NO.
Item
6
Cold air
1. In heating operation, the upper limit of the fan tap is set according to the lower of
discharge
whichever is the higher between TC2 sensor and TCJ sensor temperatures, on the
prevention
one hand, and TC1 sensor temperature, on the other.
control
• If the fan continuously operates in zone B for 6 minutes, it automatically moves
• During defrosting, the control point is shifted by +6°C.
7
Freeze
1. During cooling, the air conditioner is operated in the manner described below
prevention
according to the temperature readings of the TC1, TC2 and TCJ sensors.
control (low
• If zone J operation is detected for 5 minutes, the air conditioner is forced into
temp. release)
• In zone K, the timer is put on pause, with the current timer count retained.
• If zone I operation is detected, the timer count is cleared, and the air conditioner
• If continuous zone J operation forces the air conditioner into thermostat OFF, the
Termination conditions
1) TC1 ≥ 12°C, TC2 ≥ 12°C, and TCJ ≥ 12°C
2) Passage of 20 minutes after stoppage
(°C)
2. During cooling, the air conditioner is operated in the manner described below
according to the temperature readings of the TC2 and TCJ sensors.
• If zone M operation is detected for 45 minutes, the air conditioner is forced into
• In zone N, the timer is put on pause, with the current timer count retained.
• When the air conditioner goes back into zone M, timer count is resumed from the
• If zone L operation is detected, the timer count is cleared, and the air conditioner
(°C)
P2
Q2
Reset conditions
1) TC1 ≥ 12°C, TC2 ≥ 12°C and TCJ ≥ 12°C
2) Passage of 20 minutes after stoppage
Specification outline
into zone C.
(°C)
32
D
30
C
28
26
20
16
A
thermostat OFF.
returns to normal operation.
indoor fan is operated in breeze mode until it moves into zone I.
The control is terminated under the following conditions:
I
P1
K
Q1
J
thermostat OFF.
retained value.
returns to normal operation.
L
N
M
Zone A:OFF
Zone B:26 °C or above and
below 28 °C
E
Breeze
Zone C:28 °C or above and
below 30 °C
Low
Zone D:30 °C or above and
below 32 °C
Medium
Zone E:High
B
TC1
TC2, TCJ
P1
10°C(5°C)
a
Q1
0°C
Temperature in ( ): If the temperature is below
this value when the power is turned on, the
air conditioner is forced into thermostat OFF.
TC2, TCJ
P2
5
Q2
-2.0
– 74 –
TCJ: Indoor heat
exchanger sensor
temperature
• In zones D and E,
• In zone A,
TC1: Indoor heat
exchanger sensor
temperature
-10°C
-14°C
* With models
Remarks
priority is given to
the remote
controller fan
speed setting.
"HEATING
STANDBY
" is
displayed.
without TC2, TC2
is not part of the
control
parameters.