Delta VFD-MS300 Series Quick Setup Instructions

Delta VFD-MS300 Series Quick Setup Instructions

Hide thumbs Also See for VFD-MS300 Series:

Advertisement

Quick Links

Connect Live to R and Neutral to S for single phase input
supply
Connections U/T1, V/T2, W/T3 go to the motor
Connect 3 phase input supply to L1/R, L2/S, L3/T
Connections U/T1, V/T2, W/T3 go to the motor
Instructions for Remote Setup
(Remote On/Off and Speed Variation)
For remote stop and start connect between DCM
and MI1 (FWD) and MI2 (REV) (DCM is your common)
For remote Potentiometer connect the pot to +10V,
AVI and ACM (common).
Set 00.20 to 2 (Remote Potentiometer)
Set 00.21 to 1 (Remote ON/OFF setting)
Set 02.00 to 1 or 2 (2-wire operation control)
Set 02.00 to 3 (3-wire operation control)
V/F curve set up
Factory setting is General purpose
QUICK SETUP INSTRUCTIONS
FOR VARIABLE SPEED DRIVE
1 PHASE TO 3 PHASE
AND
3 PHASE TO 3 PHASE
VFD-MS300 Series
HAMILTON PH: 07 847 3374
CHRISTCHURCH PH: 03 666 3374
sales@rotatingmachinery.co.nz
AUCKLAND PH: 09 271 6063
info@brookmtl.co.nz

Advertisement

loading
Need help?

Need help?

Do you have a question about the VFD-MS300 Series and is the answer not in the manual?

Questions and answers

Summary of Contents for Delta VFD-MS300 Series

  • Page 1 Connect 3 phase input supply to L1/R, L2/S, L3/T Connections U/T1, V/T2, W/T3 go to the motor Set 02.00 to 3 (3-wire operation control) V/F curve set up VFD-MS300 Series Factory setting is General purpose HAMILTON PH: 07 847 3374 CHRISTCHURCH PH: 03 666 3374 sales@rotatingmachinery.co.nz...
  • Page 2 1ph supply VFD the 00. will appear on the screen. 00.21 Source of master Operation Command. motor must be connected in DELTA. For 3ph Press enter again. 0 = Digital keypad (Factory setting ) supply VFD please consult the motors name 00.00 will appear on the screen.