I1-I2 are connected to terminal block J7: 1-2 and terminal block J8:1-2.
Input I1
Input I2
See also chapter Programmable inputs in EBLOne Planning instructions.

4.5. RELAY OUTPUTS FOR ROUTING EQUIPMENT (TX)

Not programmable outputs.
R1-R2 are connected to terminal block J7: 3-4 and terminal block J8:3-4.
Fire brigade TX
Fault TX
4.5.1.

FIRE ALARM OUTPUT

This output is normally used for fire brigade tx. All three jumpers on JP1 shall be open.
It is a change-over relay contact that will be activated when a fire alarm is generated in the system. The relay output is normally
closed. The output will be open during fire alarm.
4.5.2.

FAULT CONDITION OUTPUT

This output is normally used for fault warning routing equipment (fault tx). All three jumpers on JP2 shall be open.
It is a changeover relay contact that is normally activated and will be de-activated in case of a fault in the CIE. Also when the CIE is
out of power or watch-dog fault. The relay output is normally closed. The output will be open during fault condition.