7.5

Adjusting CO2

The CO2 can only be adjusted by a certified gas technician
with a calibrated CO2 analyzer.
CO
adjustment is required in Natural Gas installations where
2
energy content is less than 900 BTU/cuft, and in installations
with repeated unresolved EA and EC errors (ref. to page 66
"Problem solving").
CAUTION:
▶ One factor that may affect CO
pressure. Please see chapter 4.14 for the procedure to
measure gas pressure and record your findings below:
Static Gas Pressure:
P1 Operating Pressure:
The P1 minimum operating gas pressure is 3.5" WC for Natural
Gas and 8" WC for Propane. Do not proceed in adjusting CO
until pressure is at or above these levels, but not to exceed
10.5" WC for Natural Gas and 13" WC for Propane.
A. Once Gas Pressure is adequate
▶ Press ON/OFF button to turn OFF the heater.
▶ Remove brass flat head screw on the exhaust collar as seen
in fig. 72.
▶ Insert CO
analyzer probe into the measuring port. The tip
2
of the probe should be in the center of the flue pipe (approx
1.5" inserted). Avoid air gaps between probe and
measuring port as they can alter readings.
Fig. 72
Measuring port
▶ Press the ON/OFF button to turn ON the heater.
C 950/C 1050 (Pro TL 175 C/199 C) – 6 720 805 440 (2019/10)
levels is improper gas
2
" WC
" WC
▶ Press and hold simultaneously buttons
for 3 seconds, until display reads P2.
Fig. 73
▶ Press
button until "P1" appears on display.
B. Measuring CO
2
▶ Open all hot water taps to achieve a flow rate of at least 6
gallons per minute. (1 tub and 2 sinks should be sufficient).
If heater display reverts back to P2, open more hot water
fixtures to allow sufficient flow. Press + until P1 reappears
on the display.
▶ Record the CO
take several minutes to stabilize).
▶ Press the '+' button until P2 appears. Unit will ramp down to
2
low fire and the water flow should decrease.
▶ Record the CO
P1 CO
Reading:
2
P2 CO
Reading:
2
Note: When making adjustments, make sure combustion cover
is installed.
CO
C 950ES (Pro
TL 175 C)
Nat. Gas
max. input P1 7.2 % - 7.8 % 7.8 % - 8.4 %
min. input P2 1.5 % - 1.8 % 1.5 % - 1.8 %
LP Gas
max. input P1 8.8 % - 9.4 % 9.5 % - 10.1 % < 250 ppm
min. input P2 1.9 % - 2.2 % 1.9 % - 2.2 %
* Values above are for climate controlled conditions. Inputs
such as gas pressure, heating value of the gas, humidity
and temperature of combustion air all impact CO and CO
values. Changes in these inputs can result in different CO
and CO
values on the same appliance.
2
Table 48 CO & CO target numbers
Maintenance and service
(Combustion cover Installed):
reading in P1 below. (Analyzer reading may
2
reading in P2 below.
2
% CO
2
% CO
2
range (%)
2
C 1050ES
(Pro TL 199 C)
Nat. Gas
LP Gas
+
,
and
P
Max. CO
level
(measured)
< 250 ppm
< 60 ppm
< 60 ppm
2
59