Step3. Press " " or " " to select the item.
Press " " or " " to set value(unit: L/s).
Step4. Select "
OK
return to Step2. Or press " " to return to Step2
without saving the setting.
26.1.7 Minimum Airflow Ratio
Step1. Select "Minimum Airflow Ratio" and press "OK".
Step2. Press " " or " " to select the item.
Press " " or " " to set value.
Step3. Select "
OK
and return to Zone Installation Menu.
Or press " " to return to Zone Installation Menu
without saving the setting.
NOTE:
The value range of Minimum Airflow Ratio is 01~99(%).
26.1.8 Damper Timing
Step1. Select "Damper Timing" and press "OK".
Step2. Press " " or " " to select the item.
Press " " or " " to set value(unit: Sec.).
Step3. Select "
OK
and return to Zone Installation Menu.
Or press " " to return to Zone Installation Menu
without saving the setting.
NOTE:
The value range of Damper Timing is 006~150(Sec.).
52
" and press "OK" to save the setting and
" and press "OK" to save the setting
" and press "OK" to save the setting
26. Premium Zoning Function
Airflow
0
6
0
Zone Installation Menu
Airflow
Minimum Airflow Ratio
Damper Timing
Turn On All Zones
OK Select
Minimum Airflow Ratio
6
0
%
Zone Installation Menu
Airflow
Minimum Airflow Ratio
Damper Timing
Turn On All Zones
OK Select
Damper Timing
0
0
6
Sec.
A16381H9HF
unit: L/s
OK
Back
Back
OK
Back
Back
OK
Back