Mitsubishi Electric FR-A520-2.2K Instruction Manual page 134

Transistorized inverter, high function & low acoustic noise
Hide thumbs Also See for FR-A520-2.2K:
Table of Contents

Advertisement

Instruction
No.
Item
Code
3
Run command
HFA
Inverter status
4
H7A
monitor
Running frequency
5
write
HEE
2
(E
PROM)
6
Inverter reset
HFD
7
All clear
HFC
8
User clear
HFC
9
Parameter write
H80 to HE3
10
Parameter read
H00 to H63
Read
H7F
Link
parameter
11
expansion
setting
Write
HFF
Read
H6C
Second
parameter
12
changing
(Code
FF = 1)
Write
HEC
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Description
H00 to HFF: Run command
b0:
b7
b0
b1: Forward rotation (STF)
0
0
0
0
0
0
1
0
b2: Reverse rotation (STR)
(For example 1)
b3:
[Example 1] H02
b4:
b5:
... Forward rotation
b6:
[Example 2] H00
b7:
... Stop
H00 to HFF: Inverter status monitor
b0: Inverter running (RUN) *
b7
b1: Forward rotation (STF)
0
0
0
0
0
0
1
0
b2: Reverse rotation (STR)
(For example 1)
b3: Up to frequency (SU) *
b4: Overload (OL) *
[Example 1] H02
b5: Instantaneous power
... During forward rotation
failure (IPF) *
[Example 2] H80
b6: Frequency detection (FU) *
... Stop due to alarm
b7: Alarm occurrence *
*The output data depends on the Pr. 190 to Pr. 195 settings.
H0000 to H9C40: 0.01Hz increments (hexadecimal)
(0 ≠ 400.00 Hz)
To change the running frequency consecutively, write data to the
inverter RAM. (Instruction code: HED)
H9696: Resets the inverter.
As the inverter is reset on start of communication by the computer, the
inverter cannot send reply data back to the computer.
All parameters return to the factory settings.
Any of four different clear operations is performed according to the data.
Pr.
Communi-
Calibration
cation Pr.
Data
×
H9696
{
H9966
{
{
×
×
H5A5A
×
H55AA
{
When all parameter clear is executed for H9696 or H9966,
communication-related parameter settings also return to the factory
settings. When resuming operation, set the parameters again.
H9669: User clear is made.
Communi-
Calibration
Other Pr.
cation Pr.
×
{
{
Refer to the data list (Appendix 1) and write and/or read parameter
values as required.
Note that some parameters may not be accessible.
H00 to H6C and H80 to HEC parameter values are changed.
H00: Pr. 0 to Pr. 99 values are accessible.
H01: Pr. 100 to Pr. 159 , Pr. 200 to Pr. 231 and Pr. 900 to Pr. 905
values are accessible.
H02: Pr. 160 to Pr. 199 and Pr. 232 to Pr. 285 values are accessible.
H03: Pr. 300 to Pr. 399 values are accessible.
H09: Pr. 990 value is accessible.
When setting the programmed operation
(data code H3D to H5A, H8D to HAD)
parameter
H00: Time
H01: Time
H02: Rotation direction
When setting the bias/gain (data code H5E to H6A, HDE to HED)
parameter
H00: Offset/gain
H01: Analog
H02: Analog value of terminal
121
PARAMETERS
Number
of Data
Digits
2 digits
2 digits
4 digits
4 digits
HEC
Other Pr.
HF3
HFF
{
{
4 digits
{
{
{
{
{
{
HEC
HFC
4 digits
HFF
{
4 digits
2 digits
6 3 3 B
Time (Min.) Min. (Sec.)
2 digits