Operation options

6.1

Overview of operation options

6.1.1
Display
1
2
3
1a
4
 9
LC display of the field indicator
1
Bar graph display in increments of 10% with indicators for underranging (item 1a) and overranging (item 1b)
2
Measured value display, status indication "Bad measured value status"
3
14-segment display for units and messages
4
"Communication" symbol
5
"Parameters cannot be modified" symbol
6
Unit "%"
7
"Uncertain measured value status" symbol
The backlit LCD display contains a bar graph (0-100) and arrows to indicate measured
values above or below the measuring range. Analog process values, digital status and
failure codes are displayed in the 7-segment area. Here up to 8 values can be displayed
with an alternating time of between 2 and 20 seconds. Plain text can be displayed in the
14-segment area (text is limited to 16 characters and is scrolled if needed).
The indicator also displays the quality of the measured value. If the status of the displayed
value is ' g ood' (value equal to or above 0x80), no symbol is lit and the indicator remains in
the normal operational state. If the status of the displayed value is ' u ncertain' (value
between 0x40 and 0x7F), the ' U ncertain measured value status' symbol is lit. If the status
is ' b ad' (value below 0x40), within the 7-segment area the display will show "BAD" and the
channel number where the bad value is published. The channel number is also displayed in
the 14-segment area.
6.1.2
Operation options
Two options are available to the operator for configuring and commissioning the device:
1. Configuration programs
The FF functions and device-specific parameters are configured via the fieldbus interface.
Special configuration and operating programs are available from various manufacturers for
this purpose →  18.
Device Description Files are available for download:
device driver → Type → Select product root.
2. Miniature switches (DIP switches) for various hardware settings
!
www.endress.com/download
Operation options
7
6
1b
5
A0012574