-2 Control unit / Gateway to MVA004  Controller / Gateway  →  Actuator   4 Byte: 80810408       MVA008 Communication profile EEP A5-20-01 – 13...
  • Page 14 0 = not used [Teach-In 1 = not used [Teach-In query] response] LRNB DB0.3   0 = Teach-in telegram 1 = Data telegram   DB0.2   0 = not used 1 = not used MVA008 Communication profile EEP A5-20-01 – 14...
  • Page 15 Copyright Micropelt   DB0.1   0 = not used 1 = not used   DB0.0   0 = not used 1 = not used                     MVA008 Communication profile EEP A5-20-01 – 15...
  • Page 16: Mva008 Remote Commissioning (En)

    Outbound EnOcean Link Table:               3 Tech-in relationships Comments: MVA008 uses an outbound link table only, inbound relationships are not supported. Manually erasing the outbound link table is not possible. Manual pairing (teach-in) however overwrites the first entry of the outbound link table, clearing the other two entries.
  • Page 17: Recom Supported Standard Functions

    Set Common Configuration Query • RESET DEVICE DEFAULTS RESET DEVICE DEFAULTS: MVA will execute reference run and reset all internal parameter to DEFAULT values (Table 4.5). Link connections and Security Code will not be changed. MVA008 Remote Commissioning (EN) – 17...
  • Page 18: Recom Supported Mva Internal Parameter

    T Approximated = T Ambient - ((T Flow - T Ambient) * A-Parameter) Description INDEX 12 = temperature controller gain P parameter (only with PLC = 1) MVA008 Remote Commissioning (EN) – 18...
  • Page 19 (0x00 … 0xFF) 0 … 255 = 10x GAIN DEFAULT 30 = 0x1E Battery open circuit voltage (V) (0x00 … 0xFF) 0 … 255 = 10x Voltage READ ONLY Example 0x21 = DEZ 33 : 10 = 3,3Volt     MVA008 Remote Commissioning (EN) – 19...
  • Page 20 Copyright Micropelt     MVA008 Remote Commissioning (EN) – 20...
  • Page 21: Mva008 Energy Harvesting

    General reloading of the storage by means of forced heating requires full heating operation over several days, which is why this state must be avoided in advance by taking suitable measures. Operation in unheated or insufficiently heated rooms is to be avoided. MVA008 Energy Harvesting – 21...
  • Page 22: Mva008 Battery Recharging

    For the EnOcean products MVA008 and MVA009 • 10.1 Flow chart instructions MVA008 and MVA009: • 10.2 Video instruction charge startup (MVA008 without cover prints, is identical to MVA009): • 10.3 Charging curve LiFePO4 cell in the MVA EnOcean series: MVA008 Battery recharging – 22...
  • Page 23: Flow Chart Instructions Mva008 And Mva009

    Copyright Micropelt 10.1 Flow chart instructions MVA008 and MVA009: MVA008 Battery recharging – 23...
  • Page 24: Video Instruction Charge Startup (Mva008 Without Cover Prints, Is Identical To Mva009)

    Copyright Micropelt 10.2 Video instruction charge startup (MVA008 without cover prints, is identical to MVA009): Sorry, the video is not supported in this export. But you can reach it using the following URL: https://micropelt.atlassian.net/wiki/download/attachments/153157633/DSCN0230.mp4?api=v2   10.3 Charging curve LiFePO4 cell in the MVA EnOcean series:...
  • Page 25: Mva008 Product-Id And Label

    Copyright Micropelt 11 MVA008 Product-ID and Label The MVA Product ID consists of the Micropelt manufacturer ID as well as the product reference number. All functions and properties are available electronically in the shape of the Device Description File (DDF). ...
  • Page 26: Mva008 Technical Data

    (following 6 consecutive communication failures) communication is online again EnOcean EEP and operating mode A5-20-01 (Valve Position and SetTemp) EnOcean Remote management & Remote commissioning capability Accuracy of internal ambient temperature sensor +/- 0.5 ºC  MVA008 Technical Data – 26...
  • Page 27 Set battery-low flag and reset RF communication interval to default 10 min Radio carrier frequency 868.3 MHz Maximum radiated power +1.4 dBm (EN 300220-2: V3.1.1) Receiver Category 2 (EN 300 220-1 V3.1.1) Conformity MVA008 Technical Data – 27...
  • Page 28: Mva008 Valve Connection

    Copyright Micropelt 13 MVA008 Valve connection The Micropelt series of products is designed to mount onto an M30 x 1.5mm valve thread. Adapters are available for a majority of non-M30 x 1.5mm valve bodies. MVA008 Valve connection – 28...

Table of Contents