Wattstopper LVSW-101 /103 / 102 / 104 / 108 Installation Manual

Wattstopper LVSW-101 /103 / 102 / 104 / 108 Installation Manual

Advertisement

Wattstopper LVSW-101 /103 / 102 / 104 / 108 Installation Manual

Introduction

The LVSW series low voltage switch is intended for use with lighting control devices that expect a momentary contact closure to toggle the state of the lighting load. Each button on the LVSW switch has an LED indicator intended to display the current state of the lighting load when connected appropriately to the lighting control device. Five color kits and custom engraving options are available.

MOUNTING THE SWITCH

MOUNTING THE SWITCH

Do Not install To Cover Junction Box Having Class 1, 3 or Power and Lighting Circuits.

For install in UL Listed Junction Box or Enclosure Containing Only Class 2 Wiring - Do not Reclassify and Install as Class 1, 3 or Power and Lighting Wiring.

BUTTONS AND INDICATORS

BUTTONS AND INDICATORS

WIRING

  1. Connect the "Com" terminal (common) of the LVSW switch to the lighting control device per the instructions provided with the device. Note that both "Com" terminals on the LVSW switch are internally connected together.
  2. Connect the terminal corresponding to the button on the LVSW switch (SW1 –SW8) to the input of the lighting control device per the instructions provided with the lighting control device.
  3. Connect the terminal corresponding to the LED pilot light on the LVSW button (LED1 – LED8) to the pilot light output of the control device per the instructions provided with the lighting control device.
  4. Repeat for all buttons on the switch. Refer to diagram for button-terminal cross reference.
  5. Install the LVSW switch into a single gang wall box or one position in a multi-gang switch box using the mounting screws provided with the LVSW switch. Be careful to press the low voltage wires into the box so they are not pinched by the mounting plate.
  6. Install an appropriate switch cover plate (not supplied) over the LVSW switch to complete the installation.

Button-Terminal Cross Reference
Button-Terminal Cross Reference

SPECIFICATIONS

Voltage, from panel: 24VDC, Class 2
Maximum Contact Current Per Button: 50mA
Maximum Operating Current: 2mA
Wire Connections; Removable Terminal Blocks
Use 18 -22 AWG Copper Conductors Only
One terminal per button
One terminal per LED
Two common terminals; shared with all buttons and LEDs
Environment: For Indoor Use Only
Operating Temperature: 32° to 130°F (0° to 55°C)
Relative Humidity: 5 to 95% (non condensing)
UL and cUL listed

2800 De La Cruz Blvd. Santa Clara, CA 95050
Phone: 800.879.8585
www.wattstopper.com

Documents / Resources

References

Download manual

Here you can download full pdf version of manual, it may contain additional safety instructions, warranty information, FCC rules, etc.

Download Wattstopper LVSW-101 /103 / 102 / 104 / 108 Installation Manual

Advertisement

Need help?

Need help?

Do you have a question about the LVSW Series and is the answer not in the manual?

Questions and answers

Table of Contents