Oil Supply; Single Pipe Gravity Feed System; Double Pipe Sub-Gravity Feed System; Single Pipe Suction Lift With De-Aerator - Bosch WORCESTER Danesmoor Utility Regular 2022+ 12/18 Installation, Commissioning And Servicing Instruction Manual

Floor standing oil-fired condensing boiler using conventional flue & room sealed flue
Table of Contents

Advertisement

Pre-Installation
4.3

Oil supply

NOTICE: Contaminated oil supplies can damage the
appliance.
Failure to ensure that the oil supply is clear of
contaminants may invalidate the appliance warranty.
▶ Ensure the oil supply is free of contaminates and
measures are taken to prevent contamination of the
appliance.
NOTICE: Liquid fuel supply pipes should be provided
with mains equipotential bonding in accordance with BS
7671.
• This appliance is suitable for Kerosene (Class C2) only, no other
fuel must be used.
• Plastic or steel tanks should be installed to BS 5410.
A steel tank should conform to BS 799: part 5 and have a slope of
1:24 away from the outlet with a sludge cock at the lower end.
• Do not use galvanised steel tanks or pipework for the oil system.
• Do not use soldered joints on the oil supply pipework.
Key to Oil supply illustrations, figures 5, 6 & 7
1
Oil storage tank
2
Full base (plastic tank)
3
Isolating valve
4
Oil strainer and water separator
5
Fire valve to BS 5410
6
External wall
7
Oil filter (70μm max filtration size)
8
Fire valve sensor
9
Oil pump
10
Oil burner
11
Non-return valve
12
De-aerator
13
Appliance isolation valve
14
Sleeve
Table 4 Key to oil supply feed system
4.3.1

Single pipe gravity feed system:

The oil storage tank [1] must be positioned so that the oil level does not
exceed 4 metres above the level of the burner oil pump [9] and in
addition the oil level must be at least 300mm above the oil pump [9].
Where the maximum oil level in the oil storage tank exceeds 4 metres, a
head breaking device must be installed between the tank [1] and the
burner oil pump [9].
1
2
3
4
Fig. 5
Single pipe feed
All dimensions are in metres unless otherwise stated.
The maximum pipe run figures are based on using
copper pipe with an inside diameter of 2mm less than
the outside diameter.
Maximum pipe run for single pipe suction lift with de-aerator
12
6
8
14
9
10
14
3
7
5
13
6720813284-08.3Wo
Maximum pipe run for single pipe gravity fed system
Head (m) 10mmØ 12mmØ
0.5
12
30
1.0
25
69
1.5
37
91
2.0
49
100
4.3.2

Double pipe sub-gravity feed system:

Maximum suction height 3.5 m. Non-return valves must be fitted to the
inlet and return oil line between the oil pump [9] and oil storage tank [1].
1
11
150mm
2
3
4
Fig. 6
Double pipe feed
Maximum pipe run for double pipe sub-gravity fed system
Head (m) 10mmØ 12mmØ
0
50
100
0.5
44
100
1.0
38
95
1.5
32
80
4.3.3

Single pipe suction lift with de-aerator:

Maximum suction height 3.5 metres. The oil tank [1] must be positioned
below the oil pump [9]. Create an inlet and return loop between the de-
aerator [12] and oil pump [9].
A non-return valve must be incorporated within the de-aerator or fitted
to the oil line between the oil storage tank [1] and the de-aerator [12].
A top feed oil tank fitted with a de-aerator using an internal non-return
valve should have any non-return valves fitted in the base of the tank to
the suction line removed to assist purging air from the oil line.
1
2
3
4
Fig. 7
De-aerator feed
Greenstar Danesmoor Utility
2022+
and Utility System
Head (m) 10mmØ 12mmØ
2.5
62
100
3.0
74
100
3.5
87
100
4.0
99
100
6
14
8
5
9
10
3
7
13
14
6720813284-09.2Wo
Head (m) 10mmØ 12mmØ
2.0
26
66
2.5
20
50
3.0
14
37
3.5
8
22
12
6
8
14
9
10
5
14
3
7
13
2022+