Wiring for an LMRC-100
Wiring for two LMRC-100s
Step 5
Attach the ground wire.
Step 6
Connect the Power Supply to the LMPI board.
Connect one or more LMRJ cables to the RJ45 jacks. There are two DLM IRB networks (labeled A & B) used to connect DLM devices such as the LMFC-011 Fixture Controllers, switches, sensors, and room controllers. The networks are labeled A and B. Each network has two RJ-45 jacks, for connecting CAT5 cable. It is not important which of the two jacks are used.
Note: RJ45 jacks/Cat5 cables are only used to connect to DLM switches, sensors, room controllers, etc. to the panel. To connect one panel to another panel, use the MS/TP connectors
Once installation is complete, re-attach the cover to the LMCZ-301.
In situations where a larger number of devices are connected to a DLM network, you can increase the amount of power output from the LMZC-301 by installing a powered room controller on either Cat 5e network (which adds power to just that network), or by installing one or two LMRC-100s within the unit (one per network). Secure the LMRC-100 to the power supply board on the LMZC-301, as shown to the right. Then, connect an LMRJ cable from the LMRC-100 to the LMZC-301.
Note: If using an LMRC-100, maximum operating condition is 104 F (40 C)
Note: An LMRC-100 should be only connected to Network A or B only. To use both Networks, you will need to install two LMRC-100s.
WattStopper warranties its products to be free of defects in materials and workmanship for a period of five (5) years. There are no obligations or liabilities on the part of WattStopper for consequential damages arising out of, or in connection with, the use or performance of this product or other indirect damages with respect to loss of property, revenue or profit, or cost of removal, installation or reinstallation.
2800 De La Cruz Boulevard
Santa Clara, CA 95050
Phone: 800-879-8585