Model Specifications
Table 14. Environmental and Safety (Continued)
* for output cable < 10m.
Agency Markings*
Operating Temperatures
Storage Temperatures
Transit Temperature
Relative Humidity
Operating Altitude
Transit Altitude
Audible Noise
Table 15. Battery
Rack / Tower configuration
Type
Monitoring
EBM Battery Cable Length
46
Eaton 9PX Lithium-Ion
Internal Batteries
1000VA: 48Vdc
1500VA: 48Vdc
2000VA: 72Vdc
3000VA: 72Vdc
Lithium Iron Phosphate (LFP) battery module
Lithium-Ion float service life 8 years /25°C
Advanced monitoring for earlier failure detection and warning
350 mm / 13.78 in
P-164001006—Rev 01
IEC 61000-4-5, (Surges): 2 kV Differentiel Mode / 4 kV Common
Mode /
1 kV Ethernet
IEC 61000-4-6, (Electromagnetic field): 10 V
IEC 61000-4-8, (Conducted magnetic field): 30 A/m
CE / cULus / NOM /EAC/RCM/KC/ Energy Star
0 to 40°C (32 to 104°F) in Online mode, with linear derating for
altitude
Note: thermal protection switches load to Bypass in case of
overheating.
0 to 35°C (32 to 104°F) with batteries
-25 to 55°C (-13 to 130°F) without batteries
-25 to 55°C (-13 to 130°F)
0 to 96% no condensing
Up to 3,000 meters (9,843 ft) above sea level, no derating for
35°c (95°F) room temperature
Up to 10,000 meters (32,808 ft) above sea level
< 47 dBA at 1 meter typical
EBM
9PXEBM48RT: 48Vdc
9PXEBM72RT: 72Vdc