OPTIONS FOR ABB DRIVES AND CONVERTERS
FDPI-02 diagnostics and panel interface unit
User's manual

Advertisement

Table of Contents
loading

Summary of Contents for ABB FDPI-02

  • Page 1 — OPTIONS FOR ABB DRIVES AND CONVERTERS FDPI-02 diagnostics and panel interface unit User's manual...
  • Page 3 FDPI-02 diagnostics and panel interface unit User's manual Table of contents 3AUA0000113618 Rev B Original instructions EFFECTIVE: 2023-08-04...
  • Page 5: Table Of Contents

    Installing the FDPI-02 onto the control unit ..........Installing an F-option module onto the installed FDPI-02 .......
  • Page 6 6 Table of contents Further information...
  • Page 7: Introduction To The Manual

    Introduction to the manual Contents of this chapter This chapter introduces this manual. Applicability This manual applies to the FDPI-02 diagnostics and panel interface unit. Compatibility The interface unit is compatible with the following devices: • ZCU-..., BCU-... and UCU-... control units •...
  • Page 8: Terms And Abbreviations

    8 Introduction to the manual Terms and abbreviations Term Description Drive Frequency converter for controlling AC motors Electromagnetic compatibility Printed circuit board Underwriters laboratories Related manuals Appropriate drive firmware manual Appropriate drive hardware manual ACS-AP-... Assistant control panels user’s manual [3AUA0000085685 (English)].
  • Page 9: Hardware Description And Operation Principal

    This chapter briefly describes the operation principle and layout of the interface unit. Product overview FDPI-02 diagnostics and panel interface is used for branching the RS-485 panel bus and chaining a control panel or PC tool to several drives. The interface unit provides a feed-through connection between a control unit and an F-type option module.
  • Page 10 10 Hardware description and operation principal Lock X101 (under the dust seal) Mounting screw Termination switch S1 Slide for chassis/grounding screw, and the screw X100 Connector or Description switch RJ-11 female control unit connector Daisy chain bus terminal 1, RJ-45 shielded female connector for connecting a control panel.
  • Page 11 F-type option. X101 Option slot interface, male connector on the top of the FDPI-02 for connecting a small F-type option to the interface unit and providing a feed-through connection between the control unit and the F-type option.
  • Page 13: Mechanical Installation

    Mechanical installation 13 Mechanical installation Contents of this chapter This chapter contains instructions on installing the interface unit and installing an F-option module onto the interface unit.
  • Page 14: Installing The Fdpi-02 Onto The Control Unit

    Stop the drive and do the Electrical safety precautions in the drive safety instructions before you start the work. On the FDPI-02 interface unit, move the slide for the chassis screw to the right. Insert the interface unit into its designated option slot on the control unit (usually the option slot nearest to the panel bus connector of the control unit).
  • Page 15: Installing An F-Option Module Onto The Installed Fdpi-02

    Mechanical installation 15 Installing an F-option module onto the installed FDPI-02 WARNING! Obey the safety instructions of the drive. If you ignore them, injury or death, or damage to the equipment can occur. If you are not a qualified electrical professional, do not do installation, commissioning or maintenance work.
  • Page 16 16 Mechanical installation...
  • Page 17: Electrical Installation

    Electrical installation 17 Electrical installation Contents of this chapter This chapter contains instructions on connections, bus chaining and bus termination associated with the interface unit.
  • Page 18: Connecting The Fdpi-02 To The Control Unit

    Connecting the FDPI-02 to the control unit Connect the RJ-45 end of the connection cable to the panel bus connector of the control unit. The cable is included in the delivery. Connect the RJ-11 end of the cable to connector X1 of the FDPI-02 unit.
  • Page 19: Connecting A Control Panel To The Fdpi-02

    RS-485 bus (page 34). Connect the other end of the cable to connector X2 of the FDPI-02 unit. Check that termination switch S1 of the FDPI-02 is in the OPEN position. Note: When a control panel is connected to the bus end, it terminates the bus. Only the other end must be terminated by turning termination switch S1 to the TERMINATED position.
  • Page 20 20 Electrical installation...
  • Page 21: Chaining A Control Panel To Several Drives

    Electrical installation 21 Chaining a control panel to several drives You can use the FDPI-02 interface unit for chaining a control panel to several drives. After connecting the first interface unit to the drive’s control unit and the control panel to the interface unit, continue as follows: Install and connect the second interface unit to the second drive’s control unit.
  • Page 22 22 Electrical installation...
  • Page 23: Connecting A Pc To The Fdpi-02

    Electrical installation 23 Connecting a PC to the FDPI-02 You can connect a PC to the FDPI-02 unit either through a control panel or to a commercial USB - RS-485 converter or Ethernet - RS-485 converter. Note: • Never connect the PC to connector X2 of FDPI-02. The panel voltage or LED signals may cause damage to the PC.
  • Page 24: Connecting A Pc Through A Commercial Converter

    Connecting a PC through a commercial converter Note: • Never connect the PC to connector X2 of FDPI-02. The panel voltage or LED signals may cause damage to the PC. • Simultaneous control panel and PC communication is not allowed.
  • Page 25 For information on the converter connectors, see the appropriate converter manual. For more information on the cable, see RS-485 bus. Connect the other end of the cable to connector X3 of the FDPI-02 unit. For the X3 pin information, see section Pin allocation (page 32).
  • Page 26: Chaining A Pc To Several Drives

    Chaining a PC connected to a commercial converter ■ You can use the FDPI-02 interface unit for chaining a PC to several drives through a commercial USB - RS-485 converter or Ethernet - RS-485 converter. After connecting the first FDPI-02 interface unit to the drive’s control unit and the commercial converter to the interface unit, continue as follows: Install and connect the second interface unit to the second drive’s control unit.
  • Page 27 Electrical installation 27 Note: Maximum 32 nodes can be connected to the RS-485 bus. For a chaining example, see section Example: Chaining a PC through a commercial converter on page To enable the panel bus networking, select in the Options menu of the control panel the Select drive menu, then Panel bus and On.
  • Page 28: Panel Bus Termination And Chaining Examples

    In the last FDPI-02 interface unit of the bus, termination switch S1 of the interface unit must be turned to the TERMINATED position. In the following examples, ZCU-13 is used as the control unit.
  • Page 29: Example: Chaining A Pc Through A Control Panel

    Electrical installation 29 Example: Chaining a PC through a control panel ■ The following figure shows how a PC is chained to several drives through a control panel. FDPI-02 FDPI-02 FDPI-02 FDPI-02 TERMINATED X1 X2 X3 X1 X2 X3 X1 X2 X3...
  • Page 30: Example: Connecting Chains To The Pc's Usb Port

    30 Electrical installation Example: Connecting chains to the PC’s USB port ■ The following figure shows how you can connect chains to the PC’s USB ports. FDPI-02 FDPI-02 FDPI-02 FDPI-02 TERMINATED X1 X2 X3 X1 X2 X3 X1 X2 X3...
  • Page 31: Example: Chaining A Pc Through A Commercial Converter

    Electrical installation 31 Example: Chaining a PC through a commercial converter ■ The following figure shows how a PC is chained to several drives through a commercial converter. FDPI-02 FDPI-02 FDPI-02 FDPI-02 TERMINATED X1 X2 X3 X1 X2 X3 X1 X2 X3...
  • Page 32: Pin Allocation

    32 Electrical installation Pin allocation The following tables list the pins of connectors X1, X2 and X3 of FDPI-02. Dir. Description In/Out Transmit / receive differential - signal (RS-485) In/Out Transmit / receive differential + signal (RS-485) LED driver input, open collector...
  • Page 33: Technical Data

    Technical data 33 Technical data Contents of this chapter This chapter contains the technical specifications of the interface unit and the RS-485 bus. General Mounting Into the designated option slot of the BCU-… or ZCUxx control unit (usually the option slot nearest to the panel bus connector of the control unit) Degree of protec- IP20 tion...
  • Page 34: Rs-485 Bus

    Medium Shielded CAT 5e or better Ethernet cable Termination: 120 ohms (with termination switch S1 built in the interface unit) Note: Only the cable connected between the FDPI-02 and the control unit is included in the delivery. Dimension drawings...
  • Page 35 Technical data 35...
  • Page 37 Product and service inquiries Address any inquiries about the product to your local ABB representative, quoting the type designation and serial number of the unit in question. A listing of ABB sales, support and service contacts can be found by navigating to www.abb.com/searchchannels.
  • Page 38 3AUA0000113618B © Copyright 2023 ABB. All rights reserved. Specifications subject to change without notice.