Hitachi Relion REL670 Product Manual page 97

Line distance protection
Hide thumbs Also See for Relion REL670:
Table of Contents

Advertisement

Line distance protection REL670
Version 2.2
Table 62. Stub protection STBPTOC
Function
Operating current
Reset ratio
Independenttime delay at 0 to 2 x I
Operate time, start at 0 to 2 x I
Reset time, start at 2 x I
to 0
set
Operate time, start at 0 to 5 x I
Reset time, start at 5 x I
to 0
set
Critical impulse time
Impulse margin time
Table 63. Pole discordance protection CCPDSC
Function
Operate current
Independent time delay between trip
condition and trip signal
Table 64. Directional underpower protection GUPPDUP
Function
Power level
for Step 1 and Step 2
Characteristic angle
for Step 1 and Step 2
Independent time delay to operate for Step 1
and Step 2 at 2 x S
to 0.5 x S
r
Hitachi Energy
Range or value
(5-2500)% of IBase
>95% at (50- 2500)% of IBase
(0.000-60.000) s
set
Min.= 10 ms
set
Max.= 25 ms
Min.= 10 ms
Max.= 25 ms
Min.= 5 ms
set
Max.= 20 ms
Min.= 15 ms
Max.= 30 ms
10 ms typically at 0 to 2 x I
15 ms typically
Range or value
(0–100)% of IBase
(0.000-60.000) s
Range or value
(0.0–500.0)% of SBase
(-180.0–180.0) degrees
(0.01-6000.00) s
and k=0.000
r
© 2017 - 2022 Hitachi Energy. All rights reserved
M12350-1 v13
set
M13279-1 v10
Accuracy
±1.0% of I
±0.2% or ± 30 ms whichever is greater
SEMOD175152-2 v11
Accuracy
±1.0% of S
±1.0% of S at S > S
where
=
S
1.732
r
±2.0 degrees
±0.2% or ±40 ms whichever is greater
1MRK 506 372-BEN Q
Accuracy
± 1.0% of I
at I ≤ I
r
r
± 1.0% of I at I > I
r
±0.2% or ±30 ms whichever is greater
r
at S ≤ S
r
r
r
×
×
U
I
r
r
97