Connection Of Remote Controller Cable - Fujitsu UTY-TTRXZ1 Installation Manual

Thermostat convertor
Table of Contents

Advertisement

7. CONNECTION OF REMOTE CONTROLLER CABLE

When connecting the remote controller cable to the indoor unit, do not
connect it to the outdoor unit or the power terminal block. It may cause a
failure.
When connecting Indoor unit and
thermostat convertor with the Remote
controller cable, the following items
should be considered.
Remote controller cable
This product
There are 2 methods to connect the remote controller cable to the indoor
unit. One is the connection using connecting cable contained by indoor
unit, and the other is the connection the remote controller cable is con-
nected to the exclusive terminal block of the indoor unit.
Exclusive terminal block for remote controller connection method is differ-
ent depending on each model. Modify the remote controller cable as per
below description and connect it.
(For the details, refer to the installation manual of the indoor unit to be
used.)
When connecting to the connector
(1)
Case 1: For non-polar 2-wire
Use a tool to cut off the terminal on the end of the remote controller cable,
and then remove the insulation from the cut end of the cable as shown
in Fig. 1. Connect the remote controller cable and connecting cable as
shown in Fig. 2. Be sure to insulate between the cables.
Fig.1
Fig.2
13/16 in
Insulated
(20 mm)
connection
Remote controller
cable (Non-polar)
Insert it to the connector. Set to "2WIRE" the DIP switch (SW1) on the
PC board of the indoor unit.
Set to "2WIRE" the
DIP switch (SW1)
Connect to earth
Functional earthing
(ground) screw
(If necessary)
Remote controller
cable (Non-polar)
Connecting cable
* Layout of Connector and PC
board is varies, depending on
the type of indoor unit.
En-5
CAUTION
Indoor unit
Red
White
Black
White
Connecting cable
(The number of terminal
Red
is different depending
Black
on the model.)
Cut and
insulate
Indoor unit
PC board
Connector CNC01
(onboard)
SW1
Connector
(adapter)
Indoor unit
PC board
Case 2: For polar 3-wire
Modify the cable as per below methods.
Use a tool to cut off the terminal on the end of the remote controller
cable, and then remove the insulation from the cut end of the cable as
shown in Fig. 1.
Connect the remote controller cable and connecting cable as shown in
Fig. 2.
Be sure to insulate between the cables.
Fig. 1
13/16 in
(20 mm)
Remote
controller cable
Red
Insert it to the connector.
Connecting cable
Remote controller cable
When the board has the 2WIRE/3WIRE DIP switch on it, set it to
3WIRE.
For how to set, see "Case 1: For non-polar 2-wire".
When connecting to the exclusive terminal block
(2)
Connect the end of remote controller cable directly to the exclusive
terminal block.
If there is the 2WIRE/3WIRE switch on the PC board of the indoor unit,
set it to match the connection method of the connected remote control-
ler cable.
Example) Connection of non-polar 2-wire
Terminal block
Functional earthing
(If necessary)
Remote controller
cable
* Layout of terminal block and
PC board is varies, depending
on the type of indoor unit.
Fig. 2
White
Connector
Red
Black
White
Insulated con-
Connecting
nection
cable
Black
Indoor unit
Connector
PCB
PCB
Terminal block
to outdoor unit /
power supply
Indoor unit
PC board
Set to "2WIRE" the
DIP switch (SW1)

Advertisement

Table of Contents
loading

This manual is also suitable for:

Uty-ttrx

Table of Contents