The module must be in STOP mode with the engine at rest before configuration mode can be accessed.
To enter the 'configuration mode' press both the INFO and STOP buttons together.
If the module PIN number has been set, the PIN number request is then shown. The configuration cannot be viewed or changed until the PIN number is correctly entered.
If the Configuration PIN has been entered successfully (or the PIN number has not been set in the module) the first configurable parameter is displayed.
NOTE:- When is pressed after editing the final PIN digit, the PIN is checked for validity. If the number is not correct, the editor is automatically exited. To retry you must re-enter the editor as described above.
Enter the editor as described above.
NOTE: - Values representing pressure will be displayed in Bar. Values representing temperature are displayed in degrees Celsius.
NOTE: - When the editor is visible, it is exited after 5 minutes of inactivity to ensure security.
NOTE:- To exit the front panel configuration editor at any time, press and hold the (
) button. Ensure you have saved any changes you have made by pressing the
button first.
NOTE:- The PIN number is automatically reset when the editor is exited (manually or automatically) to ensure security.
(Configuration editor)
(Factory default settings are shown in bold italicised text)
Section | Parameter as shown on display | Values |
PIN | Pin Entry | # # # # |
DISPLAY | Contrast | 0% - 100% (53%) |
Language | English - Others | |
LCD Page Timer | hh: mm: ss (5m) | |
Auto Scroll Delay | 1s - 1hr (2s) | |
ALT CONFIG | Default Config | Default Config |
ENGINE | Oil Pressure Low Shutdown | 0bar - 9.97bar (1.03bar) |
Coolant Temperature High Shutdown | 2ºC - 140ºC (95ºC) | |
Start Delay Timer | 0 - 10hr (5s) | |
Pre Heat Timer | 0 - 5m (0s) | |
Crank Duration Timer | 0 - 1m (10s) | |
Crank Rest Timer | 0 - 1m (10s) | |
Safety On Delay | 0 - 1m (10s) | |
Smoke Limiting | 0 - 15m (0s) | |
Smoke Limiting Off | 0 - 1m (0s) | |
Warm Up Timer | 0 -1hr (0s) | |
Cool Down Timer | 0 - 1hr (1m) | |
Speed Low Shutdown | Active, Inactive | |
Speed Low Shutdown | 0RPM - 6000RPM (1270RPM) | |
Speed High Shutdown | 0RPM - 6000RPM (1740RPM) | |
Speed Overshoot Delay | 0-10s (2s) | |
Speed Overshoot | 0% - 10% (0s) | |
Fail To Stop Delay | 0 - 2m (30s) | |
Battery Voltage Low Warning | Active, Inactive | |
Battery Low Voltage | 0V – 40V (10V) | |
Battery voltage Low Warning Delay | 0 - 24hr (1m) | |
Battery Voltage High Warning | Active, Inactive | |
Battery Voltage High Warning Delay | 0V - 24hr (1m) | |
Battery Voltage High Warning | 0V – 40V (30V) | |
Charge Alternator Failure Warning | Active, Inactive | |
Charge Alternator Failure Warning | 0V – 39V (6V) | |
Charge Alternator Failure Warning Delay | 0 - 24hr (5s) | |
Charge Alternator Failure Shutdown | Active, Inactive | |
Charge Alternator Failure Shutdown | 0V – 5.9V (4.0V) | |
Charge Alternator Failure Shutdown Delay | 0 - 24hr (5s) | |
GENERATOR | Voltage Low Shutdown | 50V – 360V (184V) |
Voltage Nominal | 50V – 276V (230V) | |
Voltage High Shutdown | 231V – 360V (277V) | |
Frequency Low Shutdown | 0Hz - 75Hz (43Hz) | |
Frequency Nominal | 0Hz - 75Hz (50Hz) | |
Frequency High Shutdown | 0Hz - 75Hz (58Hz) | |
Full Load Rating | 5A – 6000A (500A) | |
Delayed Over Current | Active, Inactive | |
Delayed Over Current | 50% - 120% (100%) | |
AC System | Single Phase, 2 Wire 3 Phase, 4 Wire 2 Phase, 3 Wire (L1 & L3) 3 Phase, 4 Wire (Delta) 2 Phase, 3 Wire (L1 & L2) 3 Phase, 3 Wire | |
CT Primary | 5A - 6000A (600A) | |
Generator Transient Delay | 0 - 10m (0.7s) | |
MAINS | Voltage Low Trip | 50V – 360V (184V) |
Voltage High Trip | 50V – 360V (276V) | |
Frequency Low Trip | 0Hz - 75Hz (45Hz) | |
Frequency High Trip | 0Hz - 75Hz (55Hz) | |
Mains Transient Delay | 0 - 30s (2s) | |
Return Delay | 0 - 1hr (30s) | |
Mains Transfer Time | 0 - 10m (0.7s) | |
TIMERS | LCD Page Timer | hh: mm: ss (5m) |
Auto Scroll Delay | 1s - 1hr (2s) | |
Pre Heat Timer | 0 - 5m (0s) | |
Crank Duration Timer | 0 - 1m (10s) | |
Crank Rest Timer | 0 - 1m (10s) | |
Safety On Delay | 0 - 1m (10s) | |
Smoke Limiting | 0 - 15m (0s) | |
Smoke Limiting Off | 0 - 1m (0s) | |
Warm Up Timer | 0 -1hr (0s) | |
Cool Down Timer | 0 - 1hr (1m) | |
Fail To Stop Delay | 0 - 2m (30s) | |
Battery voltage Low Warning Delay | 0 - 24hr (1m) | |
Battery Voltage High Warning Delay | 0V - 24hr (1m) | |
Return Delay | 0 - 5hr (30s) | |
Generator Transient Delay | 0.1s - 2m (30s) | |
Mains Transient Delay | 0 - 30s (2s) |
216mm x 158mm x 42mm
(8.5" x 6.2" x 1.6")
182mm x 137mm
(7.2" x 5.4")
510g (0.51kg)
The module is held into the panel fascia using the supplied fixing clips.
NOTE:- In conditions of excessive vibration, mount the panel on suitable anti-vibration mountings.
Here you can download full pdf version of manual, it may contain additional safety instructions, warranty information, FCC rules, etc.