DataHub 1000 User Manual 1 Safety The DataHub produced by SolaX Power Network Technology (Zhejiang) Co., Ltd. has been designed and tested strictly in accordance with relevant safety regulations. The safety instructions must be followed when installing and maintaining the electrical and electronic equipment. Improper operation will cause personal injury and property damage to the operator and the third party.
DataHub 1000 User Manual 2 Overview of DataHub 2.1 Introduction DataHub, a special equipment of the monitoring platform of photovoltaic power generation system, has realized many functions, with details as follows: interface aggregation, data acquisition, data storage, output control, and centralized monitoring and centralized maintenance of inverters, electricity meters, environmental monitors and other equipment in photovoltaic power generation systems.
DataHub 1000 User Manual 2.3 LED Indicator Sign Status Explanation Flash The program runs normally. (GREEN) Always on or always off The program runs abnormally. The network connection is SERVE normal. (GREEN) The network connection isn’t normal. ALARM Device alarms...
DataHub 1000 User Manual 3 Installation 3.1 Packing List After receiving the package of DataHub, please check whether the accessories are complete and there is no obvious damage to the appearance. If there is any damage or items missing, please contact the dealer.
DataHub 1000 User Manual *Note: When the Wi-Fi signal is weak, please install a Wi-Fi signal booster at the appropriate location. 3.2.2 Indoor Wall Mounting Choose a flat and solid indoor wall to drill for installation; Hang the DataHub on the wall with the cable connection area facing down.
DataHub 1000 User Manual 4 Electrical Connection 4.1 Inverter Connection The inverter is connected to the DataHub through the RS485. For the connection method of the inverter, please refer to the inverter installation manual; It is recommended that the number of devices connected to each channel of RS485 is less than 20;...
DataHub 1000 User Manual 4.3 Installation of DI Signal Cable DataHub can access DI signals such as remote control and alarms through the DI port. socket mark 8-10mm D 1 I D 2 I Support pa ssi ve dry co n tact...
DataHub 1000 User Manual Illustrate socket mark 8-10mm 8-10mm Max. load 30V/2A 4.6 Installation of Network Cable Use Cat 5e or higher specifications and Shielded crystal head connectors to prepare the network cable. The communication distance does not exceed 100 m.
DataHub 1000 User Manual 5 Configuration Function 5.1 Login Local login: connect the computer to the DataHub hotspot (WiFi _xxxxxxx; xxxxxxx refers to the Registration No. of datahub), and use the computer to access 192.168.10.10 to enter the login interface.
DataHub 1000 User Manual 5.2 Site Management 5.2.1 Add Device The devices supported by DataHub are as follows: Inverters, Electricity Meters, and Environmental Monitors. Select the device type under the serial port, set the starting address and the number of devices under the serial port, and save these settings.
DataHub 1000 User Manual 5.2.2 Device Detail Click the corresponding device to query the device data, or select the device to export the device data. 5.3 Sits Setting “Site Setting” is equipped with three modules, which are “Export Limit Control”, “Power Control” and “Other...
DataHub 1000 User Manual 5.3.1 Export Limit Control The purpose of the “Export Limit Control” is to limit the power supplied to the grid. The inverter generates electricity to the grid when the power source is positive, and takes electricity away from the grid when the power source is negative.
Page 17
DataHub 1000 User Manual Please refer to 5.4.3 “Parameter Setting” to enable Datahub communication loss shutdown and Datahub communication connection startup. The corresponding Modbus addresses are respectively: 6152 and 6153; Set value: “0”: Disable, “1”: Enable. Datahub communication refers to: i) The communication between Datahub and inverters; ii) The communication between Datahub and meters.
DataHub 1000 User Manual 5.3.2 Power Control Power control includes “Ripple Control Receiver” and “DRED Control” disable. The “Ripple Control Receiver” is to control the input active power and reactive power, output active power and reactive power of the inverter and inverter off according to the high or low input of the DI port.
DataHub 1000 User Manual Mode Operate Explanation Note Close S9,S1, When two or more DRM DRM1 Close S1,charging power is 0% disconnect S0 modes work at the same time, take the optimal result DRM5 Close S9,S5 Inverter does not output active power that can satisfy both of them.
DataHub 1000 User Manual 5.4 Inverter Setting There are three functions under "Inverter Setting”: “Inverter Active/Reactive Power Setting”, “Remote System Switch” and “Parameter Setting”. 5.4.1 Inverter Active/Reactive Power Setting Remotely set the active or reactive power of the inverter. The reactive power mode is divided into “OverExcited”,...
DataHub 1000 User Manual 5.4.2 Remote System Switch Remote control of inverter switching. (Can be operated in batches) 5.4.3 Parameter Setting Professionals can read and write the inverter through the inverter's “Modbus Opcode”, under which there are “READ_HOLDING_REGISTERS”, “READ_INPUT_REGISTERS”, “WRITE_SINGLE_REGISTER”and“WRITE_MULTIPLE_REGISTERS”. (Can be operated in batches) 5.4.4 IV Curve Scanning...
DataHub 1000 User Manual 5.5 Smart Scene The user can customize “IF-Then” function on Datahub. By creating the “IF” conditions (e.g. time, weather, inverter status and electric price), the user-defined “Then” instruction will be executed automatically such as inverter charge or discharge, inverter startup or shutdown, e-mail sending, etc.
DataHub 1000 User Manual 5.6 Inverter Upgrade Using DataHub to upgrade the inverter. Click “Upgrade” to select the upgrade file types which include “ARM”, “MDSP”, “SDSP”, “ARC”, “ARM+DSP”, “BMS_M” and “BMS_S”. Select the corresponding file to upgrade the inverter. *Note: It takes nearly 15-30 minutes to upgrade the inverter. During upgrading, no data will be uploaded.
DataHub 1000 User Manual 5.7 DataHub Setting 5.7.1 Internet Setting Wired connection: connect the Datahub and router via network cable. Wireless connection: After local login, please enter “System Setting”-“Internet Setting”-“WiFi Setting” to select the WiFi and enter the password. Connect the computer and DataHub to the same WiFi, and then visit http://datahub.local/ to log in. If the user cannot access, please install the Bonjour SDK, or log in through the DataHub LAN IP address.
DataHub 1000 User Manual “Other Server Synchronization”: The IEC104 server sends a synchronization command to change the time of system. *Note: When using SolaXClound to set the time, please switch to “SolaXCloud Synchronization” mode. 5.7.3 Serial Port Settings Serial port settings is to set the baud rate of the four serial ports of DataHub, the default value of the baud rate is 19200.
DataHub 1000 User Manual 5.7.5 Datahub Information “Datahub Information” displays the basic information of datahub, including “Registration Number”, “Firmware Version”, “Internal Codes”, “System Time”, “Memory Usage”, “Free Disk Space”, “Free TF Space”, “Wi-Fi Connection”, “LAN IP Address”, “LAN MAC Address”, “WiFi IP Address” and “WiFi MAC Address”.
DataHub 1000 User Manual 5.7.6 DataHub Upgrade Click the “Click to Upload and Upgrade” button to upload and upgrade the DataHub, then select the upgrade file and wait for the upgrading. (Only one file can be uploaded at a time, and the interface needs to be refreshed for continuous operation.)
DataHub 1000 User Manual 6 Technical Specifications Product DataHub1000 Hardware Power adapter 100-240V 50/60HZ AC Input 12V 2A DC Input Rated power Data transfer interval 5min Storage capacity 8G/16G TFcard The number of managed devices Communication Inverter communication 3xRS485 wireless module WiFi 2.4GHz...
DataHub 1000 User Manual 7 Certified Quality Assurance 7.1 Certification mark 7.2 Warranty SolaX grants a standard 24-month warranty, if it is otherwise stipulated in the contract, the contract shall prevail. 7.3 Warranty Conditions In case the product is operated according to the above instruction, SolaX will provide after-sales service during the product warranty period if any failure (error) is caused by product quality.
If you have any question or any technical question about DataHub, please contact us through the following methods, we will serve you wholeheartedly. SolaX Power Network Technology (Zhejiang) Co., Ltd. ADD: No.288 shizhu Road, Tonglu Economic Zone, Tonglu City, Zhejiang Province, China.