Air conditioning control system
Hide thumbs Also See for TRANE TE-50A:

Advertisement

Quick Links

Air Conditioning Control System
Centralized Controller
TE-200A/TE-50A
Before using the controller, please read this Instruction Book carefully to ensure proper operation.
Retain this manual for future reference.
Contents
1. Safety precautions ..............................................................4
1-1. General precautions ...................................................................4
1-3. Additional precautions .................................................................5
2. Introduction .........................................................................6
2-1. Terms used in this manual ..........................................................6
2-2. Required licenses .......................................................................6
2-4. About this manual .......................................................................6
3. Basic operations .................................................................7
3-1. Monitor/Operation .......................................................................7
3-2. Energy Management ................................................................22
3-3. Schedule ...................................................................................25
3-4. Status List .................................................................................45
3-5. Malfunction Log ........................................................................49
4. Practical operations ..........................................................51
4-1. Cleaning the touch panel ..........................................................51
5. Initial startup settings ........................................................52
5-1. Initial startup setting procedures ...............................................52
5-2. Initial Settings ...........................................................................57
Control Web ..............................................................................80
6. Maintenance .....................................................................84
6-1. Backing up settings data ...........................................................84
6-2. Importing settings data .............................................................85
6-3. Software Update .......................................................................86
6-4. Software information .................................................................86
7. Specifications ....................................................................87
<ORIGINAL>
Instruction Book

Advertisement

Table of Contents
loading

Summary of Contents for Mitsubishi Electric TRANE TE-50A

  • Page 1: Table Of Contents

    <ORIGINAL> Air Conditioning Control System Centralized Controller TE-200A/TE-50A Instruction Book Contents 1. Safety precautions ..............4 1-1. General precautions ..............4 1-2. Precautions for relocating or repairing the unit ......5 1-3. Additional precautions ..............5 2. Introduction .................6 2-1. Terms used in this manual ............6 2-2.
  • Page 2 Contents 1. Safety precautions ....................4 1-1. General precautions ....................4 1-2. Precautions for relocating or repairing the unit ............5 1-3. Additional precautions ..................... 5 2. Introduction ......................6 2-1. Terms used in this manual ..................6 2-2. Required licenses ....................6 2-3.
  • Page 3 5-2-4. License registration for optional functions ..........62 5-2-5. Unit Information ..................63 5-2-6. Network ...................... 67 5-2-7. Groups ......................70 5-2-8. Blocks ......................72 5-2-9. Floor Layout....................73 5-2-10. System View ..................... 78 5-2-11. Floor Layout settings on the Integrated Centralized Control Web .... 79 5-3.
  • Page 4: Safety Precautions

    1. Safety precautions ►Observe these precautions carefully to ensure safety. ►After reading this manual, pass the manual on to the end user to retain for future reference. ►The user should keep this manual for future reference and refer to it as necessary. This manual should be made available to those who repair or relocate the units.
  • Page 5: Precautions For Relocating Or Repairing The Unit

    Consult your dealer for the proper disposal of the controller. Improper disposal will pose a risk of environmental pollution. 1-2. Precautions for relocating or repairing the unit The controller must be repaired or moved only by qualified personnel. Do not disassemble or modify the controller.
  • Page 6: Introduction

    Instruction Books. Ask your dealer for how to obtain these Instruction Books. AE-200A/AE-50A/EW-50A Instruction Book (Initial Settings) AE-200A/AE-50A Instruction Book (Detailed operations) AE-200A/AE-50A/EW-50A Instruction Book (Integrated Centralized Control Web) * TE-200A/TE-50A/TW-50A and Mitsubishi Electric’s AE-200A/AE-50A/EW-50A have the same functions. Use these instruction books, replacing the model names AE-200A/AE-50A/EW-50A to TE-200A/TE-50A/TW-50A. WT09304X01...
  • Page 7: Basic Operations

    3. Basic operations 3-1. Monitor/Operation Unit groups can be monitored and operated on the TE-200/TE-50’s LCD or the Integrated Centralized Control Web. This section explains how to monitor and operate the unit groups. 3-1-1. Screen sequence 3-1-1-1. LCD [Floor] display (zoomed-in) [Floor] display (zoomed-out) Touch [ Touch [...
  • Page 8 3-1-1-2. Integrated Centralized Control Web Home Home (preview) Floor Layout (simple operation) Floor Layout Advanced settings Group list Group list (simple operation) Measurement status WT09304X01...
  • Page 9: Group Icons

    3-1-2. Group icons Each group icon indicates the operation condition of the group. Touch the icon, and then touch [Operate] to bring up the operation settings screen. Air conditioning unit group Error Schedule set Note: Refer to the Instruction Book (Detailed operations) or Instruction Book (Integrated Centralized Control Web) for details and other icons.
  • Page 10 Item Description Floor selection Select a floor you want to monitor. Area selection Select an area of the selected floor you want to monitor. Group name The name of the group will appear. Indoor unit return air temperature, set temperature, or room humidity will appear. Room temperature, set Note: The outlet air temperature is displayed for the room temperature of outlet air temperature temperature, or room humidity...
  • Page 11 [3] [EM Block] display Touch [Monitor/Operation] in the menu bar, and then touch [Block]. Weekly schedule number Block name Block selection Number of units currently in error Group icons The icon indicates the Number of units whose operation condition of the filter sign is turned on group.
  • Page 12 3-1-3-2. Integrated Centralized Control Web [1] Group display Click [Monitor/Operation] in the menu, and then click [Show groups] to display the operation status of unit groups. Show groups Controller Select all Deselect all Number of units Group icon currently in error Item Description Click to narrow down the unit groups to display into “Centralized controller units,”...
  • Page 13 [2] Floor Layout display Click [Monitor/Operation] in the menu, and then click [Floor Layout] or “Floor display area” to display the operation status of unit groups on the floor layout. The floor layout to be displayed can be changed by clicking “Floor display area”...
  • Page 14: Selecting The Icons Of The Groups To Be Operated

    3-1-4. Selecting the icons of the groups to be operated On the [Floor] or [Block] display under the [Monitor/Operation] menu, select the icon(s) of the group(s) to be operated as explained below, and then touch [Operate] (click [Advanced] on the Integrated Centralized Control Web) to bring up the operation settings screen.
  • Page 15 (3) Selecting all groups on all floors On the [Floor] or [Block] display, touch the “Select-all- groups” button. All floor and group icons will appear with an orange frame. To cancel all group selections, touch the “Deselect-all” button. Select-all-groups Deselect-all (4) Selecting all groups in the selected block On the [Block] or [EM Block] display, touch the block(s) Block icon...
  • Page 16 3-1-4-2. Integrated Centralized Control Web [1] Selecting group icons (1) Selecting unit group(s) (1) In the Floor Layout screen or group list, click the icon(s) of the group(s) you want to operate. The selected group icon(s) will appear with a checkmark and a dark blue frame. Click again to deselect.
  • Page 17 (3) Selecting all groups (1) In the group list, click [Select all]. The all icon(s) will appear with a checkmark and a dark blue frame. To cancel all group selections, click [Deselect all] or [Close] in the taskbar. Group list Select all Deselect all Close...
  • Page 18 (6) Selecting all groups in the entire building (1) In the Home screen, click [Entire building]. To cancel all group selections, click [Close] in the taskbar. Close Entire building WT09304X01...
  • Page 19 [2] Selecting equipment type (1) When the equipment types of all selected groups are the same Selecting the group icons to operate and clicking [Advanced] in the taskbar will bring up the operation settings screen for the selected groups. Refer to section 3-1-5 “Operation settings screen” for details about the advanced settings. Selecting groups of the same equipment type...
  • Page 20: Operation Settings Screen

    3-1-5. Operation settings screen On the screen under the [Monitor/Operation] menu, selecting the group icon and touching [Operate] (click [Advanced] on the Integrated Centralized Control Web) will bring up the operation settings screen for the selected group. The current operation conditions will appear. Change necessary operation settings, and then touch [OK] (click [Send] on the Integrated Centralized Control Web) to save the settings.
  • Page 21 3-1-5-2. Integrated Centralized Control Web Set temperature Group name Air Direction ON/OFF Operation mode Fan Speed Send Click to reflect the changes Close made. Click to close the settings screen without making any changes. Schedule Prohibit Remote Controller Operation Hold Send Click to reflect the changes made.
  • Page 22: Energy Management

    3-2. Energy Management Only the outline of energy management function is given in this manual. For details on how to use the function, refer to the AE-200/AE-50 Instruction Book (Detailed operations) or the AE-200/AE-50/EW-50 Instruction Book (Integrated Centralized Control Web). 3-2-1.
  • Page 23: Ranking

    3-2-2. Ranking On the Ranking screen, the rankings in electric energy consumption, fan operation time, and Thermo-ON time (Total/ Cool/Heat) of given indoor units can be displayed per block, group, and unit address in descending order in the bar graph. 3-2-2-1.
  • Page 24: Target Value

    3-2-3. Target value This section explains how to set the target electric energy consumption values for the entire system for the current year, each month, each day of the week, and each block. 3-2-3-1. LCD 3-2-3-2. Integrated Centralized Control Web Note: Target values can only be displayed on the Integrated Centralized Control Web.
  • Page 25: Schedule

    3-3. Schedule Weekly (5 types), annual (5 types), and current day scheduling are available. Schedules can be set for each group, each floor, each block, or all groups. Important ● When one or more TE-50/TW-50 controllers are connected, the schedule settings must be made with the TE-50/TW-50 properly connected to ensure proper settings.
  • Page 26 Note: When the schedules overlap, schedule with the highest priority will run as shown below. Priority High Today’s schedule Schedules can be set for the current day without modifying the weekly or annual schedules. Annual schedule Different schedules can be set for public holidays or summer vacation.
  • Page 27: Weekly Schedule

    3-3-1. Weekly Schedule Schedules can be set for each day of the week. Note: When today’s schedule and weekly schedule are set for the same day, today’s schedule settings take precedence over weekly schedule settings. Note: When the “Schedule: Season setting” setting is set to [Available] (default setting), weekly schedule date range settings can be configured.
  • Page 28 (2) If different equipment types exist together, a screen to select an equipment type will appear. Touch one of the equipment types to set the schedule. (3) A [Schedule Settings] screen will appear. To create a schedule for the given block from scratch, touch [New settings] and touch [OK].
  • Page 29 [4] Setting the contents of the schedule (1) Touch the row of the schedule to be set in the “Contents of Schedule” section to display the schedule settings screen. Set the start time to apply to the schedule, set the operations to be scheduled, and then touch [OK]. Note: If [Optimized Start] is selected, the operation mode and the set temperature need to be set as well.
  • Page 30 [5] Copying a schedule to another day of the week (1) To copy the schedule settings of a day to the schedule Day of the week selection settings for another day of the week, select the day Paste whose schedule settings are to be copied, touch [Copy], Copy select the day to which the copied schedule settings are to be pasted, and touch [Paste].
  • Page 31 3-3-1-2. Integrated Centralized Control Web [1] Selecting a target to which the schedule will be applied In the Floor Layout screen or group list, select a group icon(s) to which the schedule will be applied, and click [Schedule settings]. A screen to set a schedule for the selected group(s) will appear. Refer to section 3-1-4 “Selecting the icons of the groups to be operated”...
  • Page 32 [2] Setting the date range for each schedule Five types of weekly schedules can be set. (One year is divided into the maximum of five periods.) Note: This setting is “Season Settings” on the LCD. Note: The weekly schedule date ranges are set for each centralized controller (TE-200/TE-50/TW-50). When the weekly schedule date ranges are set with Integrated Centralized Control Web, the same settings will be sent to all the centralized controllers that are control targets of Integrated Centralized Control Web.
  • Page 33 [3] Selecting a day of the week Schedules can be set for each day of the week for each weekly schedule (Weekly 1 to 5). (1) In the Schedule settings screen, select one of the weekly schedule (Weekly 1 to 5). (2) Click the day to set the schedule.
  • Page 34 (2) In the schedule contents settings screen, set the start time to apply to the schedule, set the operations to be scheduled, and then click [OK]. If [Optimized Start] is selected, the operation mode and the set temperature need to be set as well. Schedule contents settings (1/2) Schedule contents settings (2/2) Scheduled...
  • Page 35 [5] Saving the schedules (1) After the schedule settings are completed, click [Send] on the Schedule settings screen to send and save the settings to the centralized controllers. To undo the changes made, click [Cancel]. Schedule settings Send Cancel Click to undo the changes Click to save the settings.
  • Page 36 • Group list Procedure (1) Procedure (3) Procedure (2) Group icon Copy Name of the group Copied Group icon Select the group Click to copy the whose schedule The group icon Select the group whose schedule schedule contents of settings are copied will appear to which the settings are to be...
  • Page 37: Annual Schedule

    3-3-2. Annual Schedule On the Annual Schedule settings screen, schedules can be set for public holidays or summer vacation. Up to five operation patterns (Pattern A through E) can be set for the 24 months including the current month, and total of 50 days can be allocated to the patterns.
  • Page 38 [3] Setting the contents of the schedule (1) Touch the row of the schedule to be set in the “Contents of Schedule” section to display the schedule settings screen. Set the start time to apply to the schedule, set the operations to be scheduled, and then touch [OK]. (Refer to section 3-3-1-1 [4] “Setting the contents of the schedule”...
  • Page 39 [6] Saving the schedules (1) To undo the changes made, touch [Cancel] before saving the schedules. After completing the settings, touch [OK] to save the schedules. Cancel [7] Copying a schedule to another group (1) Refer to 3-3-1-1 [7] “Copying a schedule to another group” for details. WT09304X01...
  • Page 40 3-3-2-2. Integrated Centralized Control Web [1] Selecting a target to which the schedule will be applied (1) In the Floor Layout screen or group list, select a group icon(s) to which the schedule will be applied. Refer to 3-3-1-2 [1] “Selecting a target to which the schedule will be applied” for details. [2] Selecting a schedule pattern Up to five operation patterns can be set.
  • Page 41 [4] Allocating schedule patterns to special dates Each schedule pattern can be allocated to the specified dates such as public holidays and summer vacation. (1) In the Schedule settings screen (Month or Week display), click the date to set a pattern. (2) Select the pattern to be allocated to the selected date.
  • Page 42 [7] Creating a schedule based on existing settings of other pattern When setting annual schedule patterns, the schedule settings can be created based on existing settings of other pattern. (1) In the Edit schedule settings screen, click [Based on...]. (2) In the [Based on...] screen, select the pattern or the day of the week whose schedule is to be based on. (3) The contents of the schedule that have been set for the selected pattern or the day of the week will appear in the Edit schedule settings screen.
  • Page 43: Today's Schedule

    3-3-3. Today’s Schedule On the Today’s Schedule settings screen, schedules can be set for the current day without modifying the weekly or annual schedules. Note: Be sure to set the contents of schedule in a way that will not impact on the next day’s operation. For example, if Prohibit setting of remote controller operation is made for any time such as 17: 00, Permit setting needs to be made for any time before the date changes such as 23: 59.
  • Page 44 3-3-3-2. Integrated Centralized Control Web [1] Selecting a target to which the schedule will be applied (1) In the Floor Layout screen or group list, select a group icon(s) to which the schedule will be applied. Refer to 3-3-1-2 [1] “Selecting a target to which the schedule will be applied” for details. [2] Setting or changing the contents of the schedule (1) In the Schedule settings screen (Month or Week display), click the date of the current day.
  • Page 45: Status List

    3-4. Status List 3-4-1. Malfunction List 3-4-1-1. LCD Touch [Status List] in the menu bar, and then touch [Malfunction]. A list of units that are currently malfunctioning will appear. Note: The [Controller] setting will appear (only on the TE-200’s LCD) when the [System Exp] setting on the [Unit Info.] screen is set to [Expand].
  • Page 46 3-4-1-2. Integrated Centralized Control Web Click [Notice] in the menu, and then click [Error List] to access the Error List screen. A list of units that are currently malfunctioning will appear. Note: When an error occurs, check the address of the unit in error, error code and its definition, and then contact your dealer. Reset All Controller Group name...
  • Page 47: Filter Sign List

    3-4-2. Filter Sign List 3-4-2-1. LCD A list of units whose filter sign is turned on can be displayed. Touch [Status List] in the menu bar, and then touch [Filter Sign]. Note: The [Controller] setting will appear (only on the TE-200’s LCD) when the [System Exp] setting on the [Unit Info.] screen is set to [Expand].
  • Page 48 3-4-2-2. Integrated Centralized Control Web A list of units whose filter sign is turned on can be displayed. Click [Notice] in the menu, and then click [Filter sign] to access the Filter sign screen. Reset All Group name Controller Reset Unit address Item Description...
  • Page 49: Malfunction Log

    3-5. Malfunction Log 3-5-1. Unit Error/Communication Error 3-5-1-1. LCD Touch [Log] in the menu bar, and then touch [Unit Error] to display unit errors, or touch [Communication Error] to display M-NET communication errors. Note: The [Controller] setting will appear (only on the TE-200’s LCD) when the [System Exp] setting on the [Unit Info.] screen is set to [Expand].
  • Page 50 3-5-1-2. Integrated Centralized Control Web Click [Notice] in the menu, and then click [Unit error log] to access the Unit error log screen. Note: The latest 64 unit errors will appear for each TE-200/TE-50/TW-50. Note: Unit errors of all TE-200/TE-50/TW-50 controllers will appear in a list. Clear log Controller Group name...
  • Page 51: Practical Operations

    4. Practical operations 4-1. Cleaning the touch panel (1) Touch [ ] to display the login window. (2) On the Login window, touch the “Touch-panel-cleaning” button. Touch-panel-cleaning (3) Clean the touch panel with a soft dry cloth, a well-wrung cloth that has been soaked in water with mild detergent, or a cloth dampened with ethanol.
  • Page 52: Initial Startup Settings

    5. Initial startup settings 5-1. Initial startup setting procedures 5-1-1. TE-200 initial startup for a system without connection to a TE-50/TW-50 controller (1) After the power is turned on, a language selection screen will appear. Select the language to be used for display, and then touch [OK]. Note: It will take approximately one minute for the display to appear after the power is turned on.
  • Page 53 (4) Touch the right triangle button to display the [Groups] tab, and touch it. Referring to section 5-2-7, make group settings, and then touch [Save Settings]. (5) Make the following settings, as required. ● Block settings (See section 5-2-8 “Blocks”.) ●...
  • Page 54: Te-200 Initial Startup For A System With Connection To One Or More

    5-1-2. TE-200 initial startup for a system with connection to one or more TE-50/TW-50 controllers Note: When connecting one or more TE-50/TW-50 controllers, make sure to make network settings for the TE-50/TW-50 first, and then make network settings for the TE-200. [1] Settings on the TE-50 (1) After the power is turned on to the TE-50, a language selection screen will appear.
  • Page 55 (2) Touch the [Unit Info.] and [Unit Info. 2] tabs. Unit Info. Referring to section 5-2-5, make necessary basic settings, and then touch [Save Settings]. Note: Make sure to set the [System Exp] setting for the TE-200 to [Expand]. Note: The [AE-200 Apportion] setting will appear only when the “Charge”...
  • Page 56 (5) Touch the [Groups] tab. Referring to section 5-2-7, select [AE], [1], [2], [3], or [4] in the [Controller] section, make group settings for each TE-200/TE-50/TW-50, and then touch [Save Settings] on each settings screen. A message “Collecting connected equipment status data. Please wait...”...
  • Page 57: Initial Settings

    5-2. Initial Settings 5-2-1. Logging in to the Initial Settings menu (1) Touch [ ] to display the login window. (2) Enter the user name and the password on the keyboard screen (See [1] “Keyboard screen”), and touch [Login]. [Initial Settings] menu screen will appear. The table below shows the default user names, passwords, and functions that are available for maintenance users and building managers.
  • Page 58 [1] Keyboard screen Arrow The entered characters will appear here. Touch to move the cursor. Delete Touch to delete one character to the left of the cursor. Touch to display the keyboard for entering capital Cancel alphabetic characters. Touch to undo the changes made and return to the previous screen.
  • Page 59: Locking The Screen

    5-2-2. Locking the screen Locking the screen prevents unauthorized users from accessing. (1) To activate the screen lock function, set the [Screen lock] setting to [Use] on the [Unit Info.] screen under the [Initial Settings] menu. If the screen lock function is activated, the screen locks when the backlight turns off (after three minutes of not touching the screen).
  • Page 60: Date And Time

    5-2-3. Date and time Touch [Initial Settings] in the menu bar, and then touch [Date and time]. Set the current date and time, and then touch [Save Settings]. Note: The date and time settings may not be accessible if logged in as a building manager. Note: The date and time settings made on this screen will be reflected on all the units in the M-NET system, all connected TE-50/TW-50 units, and the TE-200 units whose [Time Master/Sub] setting is set to [Sub].
  • Page 61 Note ● Message that will appear when the date and time have been reset If the power supply is cut off for a long time due to power failure or other reasons, the date and time will be reset, and the following popup message will appear when the power is turned on next.
  • Page 62: License Registration For Optional Functions

    5-2-4. License registration for optional functions Touch [Initial Settings] in the menu bar, and then touch [License]. Please ask your dealer for more details on the optional functions and how to purchase a license number. Note: The current date and time settings are required for license registration. Refer to section 5-2-3 “Date and time” for date and time settings.
  • Page 63: Unit Information

    5-2-5. Unit Information Touch [Initial Settings] in the menu bar, and then touch [Unit Info.] or [Unit Info. 2]. Make necessary basic system settings such as unit settings, display format, sound/brightness settings, use or non- use of test run, and display or non-display of room temperature/humidity, and then touch [Save Settings]. Note: The Unit Information settings may not be accessible if logged in as a building manager.
  • Page 64 (2) Touch the [Unit ID] button to display the keyboard. Enter the unit ID in 6 figures. Use this setting to manage the multiple unit IDs. The unit ID entered here will be used on the screen of the software that controls multiple TE-200 units and will also be used as a sender ID in the error notification e-mail and e-mail alarm.
  • Page 65 (8) In the [Brightness] section, make the Show/Hide setting for the brightness/darkness status that is detected by the built-in brightness sensor on the ME remote controller (North America: PAR-U01MEDU, Europe: PAR- U02MEDA). Select [Hide] not to display the brightness/darkness icons on the [Floor] or [Block] display. Select [ ] (yellow) to display the brightness icon when the brightness level in the room reaches the predetermined brightness level.
  • Page 66 (2) In the [Temperature display] section, select the desired display option for the room temperature or the set temperature to be used on the [Floor] or [Block] display. Select [Room temp. (Always)] to display the room temperature at all times, [Room temp. (During operation)] to display the room temperature only during operation, [Set temp.] to display the set temperature at all times, [Room temp.(Always)/Set temp.] to display both the room temperature and set temperature at all times, [Room temp.(During op.)/Set temp.] to display the room temperature only during operation and to display the set...
  • Page 67: Network

    5-2-6. Network Touch [Initial Settings] in the menu bar, and then touch [Network]. Make necessary basic system settings such as LAN settings, M-NET settings, and external input settings for each TE-200, TE-50, and TW-50, and then touch [Save Settings]. A message will appear asking whether or not to restart the controller.
  • Page 68 Only when a TE-50/TW-50 is connected By using a communication error detection function, communication errors between TE-200/TE-50/TW-50 can be displayed on the TE-50’s LCD via TE-200. Detect communication error IP address of TE-200 Select whether “Detect” or “Do not detect” communication error for each IP address.
  • Page 69 (3) Enter [255.255.255.0] in the [Subnet Mask] field (only when the IP address is [192.168.1.*]). Note: If [255.255.255.0] is entered, set the IP addresses of all TE-50 units to [192.168.1.*]. (4) When monitoring the system remotely or using e-mail function via a dial-up router, enter the router IP address in the [Gateway] field.
  • Page 70: Groups

    5-2-7. Groups Touch [Initial Settings] in the menu bar, and then touch [Groups]. Register the groups of air conditioning units to be connected to the TE-200/TE-50/TW-50, and then touch [Save Settings]. Note: Some settings may not be accessible if logged in as a building manager. Note: If the system is connected to a TG-2000A, make or change the settings from the TG-2000A.
  • Page 71 [2] Registering air conditioners to a group (1) To register air conditioners to each group, touch the “Unit selection” button under the target group name. A screen to select the units will appear. Select the group type in the [Model] section, and select the address numbers of the units to be registered.
  • Page 72: Blocks

    5-2-8. Blocks By making block settings, multiple groups in a given block can be collectively monitored or operated. Touch [Initial Settings] in the menu bar, and then touch [Blocks]. Register the groups to each block, and then touch [Save Settings]. Note: Some settings may not be accessible if logged in as a building manager.
  • Page 73: Floor Layout

    5-2-9. Floor Layout The floor layout on the [Floor] display under the [Monitor/Operation] menu can be changed, and the display position of the groups on the floor can be changed. Touch [Initial Settings] in the menu bar, and then touch [Floor Layout]. All unit groups that are under the control of both TE-200 and TE-50 can be displayed on the Floor Layout screen of the TE-200.
  • Page 74 The display range of the area on the [Floor Layout] screen vary, depending on the selected floor layout. Floor layout Display area Floor layout Display area (3) Touch the “Floor level name” button to display the Floor level name keyboard. Enter the floor level name in 3 alphanumeric Floor name or symbol characters or less.
  • Page 75 Available colors (RGB) to be used in the file * Use the colors in the table above, otherwise the floor plan will appear in different colors. * The default background color is RGB [103, 103, 103]. WT09304X01...
  • Page 76 [3] Moving a group to other areas (1) On the [Floor Layout] screen, touch the group icon to be moved. The selected group icon will appear with an orange frame. Note: When the “Unassigned groups” button is touched, groups that have not been assigned to any area will appear in the order of their group numbers.
  • Page 77 (4) Touch [Save Settings]. Note: To move the pasted group icon within the area, refer to [4] “Moving a group within the area” below. [4] Moving a group within the area Note: It is recommended to use a commercially available touch pen. (1) On the [Floor Layout] screen, touch the group icon to be moved.
  • Page 78: System View

    5-2-10. System View Refrigerant system information (connection information of outdoor and indoor units) can be checked for each TE-200, TE-50, and TW-50. Touch [Initial Settings] in the menu bar, and then touch [System View]. Note: This screen shows the information of the units that have been registered to a group and have started up successfully. Note: The [Controller] setting will appear (only on the TE-200’s LCD) when the [System Exp] setting on the [Unit Info.] screen is set to [Expand].
  • Page 79: Floor Layout Settings On The Integrated Centralized Control Web

    5-2-11. Floor Layout settings on the Integrated Centralized Control Web [1] Matching the floor layout on the TE-200’s LCD and the Integrated Centralized Control Web On the Integrated Centralized Control Web, a setting can be made to use the same layout as the one used on the LCD.
  • Page 80: Environment Settings For Integrated Centralized Control Web

    5-3. Environment settings for Integrated Centralized Control Web 5-3-1. Operating environment The following table shows the supported operating systems and browsers for using this Integrated Centralized Control Web with PCs. Item Requirement 1 GHz or faster (2 GHz or faster recommended) Memory 2 GB or more Screen resolution...
  • Page 81: System Settings

    5-3-2. System Settings To use Integrated Centralized Control Web, you need to configure the settings using Initial Setting Tool. Refer to the AE-200/AE-50/EW-50 Instruction Book (Initial Settings) for details. Important ● When using Initial Setting Tool, be sure to configure the settings as described in the procedures of Instruction Book (Initial Settings).
  • Page 82: Setting The Ip Address Of The Pc

    5-3-3. Setting the IP address of the PC Follow the instructions below to set the PC’s IP address to connect the Integrated Centralized Control Web and multiple centralized controllers. The PC’s IP address must have the same network address as the TE-200/TE-50/TW-50’s IP address. (1) Click [Control Panel] in the Start menu.
  • Page 83: Logging In To The Integrated Centralized Control Web

    5-3-4. Logging in to the Integrated Centralized Control Web (1) Enter the web page address in the address field of the Web browser as follows: http://[IP address of the login destination TE-200/TW-50]/control/index.html (2) A login screen will appear. Note: If the IP address of the TE-200/TW-50 is [192.168.1.1], the web page address is [http: //192.168.1.1/control/index.html]. Note: Default IP address of TE-200/TW-50 is [192.168.1.1].
  • Page 84: Maintenance

    6. Maintenance 6-1. Backing up settings data The settings data can be exported to a USB memory as a backup. Touch [Maintenance] in the menu bar, and then touch [Backup]. Note: Use the USB memory device that meets the requirements described in 7 “Specifications”. Note: IP address settings will not be backed up.
  • Page 85: Importing Settings Data

    6-2. Importing settings data The exported data can be imported back to the TE-200/TE-50/TW-50 to restore the previous settings after the controller replacement. Touch [Maintenance] in the menu bar, and then touch [Import]. All settings Read from USB Memory Touch to import the settings data.
  • Page 86: Software Update

    6-3. Software Update Refer to the TE-200/TE-50 Installation Manual for how to update the software for TE-200/TE-50. 6-4. Software information Detailed information about the open source software of the TE-200/TE-50/TW-50 can be checked by accessing the following address: https://[IP address of each TE-200, TE-50, or TW-50]/license/ * Accessible only if logged in as a maintenance user.
  • Page 87: Specifications

    7. Specifications Item Specifications Power supply Rated input 100–240 VAC ± 10%; 0.3–0.2 A 50/60 Hz Single-phase M-NET power feeding coefficient 0.75 Network interface 100BASE-TX Operating temperature 0°C – +40°C (+32°F – +104°F) range Temperature Ambient Storage temperature conditions -20°C – +60°C (-4°F – +140°F) range Humidity 30%–90% RH (Non-condensing)
  • Page 88 This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation.
  • Page 89 WT09304X01...
  • Page 90 WT09304X01...
  • Page 91 WT09304X01...
  • Page 92 This product is designed and intended for use in the residential, commercial and light-industrial environment. The product at hand is based on the following EU regulations: • Low Voltage Directive 2014/35/EU • Electromagnetic Compatibility Directive 2014/30/EU Please be sure to put the contact address/telephone number on this manual before handing it to the customer.