Siemens FDT421 Installation Instructions
Siemens FDT421 Installation Instructions

Siemens FDT421 Installation Instructions

Heat detector

Advertisement

Quick Links

Installation Instructions
Model FDT421
Heat Detector
UL521 listed
These instructions are written in accordance with the
installation guidelines of NFPA 72, National Fire Alarm
Code, and CAN/ULC-S524, The Installation of Fire Alarm
Systems.
CAUTION
DO NOT install this detection device until all construction
is completed.
DO NOT store this detection device where it can be
contaminated by dirt, dust, or humidity.
DETECTOR PLACEMENT
Locate Model FDT421 on the ceiling, at least 4 inches
from the side walls. For an ideal, smooth ceiling
condition, place the detectors at a maximum center
spacing of 50 feet (2500 square
Actual job conditions must determine detector spacing.
Consider environmental factors including ambient
temperature fluctuation, and the nature of the fire
hazard. Room or area configuration and ceiling type
(sloped or flat, smooth or beamed) also dictates
placement.
Drawings provided or approved by Siemens Industry,
Inc., or by its authorized distributors are extremely
important.
The detector placements shown on these
drawings were chosen after a careful evaluation of the
area that is protected. Siemens Industry, Inc.'s
extensive experience in the design of the system
assures the best detector placement by following these
drawings. Sound engineering judgment by qualified
personnel must be followed.
TEMPERATURE – HUMIDITY – PRESSURE
The temperature range for the FDT421 detector is 32°F
(0°C) to 100°F (38°C). The thermal alarm temperature
depends on the parameter selected. Use the detector in
environments where the humidity does not exceed 95%
(non-condensing). Normal changes of atmospheric
pressure do not affect detector sensitivity.
A6V10323930_c_en_--
2020-07-14
Scan for electronic version
feet).
LED INDICATOR OPERATION
The Model FDT421 contains an LED indicator capable of
flashing either one of three distinct colors: green, yellow,
or red. The microprocessor-based detector monitors the
following:
·
Internal sensors and electronics
Based on the results of the monitoring, the LED indicator
flashes the following:
Flash
Condition
Color
Normal supervisory operation.
Green *
Detector is in trouble and needs
Yellow
replacement.
Red
Alarm
No
Detector is not powered, or
Flashes
replacement is needed.
* LED can be turned off. Please follow the corresponding
description of the Panel used.
Figure 1
Flash Interval
(Seconds)
10
4
1
SIEMENS Industry, Inc.
Smart Infrastructure

Advertisement

loading

Summary of Contents for Siemens FDT421

  • Page 1 Flash Interval Color (Seconds) DETECTOR PLACEMENT Normal supervisory operation. Locate Model FDT421 on the ceiling, at least 4 inches Green * from the side walls. For an ideal, smooth ceiling Detector is in trouble and needs Yellow condition, place the detectors at a maximum center replacement.
  • Page 2 Line -6 and -5 can be either line of the loop. Under no circumstances is the detector head to be When the FDT421 is wired for Isolator mode, the positive disassembled. line needs to be connected to 1b and the negative line to No repairs should be attempted.
  • Page 3 END OF LINE DEVICE TO NEXT BASE * FDT421 is a polarity insensitive detector. Line 1 and Line 2 can be either line of the loop. ** The relay contacts are shown after System reset, which represents the non-alarm condition.
  • Page 4 Siemens Industry, Inc. Siemens Canada Limited Smart Infrastructure Smart Infrastructure 8, Fernwood Road 2 Kenview Boulevard Florham Park, New Jersey 07932 Brampton, Ontario L6T 5E4 © Siemens Industry, Inc. www.siemens.com/buildingtechnologies Canada Data and design subject to change without notice. A6V10323930_c_en_-- P/N A5Q00041075...