Operation

Note:
Setup can be done in the field with the Pointek CLS 100 mounted into process, or in the
shop prior to mounting.
Unscrew the clip to access the terminals.
Start Up
After the CLS 100 is properly mounted and wired, apply power to the unit. The green LED
lights to indicate the unit is powered and operational.
LED Indicators
Yellow = sensor status
Red = output status
Green = power
Alarm Output
Setpoint Adjustment
As a guide to adjusting the alarm set point for reliable and accurate detection of the
process material, we have classified the materials and applications into three cases.
Follow the setup procedure associated with the case outline describing your application.
Please note that sensitivity of the unit can be adjusted by the user as required.
POWER
SENSITIVITY
ADJUSTMENT
SENSOR
STATUS
OUTPUT
STATUS
Page EN-10
• ON indicates contact with the process material (material capacitance is
greater than the set point).
• OFF indicates when the sensor is out of contact with the process
material (material capacitance is less than the set point).
• ON indicates the mA loop alarm and solid state switch contact status.
Refer to Alarm Output Status on page 6.
• ON indicates the CLS 100 is properly powered.
20-turn trimpot
Pointek CLS 100 – QUICK START MANUAL