Troubleshooting; Installation Verification - Huawei DTSU666-HW/YD Series Quick Manual

Smart power sensor
Table of Contents

Advertisement

Modify user password:
5

Troubleshooting

Symptom
1. The cable connection is incorrect.
No display after
2. The voltage supplied to the meter
power-on
1. The RS485 communication cable is
Abnormal
RS485
2. The communication address, baud
communication
1. The cable connection is incorrect.
Inaccurate
2. Check whether the high and low
metering
6

Installation Verification

1. Check that all mounting brackets are securely installed and all screws are tightened.
2. Check that all cables are reliably connected in correct polarity without short circuit.
Cause Analysis
is abnormal.
disconnected, short-circuited, or
reversely connected.
rate, data bit, and parity bit of the
meter do not match those of the
inverter.
Check whether the corresponding
phase sequence of voltage and
current is correct.
ends of the current transformer
inlet are reversely connected. If
the values Pa, Pb, and Pc are
negative, the high and low ends
are connected incorrectly.
Troubleshooting Method
1. Connect the cables correctly
(see wiring diagrams).
2. Supply the correct voltage
based on the specifications.
1. If the communication cable is
faulty, replace it.
2. Set the communication
address, baud rate, data bit,
and parity bit of the meter to
be the same as those of the
inverter by pressing buttons.
For details, see "Parameter
Settings".
1. Connect the cables correctly
(see wiring diagrams).
2. If a negative value is displayed,
change the cable connection
for the current transformer to
ensure that the high and low
ends are connected correctly.
13