The B208 Octo-input Module is an 8 point supervised expansion device that connects to control panels through the SDI2 bus. This module communicates back to the control panel all point status changes. The inputs are accessed through on-board screw terminal connections.
Figure 1.1: Board overview
Callout ― Description
Two address switches determine the address for the B208 Octo-input Module. The control panel uses the address for communications. The address also determines the output numbers. Use a slotted screwdriver to set the two address switches.
NOTICE!
The module reads the address switch setting only during power up. If you change the switches after you apply power to the module, you must cycle the power to the module to enable the new setting.
Set the address switches per the control panel configuration. If multiple B208 modules reside on the same system, each B208 module must have a unique address.
The module's address switches provide a tens and ones value for the module's address. For single-digit address numbers 1 through 9, set the tens switch to 0 and the ones digit to the appropriate number. Figure 2.1 shows the address switches setting for addresses 1 and 11.
Figure 2.1: Address switches
Valid B208 addresses are dependent on the number of points allowed by a particular control panel. Addresses higher than 32 require B208 firmware version 1.03.003 or higher.
Control panel | Valid B208 addresses | Corresponding point numbers |
B9512G | 01 - 59 | 11 - 18, 21 - 28, 31 - 38, 41 - 48, 51 - 58, 61 - 68, 71 - 78, 81 - 88, 91 - 98, 101 - 108, 111 - 118, 121 - 128, 131 - 138, 141 - 148, 151 - 158, 161 - 168, 171 - 178, 181 - 188, 191 - 198, 201 - 208, 211 - 218, 221 - 228, 231 - 238, 241 - 248, 251 - 258, 261 - 268, 271 - 278, 281 - 288, 291 - 298, 301 - 308, 311 - 318, 321 - 328, 331 - 338, 341 - 348, 351 - 358, 361 - 368, 371 - 378, 381 - 388, 391 - 398, 401 - 408, 411 - 418, 421 - 428, 431 - 438, 441 - 448, 451 - 458, 461 - 468, 471 - 478, 481 - 488, 491 - 498, 501 - 508, 511 - 518, 521 - 528, 531 - 538, 541 - 548, 551 - 558, 561 - 568, 571 - 578, 581 - 588, 591 - 598 |
B8512G | 01 - 09 | 11 - 18, 21 - 28, 31 - 38, 41 - 48, 51 - 58, 61 - 68, 71 - 78, 81 - 88, 91 - 98 |
B6512 | 01 - 09 | 11 - 18, 21 - 28, 31 - 38, 41 - 48, 51 - 58, 61 - 68, 71 - 78, 81 - 88, 91 - 96 |
B5512 | 01 - 04 | 11 - 18, 21 - 28, 31 - 38, 41 - 48 |
B4512 | 01 - 02 | 11 - 18, 21 - 28 |
D9412GV4 | 01 - 24 | 11 - 18, 21 - 28, 31 - 38, 41 - 48, 51 - 58, 61 - 68, 71 - 78, 81 - 88, 91 - 98, 101 - 108, 111 - 118, 121 - 127, 131 - 138, 141 - 148, 151 - 158, 161 - 168, 171 - 178, 181 - 188, 191 - 198, 201 - 208, 211 - 218, 221 - 228, 231 - 238, 241 - 247 |
D7412GV4 | 01 - 07 | 11 - 18, 21 - 28, 31 - 38, 41 - 48, 51 - 58, 61 - 68, 71 - 75 |
D7212GV4 | 01 - 03 | 11 - 18, 21 - 28, 31 - 38 |
To determine the point numbers for each address, multiply the address number by 10 for the base number, and then use numbers 1 through 8 in the ones place for the point numbers.
After you set the address switches for the proper address, install the module in the enclosure, and then wire it to the control panel.
Remove all power (AC and battery) before making any connections. Failure to do so might result in personal injury and/or equipment damage.
Mount the module into the enclosure's 3-hole mounting pattern using the supplied mounting screws and mounting bracket. Refer to Figure 3.1.
Figure 3.1: Mounting the module in the enclosure
Callout ― Description
You can connect an optional enclosure door tamper switch for one module in an enclosure. Installing the optional tamper switch:
When you wire the module to a control panel, you can use either the module's terminal strip labeled with PWR, A, B, and COM, or the module's interconnect wiring connectors (wire included). Interconnect wiring parallels the PWR, A, B, and COM terminals on the terminal strip. Figure 1.1 indicates the location of both the terminal strip and the interconnect connectors on the module. Refer to Figures 3.2, 3.3, and 3.4.
NOTICE!
Use either the terminal strip wiring or interconnect wiring connector to the control panel. Do not use both. When connecting multiple modules, you can combine terminal strip and interconnect wiring connectors in series.
Figure 3.2: Using terminal strip or interconnect cable wiring D9412GV4 shown)
Callout ― Description
Figure 3.3: Installing multiple modules using the SDI2 terminal strip (D9412GV4 shown)
Callout ― Description
Figure 3.4: Installing multiple modules using the SDI2 interconnect wiring connector (D9412GV4 shown)
Callout ― Description
Wire resistance on each sensor loop must be less than 100 Ω with the detection devices connected. The terminal strip supports 12 to 22 AWG (0.65 to 2 mm) wires.
The B208 detects open, short, normal, and ground fault circuit conditions on its sensor loops and transmits the conditions to the control panel. Each sensor loop is assigned a point number and transmits to the control panel individually. Run wires away from the premises telephone and AC wiring. For the 1 kΩ dual EOL resistor circuit style order ICP-1K22AWG-10, a package of 10 1.0 kΩ EOL resistors.
Figure 3.5: Sensor loop wiring single (upper) and dual (lower)
Callout ― Description
Dual EOL requires B208 firmware v1.05.001 or higher. Dual EOL meets the requirement of double protection for medium to high risk ULC installations.
The module includes one blue heartbeat LED to indicate that the module has power and to indicate the module's current state. Refer to Table 4.1.
Flash Pattern | Function |
Flashes once every 1 sec![]() | Normal state: Indicates normal operation state. |
3 quick flashes every 1 sec![]() | Communication error state: Indicates (the module is in a "no communication state") resulting in an SDI2 communication error. |
ON Steady![]() | LED trouble state: Module is not powered (for OFF Steady only), or some other trouble condition prohibits the module from controlling the heartbeat LED. |
OFF Steady![]() |
To show the firmware version using an LED flash pattern:
When the tamper switch is activated, the heartbeat LED stays OFF for 3 seconds before indicating the firmware version. The LED pulses the major, minor, and micro digits of the firmware version, with a 1 second pause after each digit. In the following example, the version 1.4.3 shows as LED flashes:
[3 second pause] [3 second pause, then normal operation].
Region | |
USA | UL 365 - Police Station Connected Burglar Alarm Units and Systems |
UL 609 - Local Burglar Alarm Units and Systems | |
UL 636 - Holdup Alarm Units and Systems | |
UL 864 - Control Units and Accessories for Fire Alarm Systems (Commercial Fire) | |
UL 985 - Household Fire Warning System Units | |
UL 1023 - Household Burglar Alarm System Units | |
UL 1076 - Proprietary Burglar Alarm Units and Systems | |
UL 1610 - Central Station Burglar Alarm Units | |
CSFM - California Office of The State Fire Marshall | |
FCC Part 15 Class B | |
FDNY - Fire Department of New York | |
FM 3010 - Fire Alarm Signaling Systems | |
Canada | CAN/ULC S303 - Local Burglar Alarm Units and Systems |
CAN/ULC S304 - Signal Receiving Centre and Premise | |
ICES-003 - Information Technology Equipment (ITE) | |
ULC-ORD C1023 - Household Burglar Alarm System Units | |
ULC-ORD C1076 - Proprietary Burglar Alarm Units and System |
Dimensions | 2.5 in x 3.8 in x 0.60 in (63.75 mm x 96 mm x 15.25 mm) |
Voltage (operating) | 12 V nominal |
Current (maximum) | 35 mA |
Operating temperature | +32°F to +122°F (0°C to +50°C) |
Relative humidity | 5% to 93% at +90°F (+32°C) noncondensing |
Loop inputs | Up to eight inputs. Input contacts may be Normally Open (NO) or Normally Closed (NC). NOTICE! Normally Closed (NC) is not permitted in Fire installations. |
Loop End-ofLine (EOL) resistance | 1 kΩ, 2 kΩ, No EOL (Dual 1 kΩ + 1 kΩ) |
Loop wiring resistance | 100 Ω maximum |
Loop states (Single EOL resistor circuit style) | Short: 0 - 1.1 VDC Normal: 1.25 - 1.9 VDC Open: 2.25 - 5 VDC |
Terminal wire size | 12 AWG to 22 AWG (2 mm to 0.65 mm) |
SDI2 wiring | Maximum distance - Wire size (Unshielded wire only): 1000 ft (305 m) - 22 AWG (0.65 mm) 1000 ft (305 m) - 18 AWG (1.02 mm) |
Compatibility | B9512G/B9512G-E B8512G/B8512G-E B6512 B5512/B5512E B4512/B4512E D9412GV4 D7412GV4 D7212GV4 (Refer to the control panel installation document for number of supported devices.) |
For B208 address 01 the point numbers for the input devices are 11 through 18:
Terminal no | 1 | 2 | 3 | 4 | 5 | 6 | 7 | 8 |
Input no | 11 | 12 | 13 | 14 | 15 | 16 | 17 | 18 |
For B208 address 11 the point numbers for the input devices are 111 through 118:
Terminal no | 1 | 2 | 3 | 4 | 5 | 6 | 7 | 8 |
Input no | 111 | 112 | 113 | 114 | 115 | 116 | 117 | 118 |
Here you can download full pdf version of manual, it may contain additional safety instructions, warranty information, FCC rules, etc.