Check item
2
PC connection check
No.
1
Start the browser software of the PC to be connected.
2
Enter http://the controller's IP address/**/index.html in the address bar of the browser, and
check that the login window is displayed.
(**: language code)
English
http://192.168.2.30/en/index.html
German
http://192.168.2.30/de/index.html
Italian
http://192.168.2.30/it/index.html
French
http://192.168.2.30/fr/index.html
Spanish
http://192.168.2.30/es/index.html
Chinese
http://192.168.2.30/cn/index.html
Portuguese
http://192.168.2.30/pt/index.html
Turkish
http://192.168.2.30/tr/index.html
Russian
http://192.168.2.30/ru/index.html
Greek
http://192.168.2.30/gr/index.html
Dutch
http://192.168.2.30/nl/index.html
Czech
http://192.168.2.30/cz/index.html
Croatian
http://192.168.2.30/hr/index.html
(192.168.2.30: IP address factory default)
×
NG1:
Network Error
×
NG2:
The server is not found.
OK:
The logon window is
displayed.
3
After entering TCC in User Name and TCC in Password, click "Logon" and make sure that
you can successfully logon.
×
NG1:
The dialog message,
"Logon failed." appears.
×
NG2:
The dialog message "No
response from the
server." or "The system
is being prepared."
appears.
×
NG3:
The dialog message
"The system is stopped."
appears.
OK:
The list window displays
the indoor units set in the
setting file.
33
Procedure
Error message
1) Check if the browser proxy is correctly set.
1) Check if the network wiring is correctly installed. (Refer
to "14-1. Network wiring")
2) Check if the PC's IP address is correct.
(Refer to "14-2. PC's IP address")
3) Check if the controller's IP address is correct. (Refer to
"14-3. Controller's IP address")
1) Proceed to the logon check.
Error message
1) The user name or password entered are incorrect.
Logon again with all the characters in upper case.
1) The controller is being initialized during the startup
process. Wait for 5 minutes and logon again.
1) Close the browser and turn off the controller. Wait for
30 seconds and turn on the controller. Wait for 5
minutes and logon again.
2) If the dialog message "The system is stopping."
appears again, initialize the setting file with the Setting
File Creation Software and turn off the controller.Wait
for 30 seconds and turn on the controller. Wait for 5
minutes and logon again.
3) When successfully logging on after the initialization,
upload again the setting file created, and check that
you can logon.
1) Proceed to the next check.