◆ Specifications

Item
Ambient operating temperature
Operating & storage humidity
Dimensions
Weight
Applicable
Wire strip length
wire size
Tightening torque range
ground wire
Working environment
Standards
Noise resistance
Vibration resistance
Shock resistance
RoHS2
Item
Rated input voltage
Power supply composition
Current consumption
Figure 2.1 Example of connection
Table 3.1 General specifications
Solid wire
UL
CE
FCC
By noise simulator of 500Vp-p noise voltage, 1μs noise width
Acceleration : 980m/s
Table 3.2 Power supply specifications
Specification
-20℃ to 60℃
95%RH or less (no condensation)
W 23.5 x H 104 x D 80 mm
AWG.16~28
0.5~0.6N・m
AWG.14 or more
Inside panel
UL/IEC61010-2-201
EN55032,EN61000-3-2/3,EN61000-6-2/4
IEC61000-4-2/3/4/5/6/8/11,EN55024
Part 15,Subpart B,Class A
and 25 to 60Hz noise frequency
Frequency : 13.2~100Hz, Acceleration : 4.9m/s
2 hours each in X, Y, Z directions
2
, 3 times each in X, Y, Z directions
Conforms
Specification
DC12V~48V
Redundant supply voltage
250mA (DC24V)
- 3 -
*It can't be used in case of
CC-Link IE Field Basic
220 g
7 mm
2
,